Temspec TVA Installation, Operation And Maintenance Manual Download Page 7

 

 

 

MODELS: TVA, TVE & TVS IOM  Manual 

 

MAINTENANCE INSTRUCTIONS 

Safety 

 

1. 

Always isolate the unit electrically before removing the front access panel. Do this by opening 
the  circuit  breaker  (or  other  switching  device)  in  the  distribution  panel  in  the    suite.    Do  not  
use the fan switch as the  means  of  isolation. There  is  a  high  risk  of electrocution if the 
unit is improperly isolated. If in doubt have a qualified electrician perform the service work. 

2. 

Ensure that the fan has stopped rotating before proceeding to work within the unit. 

3. 

If the unit is equipped with a fuse or circuit breaker, do not change out either of these devices 
with  ones  of  a  higher  Amp  rating.  The  purpose  of  a  fuse  or  circuit  breaker  is  to  protect  the 
power wiring to the unit. 

4. 

Take care when working inside the unit. Sheet metal components may have sharp edges. 

5. 

If the black acrylic coating on the glass fiber cabinet liner is damaged, it must be patched to 
prevent glass fiber particles entering the air stream. 

 

Every 3 Months 

Replace the filter. The filter can be one of two types: a 1”  thick  cardboard framed type  or a  wire  
frame with filter media attached. 

1. 

Unit  with  a  return  air  /  access  panel  secured  by  ¼  turn  fasteners 

-  Remove  the  panel  by 

rotating  the  fastener  head  a  ¼  turn  counter-clockwise.  Pull  the  top  edge  of    the    panel 
forwards  and  unhook  the  bottom  edge.  Slide  out  the  filter.  Fit  a  new  filter  and  replace  the 
panel. 

2. 

Unit  with  a  hinged  filter  door  in  the  upper  half  of  the  grille  panel  – 

Grasp  the  bottom    edge     

of  the  door  and  sharply  pull  the  door  forwards.  Lift  the  door  to  the  horizontal  position.  The  
filter  is  now  accessible  and  is  removed  by  sliding  it  upwards  out  of  the  channels  behind  the 
grille. 

 

Annually (before the start of the cooling season) 

Remove the return air/access panel from the wall. Remove the two sheet metal screws which secure 
the panel that shields the fan assembly. Pull the shield panel sharply downward and remove. 

1. 

Vacuum the drain pan and check that the drain outlet is not blocked. Pour water into the pan 
and check that it drains quickly. If it appears to be partly blocked, remove and clean the drain 
hose beneath the pan. 

2. 

If  the  coil  surface  is  dirty,  vacuum  the  surface  which  faces  the  room.  Take  care  not  to  
damage  the  aluminum  fins  on  the  coil.  If  the  fins  are  flattened,  the  performance  of    the  unit  
will be reduced. 

3. 

Inspect  the  surface  of  the  cabinet  liner  for  evidence  of  dampness.  The  liner  should  be 
completely dry in all areas. Vacuum excessive dust from the liner, taking care not to damage 
the  black  acrylic  coating  on  the  liner.  Do  not  run  the  unit  if  the  liner  is  damp  as  this  can 
promote  mold  growth.  Determine  the  cause  of  the  dampness.  If  there  is  evidence  of  mold 
growth  it  might  be  necessary  to  replace  part  or  all  of  the  liner.  If  in  doubt  consult  a  
remediation specialist. 

4. 

Replace the thermostat battery if supplied.. 

 

The following components do not require routine maintenance: 
Fan, fan motor, control valve, electric heater (fan coil model TVE), thermostat. 
Note  that  fan motors  have  sealed  bearings  and  do  not  require additional  lubrication.  Older units 
may have oiler tubes into which are added a few drops of SAE-20 non-detergent oil every 6 months. 

Summary of Contents for TVA

Page 1: ...720 Columbus Road Mississauga Ontario Canada L5T 2G1 Tel 905 6703595 Fax 905 6703592 www temspec com Vertical Stack Fan Coil Units Models TVA TVE TVS INSTALLATION OPERATION AND MAINTENANCE MANUAL 141111 ...

Page 2: ... agent and Temspec notified within 24 hours Remove the inlet service panel and check the fan wheel for free rotation by spinning it manually Slight misalignment can be corrected by repositioning the motor or by loosening the fan hub set screw and repositioning the fan on the motorshaft Check riser projections at each end of the cabinet for damage that would prevent making an acceptable piping conn...

Page 3: ...ot necessary to use a pad under the unit Fire stopping the floor opening and making good the riser insulation at the floor opening is the responsibility of the contractor Check that the drain hose is not kinked before soldering the condensate riser If the risers incorporate expansion compensation loops remove the support brackets after anchoring the risers The fan coil unit has unions at the shut ...

Page 4: ...ng the run out to contact the edge of the slot in the sheet metal potentially causing failures or leaks Also ensure that the condensate riser stub out is at 90 to the cabinet so that the drain hose is not kinked 4 Riser anchoring is required for two purposes The risers are anchored to the floor slab at one or more points in the height of the building so that they do not slip down under gravity The...

Page 5: ...he page in the submittals which shows where the screws can be located to avoid damaging internal components When using the panel which has quarter turn fasteners the drywall must be attached to the front The sides and back can be framed 2 Framing Frame the unit using metal studs The flange around the return air access opening is 2 deep The type of return air panel which has a hinged filter door in...

Page 6: ...lar of the fan coil unit rotate the panel upright so that it is against the wall and turn the head of the fastener clockwise to the locked position Type with a hinged filter door in the upper half of the grille panel 1 If the drywall has not been installed flush with the outer edge of the collar on the unit and if a gap exceeding exists between the inner surface of the drywall and the outer edge o...

Page 7: ...dge of the door and sharply pull the door forwards Lift the door to the horizontal position The filter is now accessible and is removed by sliding it upwards out of the channels behind the grille Annually before the start of the cooling season Remove the return air access panel from the wall Remove the two sheet metal screws which secure the panel that shields the fan assembly Pull the shield pane...

Reviews: