Temspec TVA Installation, Operation And Maintenance Manual Download Page 5

MODELS: TVA, TVE & TVS IOM Manual 

 

 

 

Drain Pan Instruction 

 

  Please check the drain pan for proper drainage as part of commissioning. 

  The  unit  should  be  checked  to  ensure  the  drain  pan  is  level,  free  of  debris,  and  the  drain  line  properly 

connected to the riser stub-out 

Flushing and Testing 

 

1. 

 

The fan coil is normally equipped with ball type shut off valves. The unit is shipped with the ball 

valves open to the coil. 

2. 

After checking mechanical fittings inside the unit for tightness, it is recommended that the units on 
each riser stack are pressure tested using compressed air or nitrogen. 

3. 

Close the ball valves and flush the riser system. 

4. 

Open the supply side ball valve and bleed air from the coils. The coil has a manual air vent for 
this purpose. The top of each riser should also have an air vent (not provided by the factory). 

5. 

Test the units and risers hydrostatically. Open the return side ball valve after testing. 

6. 

Check that the strainer mesh is not choked, if there are strainers included with the unit. 

 

Drywall Installation 

 

The fan coil model series  “TV”  has  a  cabinet  which  is  designed  to  be  furred-in.  Fan  coils  which 
are  exposed  in  the  room  (model  “TF”)  or  free  standing  in  a  closet  (model  series  “TC”)  have  a  different 
style of cabinet. For the “TV” series the drywall can be directly attached to the cabinet or the unit can be 
framed. 

1. 

Direct  Application 

– The  return air panel  which has  quarter turn fasteners must be used. It  

is  designed  to  fit  the  ½”  drywall  flange  around  the  return  air  /  access  opening  on  the  unit.   
Use  drywall  screws  no  longer  than  1  ¼”  and  follow  the  instructions  on  the  page  in  the  
submittals  which  shows  where  the  screws  can  be  located  to  avoid  damaging  internal 
components.  When  using  the  panel  which  has  quarter  turn  fasteners  the  drywall  must  be 
attached to the front. The sides and back can be framed. 

2. 

Framing  – 

Frame  the  unit  using  metal  studs

The  flange  around  the  return  air/access  

opening  is  2”  deep.  The  type  of  return  air  panel  which  has  a  hinged  filter  door    in  its  upper  
half is  used  with this type  of installation. It is  preferable that the stud does not  touch the fan 
coil cabinet so that any slight vibration which may exist is not transferred to the stud. 

Before  installing  the  thermostat  and  grilles,  the  walls  must    be    painted.    Instruct    the    painter    not    to  
spray over the labels on the unit. After  installation, dust  must  be  vacuumed  from  the  coil  surfaces, 
the drain pan, the motor windings and the cabinet  insulation. 

 

Temspec does not recommend the use of a fan coil unit during construction/drywall installation as a space 
heater or air conditioner. Motor exposure to drywall dust can reduce motor life and leads to premature failure 

 

Ducted Units 

 

Remove the supply air opening knock-out in the top panel of the fan coil. Cut out the cabinet insulation 
from the opening and butter the cut edge if it is glass fiber insulation. Attach the supply air duct. 

Note that supply air duct flanges are not provided by the factory. 

 

Electrical Connection 

 

The unit has a single point connection at the junction box inside the unit. It might also have a disconnect 
switch  and/or  a  fuse.  All  electrical  wiring  must  be  in  accordance  with    the    current    version    of    the  
national  and  local  codes.  A  qualified    electrician    must    carry    out    the    work.    The    junction    box    is  
located behind the fan/motor shield.  Electrical power to the   unit  should  be  disconnected  by opening 

Summary of Contents for TVA

Page 1: ...720 Columbus Road Mississauga Ontario Canada L5T 2G1 Tel 905 6703595 Fax 905 6703592 www temspec com Vertical Stack Fan Coil Units Models TVA TVE TVS INSTALLATION OPERATION AND MAINTENANCE MANUAL 141111 ...

Page 2: ... agent and Temspec notified within 24 hours Remove the inlet service panel and check the fan wheel for free rotation by spinning it manually Slight misalignment can be corrected by repositioning the motor or by loosening the fan hub set screw and repositioning the fan on the motorshaft Check riser projections at each end of the cabinet for damage that would prevent making an acceptable piping conn...

Page 3: ...ot necessary to use a pad under the unit Fire stopping the floor opening and making good the riser insulation at the floor opening is the responsibility of the contractor Check that the drain hose is not kinked before soldering the condensate riser If the risers incorporate expansion compensation loops remove the support brackets after anchoring the risers The fan coil unit has unions at the shut ...

Page 4: ...ng the run out to contact the edge of the slot in the sheet metal potentially causing failures or leaks Also ensure that the condensate riser stub out is at 90 to the cabinet so that the drain hose is not kinked 4 Riser anchoring is required for two purposes The risers are anchored to the floor slab at one or more points in the height of the building so that they do not slip down under gravity The...

Page 5: ...he page in the submittals which shows where the screws can be located to avoid damaging internal components When using the panel which has quarter turn fasteners the drywall must be attached to the front The sides and back can be framed 2 Framing Frame the unit using metal studs The flange around the return air access opening is 2 deep The type of return air panel which has a hinged filter door in...

Page 6: ...lar of the fan coil unit rotate the panel upright so that it is against the wall and turn the head of the fastener clockwise to the locked position Type with a hinged filter door in the upper half of the grille panel 1 If the drywall has not been installed flush with the outer edge of the collar on the unit and if a gap exceeding exists between the inner surface of the drywall and the outer edge o...

Page 7: ...dge of the door and sharply pull the door forwards Lift the door to the horizontal position The filter is now accessible and is removed by sliding it upwards out of the channels behind the grille Annually before the start of the cooling season Remove the return air access panel from the wall Remove the two sheet metal screws which secure the panel that shields the fan assembly Pull the shield pane...

Reviews: