background image

OFFSET INSTALLATIONS 

RULES GOVERNING OFFSET INSTALLATIONS  

Sometimes it is necessary to use elbows to create an 
inclined run of pipe (offset installation) that will make 
installation easier by avoiding plumbing, wiring or other 
obstructions. The following rules apply to offset installations. 

A. 60' maximum system height. 

B. Four 30° elbows (two pairs) maximum per system. Each 

offset elbow must be used with a return elbow. The 
chimney pipe must be vertical when it penetrates the 
roof. 

C. The chimney offset is to be a maximum of 30° from 

vertical. 

D. Maximum inclined chimney run of 20'. 

E. Additional support is to be provided every 6' of inclined 

run of chimney. Use flue support 8204S. 

F. Minimum height of fireplace using two elbows (one pair) 

is 13'6"; four elbows (two pairs) is 21'. 

G. Elbows may be used directly off the top of the firebox and 

may be mounted with the return elbow directly on top of 
the offset elbow. 

H. A MINIMUM OF 1" AIR SPACE CLEARANCE MUST BE 

MAINTAINED FROM THE CHIMNEY PIPE AND ELBOWS 
TO ALL COMBUSTIBLES. 

I. Local building codes must be followed in all cases as to 

the particular requirements concerning the installation of 
factory built fireplaces.  

TO INSTALL ELBOWS 

1. Place the offset elbow (no straps) on top of the firebox or 

chimney section and point the upper half in the direction 

you require the chimney to incline. Snap lock all sections 
permanently in place.  

2. Adjust the inner section of the elbow into the inside of the 

inner collar of the firebox or the inner section of the 
chimney pipe. 

3. Adjust the outer section of the elbow over the outer 

section of the flue collar or outer section of the chimney 
pipe. Snaplock all sections permanently into place. 

4. The return elbow has 18" support straps. The support 

straps should be nailed to the framing in the manner 
indicated in figure 16. It may be necessary to add framing 
or lengthen the straps with hanger iron to support 
chimney pipe and elbows. 

5. See figure 18 for offset calculation: Locate the center 

point of the flue on the ceiling with a plumb bob as shown 
on page 5. The center of the correct location for the 
ceiling opening will be the amount of the offset dimension 
away from the ceiling nail. See figure 18. The "X" dimen-
sion in the drawing is the amount of the offset. Be sure to 
consider the direction that your offset will incline. To 
achieve the minimum offset, (see table), attach the return 
elbow to the first elbow. To achieve further offset, you 
may install various lengths of pipe between the elbows to 
a maximum length of 72 inches without a flue support. 

6. When the flue penetrates the ceiling at a 30° angle, 

install firestop spacer 8230F. (See step 7 on page 8 for 
construction detail.) 

Figure 14 

CHIMNEY TERMINATION 

HEIGHT 10 FOOT RULE OF 

THUMB

  

Under most conditions the fireplace system will draw 
properly if the chimney height is determined in 
accordance with the following guidelines: 

1. If your chimney penetrates the roof within 10' of its 

peak, it must extend at least 24" above your roof's 
peak and be at least 36" above the highest point of 
the roof opening (see figure 15). 

2. If the chimney penetrates the roof farther than 10' 

from its peak, measure from the center line of the 
chimney to a point 10' away, between the chimney 
and the peak of the roof. The top of the chimney 
must be at least 24" above this point and at least 36" 
above the highest point of the roof opening. (See 
figure 16). 

3. When figuring required chimney height, the termina-

tion counts as 6" of effective chimney height. The 
balance of the required height will consist of chimney 
sections and the effective height of the firebox.  

4. The 10' Rule of Thumb is a guide for calculating 

chimney height that works under most conditions. 
However, many factors can cause the need for 
additional chimney height beyond what the 10' Rule 
of Thumb would indicate. Topographical factors can 
cause high pressure zones which prevent a chimney 
from drawing. This can occur if the house is located 
in a low lying area, in a valley or near the base of a 
cliff or hillside. The same situation can occur it the 
chimney is near other steep roof lines or tall build-
ings. Areas with high winds also frequently require 
higher than normal chimneys. Certain styles of 
architecture tend to interfere with a fireplace's proper 
draw. If the room in which the fireplace is located 
has a very high ceiling, smoke may enter  the room 
unless the chimney is terminated at a level higher 

Figure 15 

Figure 16 

Summary of Contents for TFC39-22

Page 1: ...ulating fireplace Optional Combustion Air Kits AIR 5 AIR 5A AIR 5B AIR 7 AIR 3B Optional Glass Doors CLS 4 CLS 3 CX31 CX41 Optional Blower Kit BL3922 Requires junction box JB 2 TLC39 22I With insulated outer wrap 39 louvered heat circulating fireplace with fully insulated outer wrap Optional Combustion Air Kits AIR 5 AIR 5A AIR 5B AIR 7 AIR 3B Optional Glass Doors CLS 4 CLS 3 CX31 CX41 Optional Bl...

Page 2: ...es 5 Determining the R Values 6 Fireplace Installation 7 Installing the firebox 7 Installing the chimney 8 Chimney termination height 10 Foot Rule of Thumb 9 Offset installations 9 10 11 Flashing and storm collar 12 Installing the termination 12 Chase installations 12 Installing a gas line 13 Cold climate installations 13 Mobile home installation 14 Finishing Your Fireplace 15 16 Using Your Firepl...

Page 3: ... combustible wall is 17 See Figure 4 for alternative wall shields and required R factors 7 If the floor in front of the fireplace is combustible a protective hearth extension must be used Raised or floor level extensions may be constructed On TFC39 only a raised hearth extension may be flush with the fireplace hearth It must be a minimum of 16 x 52 For a raised hearth on louvered models the firepl...

Page 4: ...ace is limited Your fireplace weighs no more than some of your fine furniture If the fireplace is located near a load bearing wall additional supports to the foundation will not be necessary HEAVY FACINGS SUCH AS BRICK STONE ETC MAY REQUIRE ADDITIONAL FOUN DATION SUPPORT ALTHOUGH THIS UNIT MAY BE INSTALLED ON COMBUSTIBLE SURFACES IT MUST NOT BE INSTALLED ON CARPET OR VINYL Figure 1 Locations Figur...

Page 5: ... wish to drive a nail through the ceiling at this spot Then go into the attic and find the nail Using the plumb bob with the ceiling nail as the center point of the flue mark the center of the area on the roof through which the flue will pass This is to see if it is possible to cut your opening for the flue in both the ceiling and roof without cutting either roof rafters or ceiling joists A locati...

Page 6: ... wall shield as well D The framing header may rest on top of the standoffs E The minimum distance from the fireplace opening to an adjacent combustible wall is 17 The minimum distance to an adjacent combustible wall may be reduced to 12 when an approved wall shield is used on the wall The wall shield must be 40 x 40 and be constructed of a noncombustible inorganic material having a thermal resista...

Page 7: ...atety strip is not required below the front face of the fireplace and mating edge of the hearth extension if the following steps are taken 1 The pre fabricated hearth extension or site built must be secured to the floor of the home to prevent shifting Various methods of attachment may be used including screws nails or common construction adhesives 2 After the fireplace and hearth extension have be...

Page 8: ...ACER USED TO CENTER THE INNER PIPE THIS IS REQUIRED TO MAINTAIN CLEARANCES TO COMBUSTIBLE CONSTRUCTION DO NOT REMOVE STEP 8 Insert the inner 8 pipe with the male end pointing DOWN into the inner collar The inner flue section fits inside the inner c ollar Push the pipe until it bottoms and the snap locks engage Check each joint to ensure that the sections are securely locked together STEP 9 Slip th...

Page 9: ... the amount of the offset dimension away from the ceiling nail See figure 18 The X dimen sion in the drawing is the amount of the offset Be sure to consider the direction that your offset will incline To achieve the minimum offset see table attach the return elbow to the first elbow To achieve further offset you may install various lengths of pipe between the elbows to a maximum length of 72 inche...

Page 10: ... 3 10 0 0 0 1 50 4 2 0 1 1 0 56 4 8 1 0 0 1 62 5 2 0 1 0 1 66 5 6 2 0 0 1 72 6 0 1 1 0 1 80 6 8 0 0 1 1 92 7 8 0 0 0 2 96 8 0 0 1 1 1 102 8 6 1 0 0 2 108 9 0 0 1 0 2 112 9 4 2 0 0 2 118 9 10 1 1 0 2 126 10 6 0 0 1 2 136 11 4 1 0 1 2 138 11 6 0 0 0 3 142 11 10 0 1 1 2 148 12 4 1 0 0 3 154 12 10 0 1 0 3 158 13 2 2 0 0 3 164 13 8 1 1 0 3 172 14 4 0 0 1 3 182 15 2 1 0 1 3 184 15 4 0 0 0 4 188 15 8 0 1...

Page 11: ... 74 7 8 140 7 8 1 0 1 1 2 1 77 7 8 149 3 8 1 1 0 0 3 2 80 7 8 154 5 8 1 0 1 0 3 2 82 7 8 158 1 2 0 0 3 2 85 7 8 163 1 4 1 1 1 0 3 2 89 7 8 170 1 8 1 0 0 1 3 2 94 7 8 178 3 4 1 1 0 1 3 2 95 7 8 180 5 8 1 0 0 0 4 2 97 7 8 184 1 0 1 1 3 2 100 7 8 189 1 4 1 1 0 0 4 2 103 7 8 194 1 2 1 0 1 0 4 2 105 7 8 197 7 8 1 2 0 0 4 2 108 7 8 203 1 8 1 1 1 0 4 2 112 7 8 213 1 4 1 0 0 1 4 3 117 7 8 221 7 8 1 1 0 1 ...

Page 12: ... local sheet metal shop is required to complete a chase installation This cover becomes a flashing that prevents water from entering the chase The chase cover should be sealed at the corners A minimum 1 high collar is required at the point where the chimney pipe or slip section will penetrate the chase cover It requires 12 5 8 diameter collar The seam at the base of the collar must be watertight I...

Page 13: ...The insulation and sealing of the enclosure around the fireplace is very important in cold climates If the enclosure is insulated and sealed properly you can avoid future cold air problems The time taken to install the firebox correctly is well worthwhile INSULATION OF THE FIREPLACE ENCLOSURE When in a chase or on an outside wall the fireplace enclosure can be insulated like any other outside wall...

Page 14: ...air kit may go through the floor or the side wall of the mobile home 4 11 6 is the minimum system height for mobile home installations The height of the system is measured from the base of the fireplace and includes 6 of the chimney cap 5 A firestop thimble is required in all mobile home installations The TEMCO Model UFT8 1 universal firestop thimble may be used for flat and vaulted mobile home ce...

Page 15: ... min adhesive or mortar when anchoring brick stone or tile to the face of the fireplace Check to see whether man made brick and stone are made of non combustible materials before using them on the face of the fireplace Some of these products contain combustible materials Combustible wall coverings such as paneling or wallboard may not overlap the black face of the fireplace The space between the w...

Page 16: ...mmon construction adhesives 2 After the fireplace and hearth extension have been secured the gap between the fireplace and hearth extension must be filled or sealed with a non combustible grout caulk or sealant OR If a protective metal strip is used under the space between the fireplace and hearth extension sealing of the gap between the fireplace and hearth extension is optional See Note Below Se...

Page 17: ...ES NOT WARRANT THE GLASS AND IS NOT RESPONSIBLE FOR CONSEQUENTIAL PROPERTY DAMAGE AS STATED IN THESEPARATEGLASSDOORWARRANTY 13 Creosote Formation and Need for Removal When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote re...

Page 18: ...efractory retainer left side 1 68339 7 Screws for refractory retainers 2 68188 8 Right side refractory 1 67902 9 Left side refractory 1 67901 10 Back refractory 1 67130 11 Bottom refractory 1 67900 12 Integral grate 1 68373 13 Grate retaining bracket 2 66130 14 Refractory retainer 1 66130 REPLACEMENT PARTS FOR 39 FIREPLACES The following replacement parts are available from your TEMCO dealer 18 ...

Page 19: ...ce Products and specifically does not cover the following Anyone other than the original owner Shipping costs after the first year of coverage Labor after the first year of coverage Damage caused by improper installation misuse abuse or alteration of the fireplace or chimney system Cracks in refractories that do not affect safe operation Any work done or cost incurred without written consent from ...

Page 20: ...k in Order of Importance 1 6 ___Appearance ___Location Flexibility ___Builder Decided Purchaser Address Phone Retailer Address Phone Date of Purchase CUT ALONG LINE To register your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products 301 Perimeter Park Dr Suite 227 Nashville TN 37211 WARRANTY REGISTRATION Please Answer the Following Questions Chec...

Reviews: