background image

16

Settings

E

Low Compensation

    Adjusting the Low Compensation Value:

 In case the Cosine value 

stays under the Low Compensation Value for 3 minutes although the 

device activates all steps, it enters an undercompensation error, the 

alarm relay is energized, the LOW led flashes while the alarm and 

SETTINGS leds are constantly lit. When the cosine value returns to the 

normal level for 10 seconds, the device disables the 

undercompensation error, the alarm relay is deactivated, the alarm 

and LOW led turn off, the cosine led turns on.
    After entering the settings menu, the first parameter displayed on the 

screen is Pr1: Current Transformer Ratio. Press the DOWN button to access 

Pr9: Low Compensation Time p  arameter. To see the parameter value, press 

the "SET" button and see that the led of the Pr9 parameter is blinking.
    When the parameter led is blinking, you can change the value of the 

parameter by using the DOWN and UP buttons. After changing the value 

of the parameter, press the SET button to save and press the ESC button 

to return to the previous menu without saving. 
    When the changed parameter value is saved by pressing the SET button, the device 

returns to the previous menu, the parameter value is displayed on the screen and the 

parameter led does not blink, it lights up steadily. When the changed parameter value is 

saved by pressing the SET button, the device returns to the previous menu, the parameter 

value is displayed on the screen and the parameter led does not blink, it lights up steadily. 

8 8 8 8

- 9 8 5

.

.

. .

8 8 8 8

- 9 8 5

.

. . .

8 8 8 8

0 0 1 0

.

.

. .

SET

(2sec.)

8 8 8 8

0 0 1 5

.

.

. .

Settings

E

Harmonic Voltage

    Adjusting the THD-V Value:

 If the Total Harmonic Distortion Voltage 

(THD-V) value stays above the THD-V Set value for 15 seconds, the 

device enters a THD-V error, it stops compensation, the alarm relay 

isenergized (it deacitivates all steps), the alarm led turns on and the 

THDV led (Pr10: THD -V Set) flashes. When the THD-V value stays 

below 3% of the THD-V set value for 15 seconds, the device disables 

the THD-V error, the alarm relay is deenergized, the alarm and THD-V 

led (Pr10: THD-V Set) turns off, the Cosine led turns on. The device 

restarts compensation.
    After entering the settings menu, the first parameter displayed on 

the screen is Pr1: Current Transformer Ratio. Press the DOWN button 

to access Pr10: TDH-V Set    parameter. To see the parameter value, 

press the "SET" button and see that the led of the Pr10 parameter is 

blinking.
    When the parameter led is blinking, you can change the value of the 

parameter by using the DOWN and UP buttons. After changing the 

value of the parameter, press the SET button to save and press the 

ESC button to return to the previous menu without saving. 
    When the changed parameter value is saved by pressing the SET 

button, the device returns to the previous menu, the parameter value 

is displayed on the screen and the parameter led does not blink, it 

lights up steadily.     

8 8 8 8

- 9 8 5

.

.

. .

8 8 8 8

- 9 8 5

.

. . .

8 8 8 8

1 0

.

. . .

SET

(2sec.)

8 8 8 8

1 5

.

. . .

Example: 

Let Cosine set: 0.940, Cosine tolerance: 10 and low compensation: 10. If the cosine value stays 

under 0.920 for 3 minutes even though it activates all steps, this error occurs. If the cosine value goes 

above 0.930 for 10 seconds after the error, the error situation will disappear.
NOTE: This feature is disabled in manual mode.

UP

DOWN

UP

DOWN

17

Settings

E

Harmonic Current

    Adjusting the THD-I Value:

 If the Total Harmonic Distortion Current 

(THD-I) value stays above the THD-I Set value for 120 seconds, the 

device enters a THD-I error, it stops compensation, the alarm relay 

isenergized (it deacitivates all steps), the alarm led turns on and the 

THDI led (Pr11: THD-I Set) flashes. When the THD-I value stays below 

5% of the THD-I set value for 60 seconds, the device disables the THD-

I error, the alarm relay is deenergized, the alarm and THD-I led (Pr11: 

THD-I Set) turns off, the Cosine led turns on. The device restarts 

compensation.
    After entering the settings menu, the first parameter displayed on 

the screen is Pr1: Current Transformer Ratio. Press the DOWN button 

to access Pr11: TDH-I Set    parameter. To see the parameter value, 

press the "SET" button and see that the led of the Pr11 parameter is 

blinking.
    When the parameter led is blinking, you can change the value of the 

parameter by using the DOWN and UP buttons. After changing the 

value of the parameter, press the SET button to save and press the 

ESC button to return to the previous menu without saving. 
    When the changed parameter value is saved by pressing the SET 

button, the device returns to the previous menu, the parameter value 

is displayed on the screen and the parameter led does not blink, it 

lights up steadily.     

8 8 8 8

- 9 8 5

.

.

. .

8 8 8 8

- 9 8 5

.

. . .

8 8 8 8

3 0

.

. . .

SET

(2sec.)

8 8 8 8

3 5

.

. . .

Settings

E

High Voltage

    Adjusting the High Voltage Value:

 If the Voltage value stays above 

the High Voltage Set value for 5 seconds, the device enters a High 

Voltage error, it stops compensation, the alarm relay isenergized (it 

deacitivates all steps), the alarm led turns on and the High Voltage led 

(Pr12: High Voltage) flashes. When the Voltage value stays below 10V 

of the High Voltage set value for 5 seconds, the device disables the 

High Voltage error, the alarm relay is deenergized, the alarm and 

High Voltage led (Pr12: High Voltage) turns off, the Cosine led turns 

on. The device restarts compensation.
    After entering the settings menu, the first parameter displayed on 

the screen is Pr1: Current Transformer Ratio. Press the DOWN button 

to access Pr12: High Voltage    parameter. To see the parameter value, 

press the "SET" button and see that the led of the Pr12 parameter is 

blinking.
    When the parameter led is blinking, you can change the value of the 

parameter by using the DOWN and UP buttons. After changing the 

value of the parameter, press the SET button to save and press the 

ESC button to return to the previous menu without saving. 
    When the changed parameter value is saved by pressing the SET 

button, the device returns to the previous menu, the parameter value 

is displayed on the screen and the parameter led does not blink, it 

lights up steadily.   

8 8 8 8

- 9 8 5

.

.

. .

8 8 8 8

- 9 8 5

.

. . .

8 8 8 8

3 0

.

. . .

SET

(2sec.)

8 8 8 8

3 5

.

. . .

UP

DOWN

UP

DOWN

Summary of Contents for RGM-12S

Page 1: ...RGM 12S USER MANUAL www tense com tr www tenseenerji com ELEKTRİK ELEKTRONİK SAN TİC A Ş ...

Page 2: ...Compensation Harmonic Voltage Harmonic Current High Voltage Blocking Access to Settings Returning to Factory Settings Fan and Alarm Output Capacitor Calculation Table According to Connection Type Factory Set Values Dimensions Technical Specifications Contact Informations 11 Step Values Considerations in Current Transformer Selection and Connection 3 3 4 5 6 7 Device Maintenance Connection Diagram ...

Page 3: ...ent Voltage and Current Harmonic Alarm Values Adjustable Over and Under Compensation Alarm Values Can Be Set Voltage Harmonic Voltage Current Over and Under Compensation Alarm Output Step Drive Release and Discharge Times are Adjustable Up to the 15th harmonic THD I Can Be Monitored Voltage Current and Frequency Values Can Be Monitored Active Power Reactive Power and Apparent Power Values Can be M...

Page 4: ...Use compensation contactors and discharge coils in the steps Single phase connection in three phase systems is only suitable for balanced load draws Otherwise the desired rates will not be achieved Warnings Use the device in accordance with the instructions set by us After the device is mounted leave a space of at least 10 cm behind it Fix the device to the front cover of the panel with the accomp...

Page 5: ... before the current transformers Otherwise there will be differences in consumption and rates between the device and the electricity meter The current transformer must be connected to the phase from which the voltage input of the device is received Otherwise the device will not be able to perform the current transformer test Current transformer output cables should not be close to the high voltage...

Page 6: ...1 k1 Steps 1 to 7 Harmonic Filter Capacitor Thermal A2 2A 6A A1 L C1 C2 C3 C4 C5 C6 Steps 8 to 12 L C8 C9 C10C11C12 Harmonic Filter Capacitor Thermal A2 2A 6A A1 C7 Fan and Alarm Outputs L FAN 6A A2 2A A1 ALR Fan A2 2A A1 Alarm Contactor Contactor Contactor Contactor To Load ...

Page 7: ...on values this LED will light 7 Buttons They are used for monitoring measurements and making settings 8 Measurments Settings LEDs Indicates that the device is in the measurement or setting menu 9 Value Parameter LEDs When the device is in the measurement menu it informs that the measured value is displayed on the screen and the parameter is displayed while in the setting menu 4 Compensation Mode L...

Page 8: ...MENTS led is on the following measurement values will be displayed sequentially Pressing the up button will display the previous measurement parameter While showing these values the led for the related measurement value lights up Figure 1 It shows the cosine value Figure 2 It shows the current value Figure 3 It shows the voltage value Figure 4 It shows the frequency value Figure 5 It shows the act...

Page 9: ...u and reach the relevant parameter with the help of up down buttons Then press the SET button to enter the relevant parameter when you enter the parameter the led of the parameter will start to blink Then adjust the value you want with the up down buttons and press the SET button to save it The device will save the value and return to the upper menu After this process the parameter led will stop f...

Page 10: ...ogram The device has 7 different compensation programs The first 6 of these modes operate automatically and when one of these modes is activated the AUTO led on the device turns on The 7th mode is manual program and works in manual mode When this mode is active the MANUAL led on the device lights up In order to change the program when you press the ESC button for 5 seconds while on the measurement...

Page 11: ...teps should be at the lowest value in the first step and at the highest value in the last step From small to large value Compensation is not made according to the step value therefore there is no need for step measurement When the step is to be activated it always starts with the first step and activates the other steps one by one When the step is to be deactivated it always starts with the first ...

Page 12: ...r test again after eliminating the error Err1 Error If you get an Err1 error in the current transformer test there may be a loose contact in the current transformer output connections s1 k and s2 l Check the connections and perform a current transformer test again after eliminating the error 8 8 8 8 E r r 3 Err3 Error If you get an Err3 error in the current transformer test it means there is an er...

Page 13: ...ights up steadily Example If the Current Transformer Value is 100 5A the ratio value to be entered in Pr1 is 20 100 5 20 Monitoring Step Values In order to see the step values that the device measures automatically press the SET button for 2 seconds while on the measurement screen while MEASUREMENTS led is on When you enter the setting menu the MEASUREMENTS led will turn off and the SETTINGS led w...

Page 14: ...s the SET button to save the measured value then exit the menu by pressing the ESC button Also press the ESC button to cancel the operation during the measurement and return to the previous menu without saving the value after the measurement is completed Measuring All Steps To have all the steps measured switch between the steps by pressing the DOWN button When you press the DOWN button again afte...

Page 15: ...life of contactors capacitors and reactors in the steps The device will not change its current intervention for reactive power changes within the Cosine SET Value Cosine Tolerance Value area In order to change the cosine tolerance value press the SET button for 2 seconds while on the measurement screen while MEASUREMENTS led is on When you enter the setting menu the MEASUREMENTS led will turn off ...

Page 16: ...blink it lights up steadily 8 8 8 8 9 8 5 8 8 8 8 9 8 5 8 8 8 8 3 SET 2sec 8 8 8 8 5 SettingsE Step Release Time Adjusting the Step Release Time It determines the time to release the active step in order to intervene in the power change in the system In order to change this value press the SET button for 2 seconds while on the measurement screen while MEASUREMENTS led is on When you enter the sett...

Page 17: ...es while the alarm and SETTINGS leds are constantly lit When the cosine value returns to the normal level for 10 seconds the device disables the overcompensation error the alarm relay is deactivated the alarm and OVER led turn off the cosine led turns on In order to change this value press the SET button for 2 seconds while on the measurement screen while MEASUREMENTS led is on When you enter the ...

Page 18: ...T 2sec 8 8 8 8 0 0 1 5 SettingsE Harmonic Voltage Adjusting the THD V Value If the Total Harmonic Distortion Voltage THD V value stays above the THD V Set value for 15 seconds the device enters a THD V error it stops compensation the alarm relay isenergized it deacitivates all steps the alarm led turns on and the THDV led Pr10 THD V Set flashes When the THD V value stays below 3 of the THD V set v...

Page 19: ...it lights up steadily 8 8 8 8 9 8 5 8 8 8 8 9 8 5 8 8 8 8 3 0 SET 2sec 8 8 8 8 3 5 SettingsE High Voltage Adjusting the High Voltage Value If the Voltage value stays above the High Voltage Set value for 5 seconds the device enters a High Voltage error it stops compensation the alarm relay isenergized it deacitivates all steps the alarm led turns on and the High Voltage led Pr12 High Voltage flashe...

Page 20: ...and SET buttons for 5 seconds while on the measurement screen while MEASUREMENTS led is on B on will appear and the feature will be inactive When this feature is disabled it is possible to enter the setting menu 8 8 8 8 9 8 5 8 8 8 8 9 8 5 8 8 8 8 b o f f SET ESC 5sec Settings E Returning to Factory Settings Returning to Factory Settings In order to return the factory settings press the SET button...

Page 21: ...15 KVAR 20 KVAR 25 KVAR 30 KVAR 3 Phase Connection Q 3 Capacitor Powers 0 16 KVAR 0 33 KVAR 0 5 KVAR 0 83 KVAR 1 66 KVAR 2 5 KVAR 3 33 KVAR 5 KVAR 6 66 KVAR 8 33 KVAR 10 KVAR R S T Phase Netural Connection Q 6 0 08 KVAR 0 16 KVAR 0 25 KVAR 0 41 KVAR 0 83 KVAR 1 25 KVAR 1 66 KVAR 2 5 KVAR 3 33 KVAR 4 16 KVAR 5 KVAR S N ...

Page 22: ...Fixed Fixed Fixed Fixed Fixed Harmonic Voltage Delay Exiting the Error State Delay To Enter the Error State High Voltage A P Delay Exiting the Error State Passive 15 15 270 5 1 Off 240 400 270 sec V sec sec It can be active or passive A P Voltage Settings Harmonic Voltage Settings Menu Program Auto Otomatik Rot1 Rot2 Rot3 Rot4 Baştan al baştan bırak ve Manuel Operating Mode The value cannot be cha...

Page 23: ...21 Dimensions 138mm 147mm 114 5mm 147mm 138mm Rear view 147mm Front view 147mm Left side view 138mm 43mm 22mm Side ear apparatus Screwed side ear apparatus 45mm 34mm 6mm 143mm ...

Page 24: ...Accuracy 100V 300VAC 50 60 Hz 10VA 20ºC 55ºC 30ºC 80ºC 90 Without condensation 10mA 5 5A 20mm 4 Digit LED Display and Notification LEDs 1 5mm 2 5mm Voltage and C T connections 12 Mounting on the panel front cover 2000metre 900Gr IP41 Front Panel IP20 Body 140mm x 140mm Plug in terminal connection 3A 250V AC Resistive Load 10V 300V AC 5 5A 9995 5A 1 1 2 2 Contact Information Muratpaşa Mh Uluyol Cd ...

Page 25: ...User Notes ...

Page 26: ...ELEKTRİK ELEKTRONİK SAN TİC A Ş Document Number DK 105 1 Rev 1 00_210505 QUALITY SOLUTIONS MADE IN TURKEY Energy and Compensation Tracking System www tenseenerji com ...

Reviews: