1. Dangerous  voltages  may  be  present  in  these

instruments.  Before  installation  or  troubleshooting,
switch off and isolate power to all equipment. If a unit
is suspected of being faulty, it should be disconnected
and  removed  to  a  properly  equipped  workshop  for
testing  and  repair.  Component  replacement  and
internal adjustments should be performed by qualified
maintenance personnel only.

2. To  minimize  the  risk  of  fire  or  shock  hazards,  avoid

exposing  these  instruments  to  rain  or  excessive
moisture.

3. Do not use these instruments in areas that are prone to

hazardous  conditions  such  as  excessive  shock,
vibration,  dirt,  moisture,  corrosive  gases,  or  oil.  The
ambient  temperature  of  the  areas  should  not  exceed
the maximum rating specified.

WARNINGS

Mounting

When mounting one of these instruments, make sure the control and
the  ambient  temperature  remain  within  the  10–125°F  range.  The
control  may  be  mounted  in  any  position.  Once  the  control  has  been
inserted into the panel, use the two mounting brackets provided with
the unit to secure it. Use light to moderate pressure.

Manual Reset Adjustment

The  reset  adjustment  is  located  on  the  front  of  the  control.
Approximately  half  an  hour  after  adjusting  the  set  point,  when  the
process stabilizes, it may become necessary to adjust “reset” as well.
Start  with  the  reset  adjustment  pointing  to  zero.  If  the  temperature
indication  stabilizes  above  the  set  point,  adjust  the  reset  to  the
“minus” side; if the temperature stabilizes below the set point, adjust
to the “plus” side. Continue making adjustments until the temperature
indication  stabilizes  at  the  set  point.  Make  sure  to  allow  15  minutes
between adjustments for stabilization.

Wiring

All wiring should conform to local and national codes.

When wiring the thermocouple, make sure that the thermocouple and
extension  wire  conform  to  the  thermocouple  type  specified  by  the
instrument. The thermocouple and the extension wires must have the
same polarity and be the same alloy. For accurate measurements, the
total lead resistance should not exceed 100 ohms.

To  assure  effective  lead  resistance  compensation  when  wiring  three
wire RTDs (Resistance Temperature Detectors), make sure that all of
the  leads  that  connect  to  the  controller  are  the  same  gauge  and
composition. Connect the two common wires of the three wire RTD to
terminals  17  and  18.  When  using  a  two  wire  RTD,  install  a  jumper
between terminals 17 and 18.