background image

 

STEP 6.  FRAMING CEILING AND ROOF OPENING 

SEE FIGURE 15 FOR INSTRUCTIONS IF THE FLUE-PIPE 
WILL BE OFFSET BELOW THE CEILING LEVEL. 

If you are not using elbows in this installation, frame the 
ceiling and roof openings directly above one another in the 
locations you chose in the Planning Ahead section of this 
manual. The flue should go straight up to the chimney 
termination.  

 
 
 
 
 
 
 
 
 
 
STEP 

7

INSTALLING FIRESTOP THIMBLE 

A firestop thimble is required in all manufactured (mobile) 
home installations.  The TEMCO Model UFT8-1 universal 
firestop thimble may be used for flat and vaulted home 
ceilings  (0

0

 to 30

0

).  

(NOTE:  TE-1 thimble extensions are 

not required if the chimney passes through a vented 
attic space and the total chimney height from the floor 
to the flue outlet is 13’-6” minimum.)

 

The firestop thimble is designed to eliminate the need to cut 
trusses when installing the 8” chimney between standard 
roof  trusses fabricated on 16” centers.  Locate and mark 
the center of the ceiling at the ceiling level.  For flat ceilings, 
cut a 14 - 1/2” square in the ceiling.  For vaulted ceilings, a 
larger cutout is needed to provide sufficinet clearance.  The 
width of the cutout will still be 14  - 1/2”, but the length 
should be increased in order to maintain proper clearances 
from the chimney components to combustibles.  

NOTE:

  

Sealing of the space between the firestop base plate and 
firestop thimble is not required.  Position the firestop thimble 
with the flanges up and with the cylindrical portion extending 
up into the hole.  Nail the firestop thimble securely to the 
framing.  The firestop thimble has a  10” sleeve that 
functions as a insulation/heat shield.  A firestop thimble 
extension model TE-1 is required if the thickness of  the 
ceiling is such that the heat shield on the thimble does not 
extend into the roof flashing.  The thimble extension slips 
into the firestop thimble and is fastened to the thimble with 
sheet metal screws.  A model 8206F roof flashing, storm 

collar, and the TEMCO 8203D termination cap are required 
to complete the installation.  (NOTE:  When clearances are 
a concern for home transportation to site, the last piece of 
vent pipe and termination cap may be installed at 

destination.) 

INSTALLING THE CHIMNEY

 

Double Wall Chimney pipe has two sections: the inner and 
the outer sections.  It is very important that both sections be 
installed for each length of chimney used in the system. 

CAUTION:  THE OUTER PIPE SECTION HAS A WIRE 
SPACER USED TO CENTER THE INNER PIPE.  THIS IS 
REQUIRED TO MAINTAIN CLEARANCES TO 
COMBUSTIBLE CONSTRUCTION.  DO NOT REMOVE!

 

STEP 8. 

Insert the inner (8") pipe with the male end pointing DOWN 
into the inner collar. The inner flue section fits inside the 
inner collar. Push the pipe until it  bottoms and the snap 
locks engage. Check each joint to ensure that the sections 
are securely locked together. 

STEP 9. 

Slip the outer (12") pipe with the male end UP over the 
other pipe and over the outer collar. The outer flue section 
fits on the outside of the outer flue collar. Push the pipe until 
it bottoms and the snap locks engage. Screws may be used 
only in the outer pipe for additional support if desired. 

STEP 10.

 

Continue this process of adding chimney pipe sections on 
top of each other until the pipe penetrates the roof opening 
enough to allow you to install the flashing and storm collar.  
Chimney sections must be supported by either guy wires or 
3/4" conduit flattened on the ends when the chimney 
extends 6' or more above the roof.  The chimney may be 
extended to a maximum of 12' above the roof.  A flue 
support must be used when the system is 35' or higher. 

Figure 8  

Figure 9  

CAUTION:  The structural integrity of the floor, wall, 
ceiling, roof trusses and any other structural members 

minimum system height 

TFC/TLC36-3MB:  11’6”  

TLC42-4MB:  12’6” 

minimum system height 

TFC/TLC36-3MB:  11’6”  

TLC42-4MB:  12’6” 

Figure 10 

 

Figure 11 

OPTIONAL 

OPTIONAL 

OPTIONAL 

MANUFACTURED HOME INSTALLATIONS 

Summary of Contents for TLC36-3M

Page 1: ...ormed by a qualified installer Do not attempt to install this fireplace yourself If the information in this manual is not followed exactly a fire or explosion may result causing WARNING THIS FIREPLACE HAS NOT BEEN TESTED WITH AN UNVENTED GAS LOG SET TO REDUCE RISK OF FIRE OR INJURY DO NOT INSTALL AN UNVENTED GAS LOG SET INTO FIREPLACE WARNING P O Box 1349 Manchester TN 37349 P O Box 1148 Perris CA...

Page 2: ...low all of the instructions contained in this book regarding installation and operation of the fireplace These instructions should be read carefully in their entirety before beginning installation of the fireplace ONCE THE FIREPLACE HAS BEEN INSTALLED THE SECTION USING YOUR FIREPLACE FOUND ON PAGE 14 OF THIS MANUAL SHOULD BE REVIEWED IN ITS ENTIRETY PRIOR TO OPERATING THE FIREPLACE It is suggested...

Page 3: ...x 52 42 models 20 x 66 Since many hearth extension materials are not insulating materials a layer of noncombustible inorganic insulating material must be used also See pages 6 and 7 for R factor requirements 8 Adhere to the 10 Rule of Thumb for chimney height see page 9 9 Chimney supports a Flue support is required for every 35 of vertical system height b Flue support is required for every 6 of of...

Page 4: ...MAY REQUIRE ADDITIONAL FOUNDATION SUPPORT ALTHOUGH THIS UNIT MAY BE INSTALLED ON COMBUSTIBLE SURFACES IT MUST NOT BE Figure 1 Figure 2 Fireplace and Framing Dimensions inches A B C D E F G H I J K L M N O P Q R S T TLC36 3MB 36 38 1 2 35 37 3 4 7 31 1 4 2 12 1 8 8 5 8 15 1 2 9 21 38 3 4 38 1 4 22 8 7 8 46 65 32 1 2 14 3 8 TLC36 3MBE 36 38 1 2 35 37 3 4 7 31 1 4 2 12 1 8 8 5 8 15 1 2 9 21 38 3 4 38...

Page 5: ...e structural integrity of a home s floor walls ceiling and roof must be maintained It is not recommended to cut roof trusses CHIMNEY OUTLET Thought should be given to the proposed location of the chimney outlet on the roof Objects such as trees adjacent buildings or embankments that are too close to the chimney can create air circulation problems during windy weather that could affect the way the ...

Page 6: ...ed on the wall The wall shield must be 40 x 40 and be constructed of a noncombustible inorganic material having a thermal resistance of R 1 49 Determining the R Values The hearth extension must be constructed of non combustible materials which have a total thermal resistance R factor equal to or greater than 80 for floor level hearth extensions or 1 20 for raised hearth extensions and be a minimum...

Page 7: ...eve the desired height The nailing flanges on the side of the firebox were designed to allow the installation of wallboard or plywood flush with the face of the firebox Metal floor tabs are provided to secure the fireplace to the floor of the home STEP 2 HEARTH SAFETY STRIP If used a Hearth Safety Strip should be installed under the fireplace when the fireplace is installed on a combustible floor ...

Page 8: ...top thimble and is fastened to the thimble with sheet metal screws A model 8206F roof flashing storm collar and the TEMCO 8203D termination cap are required to complete the installation NOTE When clearances are a concern for home transportation to site the last piece of vent pipe and termination cap may be installed at destination INSTALLING THE CHIMNEY Double Wall Chimney pipe has two sections th...

Page 9: ...ill be the amount of the offset dimension away from the ceiling nail See figure 15 The X dimen sion in the drawing is the amount of the offset Be sure to consider the direction that your offset will incline To achieve the minimum offset see table attach the return elbow to the first elbow To achieve further offset you may install various lengths of pipe between the elbows to a maximum length of 72...

Page 10: ... 0 0 1 0 46 3 10 0 0 0 1 50 4 2 0 1 1 0 56 4 8 1 0 0 1 62 5 2 0 1 0 1 66 5 6 2 0 0 1 72 6 0 1 1 0 1 80 6 8 0 0 1 1 92 7 8 0 0 0 2 96 8 0 0 1 1 1 102 8 6 1 0 0 2 108 9 0 0 1 0 2 112 9 4 2 0 0 2 118 9 10 1 1 0 2 126 10 6 0 0 1 2 136 11 4 1 0 1 2 138 11 6 0 0 0 3 142 11 10 0 1 1 2 148 12 4 1 0 0 3 154 12 10 0 1 0 3 158 13 2 2 0 0 3 164 13 8 1 1 0 3 172 14 4 0 0 1 3 182 15 2 1 0 1 3 184 15 4 0 0 0 4 1...

Page 11: ... 1 2 1 77 7 8 149 3 8 1 1 0 0 3 2 80 7 8 154 5 8 1 0 1 0 3 2 82 7 8 158 1 2 0 0 3 2 85 7 8 163 1 4 1 1 1 0 3 2 89 7 8 170 1 8 1 0 0 1 3 2 94 7 8 178 3 4 1 1 0 1 3 2 95 7 8 180 5 8 1 0 0 0 4 2 97 7 8 184 1 0 1 1 3 2 100 7 8 189 1 4 1 1 0 0 4 2 103 7 8 194 1 2 1 0 1 0 4 2 105 7 8 197 7 8 1 2 0 0 4 2 108 7 8 203 1 8 1 1 1 0 4 2 112 7 8 213 1 4 1 0 0 1 4 3 117 7 8 221 7 8 1 1 0 1 4 3 118 7 8 223 3 4 1...

Page 12: ... inlet hole of the fireplace Slide a 1 2 gas line nipple through the tube and attach to the line Finish installation by either capping gas line inside fireplace or by attaching an approved gas appliance in accordance with its installation instructions Re install insulation around the gas line to seal between the gas line and gas conduit Seal around the gas line and the refractory with refractory c...

Page 13: ...the face of the fireplace Some of these products contain combustible materials Combustible wall coverings such as paneling or wallboard may not overlap the black face of the fireplace The space between the wall covering and the fireplace should be sealed with a heat resistant material such as rock wool insulation or mortar 4000 F Min NOTE An L shaped steel lintel must be installed across the top o...

Page 14: ... to the floor of the home to prevent shifting Various methods of attachment may be used including screws nails or common construction adhesives 2 After the fireplace and hearth extension have been secured the gap between the fireplace and hearth extension must be filled or sealed with a non combustible grout caulk or sealant OR If a protective metal strip is used under the space between the firepl...

Page 15: ...THE GLASS AND IS NOT RESPONSIBLE FOR CONSEQUENTIAL PROPERTY DAMAGE AS STATED IN THE SEPARATE GLASS DOOR WARRANTY 13 Creosote Formation and Need for Removal When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote residue accum...

Page 16: ...ight side refractory 1 70355 68337 10 Left side refractory 1 70355 68338 11 Back refractory 1 70357 66993 12 Bottom refractory 1 70354 68336 13 Integral grate 1 70361 68373 14 Grate retaining bracket 2 66130 66130 REPLACEMENT PARTS The following replacement parts are available from your TEMCO dealer 16 Description Quantity Part 1 Handles 2 67987 2 Door Guide 1 68344 3 Spring Push 1 69891 4 Spring ...

Page 17: ...nyone other than the original owner Shipping costs after the first year of coverage Labor after the first year of coverage Damage caused by improper installation misuse abuse or alteration of the fireplace or chimney system Cracks in refractories that do not affect safe operation Any work done or cost incurred without written consent from TEMCO Fireplace Products Installation performed by unlicens...

Page 18: ...k in Order of Importance 1 6 ___Appearance ___Location Flexibility ___Builder Decided Purchaser Address Phone Retailer Address Phone Date of Purchase CUT ALONG LINE To register your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products 301 Perimeter Park Dr Suite 227 Nashville TN 37211 WARRANTY REGISTRATION Please Answer the Following Questions Chec...

Page 19: ...glass door kits be effective after the expiration date of the above limited warranty A Glass Breakage Temco Fireplace Products does not warrant against breakage of glass Breakage is normally due to handling and shipping which is covered by the freight handler Breakage during use can be attributed to over firing the fireplace which means flames are going up the chimney or licking against glass when...

Page 20: ...at its option either repair or replace the part at no cost to purchaser however any labor or other charges incurred in the removal or replacement of the part as well as any delivery or shipping charge will be the sole responsibility of purchaser This warranty is not transferable in any manner by the original purchaser and is effective only if the part of TEMCO s blower is accompanied by proof of p...

Reviews: