Auto-tuning

The auto-tuning process is performed near the set point.

The process will oscillate around the set point during

the tuning process. Set the set point at a lower value if over-

shooting beyond the normal process value is likely to cause

damage.

Auto-tuning is applied in cases of:

• 

Initial setup for a new process

• 

The set point is changed substantially from the previous

auto-tuning value

• 

The control result is unsatisfactory

Operation:

1.  The system has been installed normally.

2.  Set the correct values for the setup menu of the unit, but

don’t set a zero value for PB and TI, or the auto-tuning pro-

gram will be disabled. The LOCK parameter should be set

at NONE.

3.  Set the set point to a normal operating value, or a lower value

if overshooting beyond the normal process value is likely to

cause damage.

4.  Press 

and hold until 

appears on the display.

5.  Then press 

again for at least 5 seconds. The AT indicator

will begin to flash and the auto-tuning procedure begins.

NOTE: 

The ramping function, if used, will be disabled when

auto-tuning is taking place.

Auto-tuning mode is disabled as soon as either failure mode or

manual control mode is entered.

Procedures:

Auto-tuning can be applied either as the process is warming

up (cold start), or when the process has been in a steady state

(warm start). After the auto-tuning procedures are completed,

the AT indicator will cease to flash and the unit will revert to

PID control using its new PID values. The PID values ob-

tained are stored in the nonvolatile memory.

Auto-Tuning Error

If auto-tuning fails an ATER message will appear on the upper

display in the following cases:

• If PB exceeds 9000 (9000 PU, 900.0°F or 500.0°C),

• if TI exceeds 1000 seconds,

• if the set point is changed during the auto-tuning procedure.

Solutions to

1. Try auto-tuning once again.

2. Don’t change the set point value during the auto-tuning pro-

cedure.

3. Don’t set a zero value for PB and TI.

4. Use manual tuning instead of auto-tuning (see section 3-12).

5. Touch RESET key to reset

message.

Manual Tuning

In certain applications auto-tuning may be inadequate for the

control requirements. You can try manual tuning for these ap-

plications.

If the control performance using auto-tuning is still unsatis-

factory, the following rules can be applied for further adjust-

ment of PID values:

Figure 3.9 shows the effects of PID 

adjustment on process response.

Figure 3.9  Effects of PID Adjustment

Table 3.2  PID Adjustment Guide

Summary of Contents for PCM10001

Page 1: ...oller 2 On Off Switch 3 1 Amp Control Fuse 4 20 Amp Main Fuse 240V model has 2 5 120V or 240V Power Cord 20A 6 120V or 240V Heater Receptacle 20A 7 Type J or K Thermocouple Jack WARNINGS 1 Dangerous v...

Page 2: ...2 of the TEC 9100 which can be used as a cut out in the event of an over setpoint temperature condition This is a deviation contact set to 30 F above the setpoint In the event of an over setpoint tem...

Page 3: ...Page 3 of 10 1 5 Menu Overview...

Page 4: ...Page 4 of 10 Parameter Descriptions TEC 9100 Temperature Controller Controller Parameter Descriptions that are not applicable are not shown in the above table...

Page 5: ...dvanced PID and Fuzzy Logic algorithm to create a very small overshoot and very quick response to the process if it is properly tuned Cool only control ON OFF control P PD control and PID control can...

Page 6: ...2 will perform the fail ure transfer function as the controller enters failure mode Output 1 failure transfer if activated will perform 1 If output 1 is configured as proportional control PB 0 and BP...

Page 7: ...lure mode or manual control mode is entered Procedures Auto tuning can be applied either as the process is warming up cold start or when the process has been in a steady state warm start After the aut...

Page 8: ...Page 8 of 10 Table A 1 Error Codes and Corrective Actions...

Page 9: ...ty does not apply to damage resulting from transporta tion alteration misuse or abuse RETURNS No product returns can be accepted without a completed Return Material Authorization RMA form TECHNICAL SU...

Page 10: ...ce the Advantages of our Diverse and Innovative Products Copyright 2015 All Rights Reserved Electric Heating Elements Thermocouples and RTD Assemblies SCR Power Controls Solid State Relays Mechanical...

Reviews: