INSTALLATION AND STARTUP CHECKLIST 

Installer’s Copy 

NOTE:  

TEMCO

  gas logs and fireplaces require installation by a qualified gas appliance installer.   A copy of this checklist must be 

submitted, along with proof of purchase, when applying to Technical Services for prior written approval of warranty repair or replacement.

 

All Vent-Free Gas Fireplaces and Logs  

                

Read and understand installation instructions before attempting installation. 

                 Assure that the model to be installed is of the CORRECT FUEL TYPE.  Check markings on the shipping container  (Model#s 
                 ending in “N” are natural gas products; model#s ending in “P” are LP gas products.), tags on the burner assembly, and 
                 color of the ODS safety pilot tube. 

                 (Aluminum for natural gas; brass for LP gas) 

                

Notes:  

REGULATORS ARE NOT FIELD-ADJUSTABLE.  ANY ATTEMPT TO ADJUST VOIDS THIS WARRANTY.  

                 In order to ensure adequate combustion air, make sure that the model being installed has the appropriate heating 
                 capacity for the unconfined space available.  

Allow a minimum of 50 cubic feet of unconfined space per 1000 BTU’s for all 

                 gas appliances. 

                 Assure that gas line size is adequate for the model’s input rating (BTU’s per hour), the length of run form the meter       or second 
                 stage regulator to the farthest gas appliance, and other gas appliances on the system.  A drip leg or sediment trap is required.  
LP            models require a minimum tank size of 120 gallons water capacity and two stage regulation. 

                 Assure that installation meets local codes and ordinances. 

                 Assure that there are no fans or blowers in the fireplace area. 

                 Check for leaks before lighting. 

                

Using a manometer, verify proper gas pressure at the manifold with unit at maximum setting and other appliances 

                 operating. 

                

inlet pressure:__________ (ins. wc)          manifold pressure:__________ (ins. wc) 

                 Verify proper ignition of ODS and front and rear burners, as well as proper appearance of flames. 

                

Verify that ceramic fiber and refractory components are properly positioned and secure.  

(Rear burner must not contact 

                 logs.) 

                 Verify adequate clearance to mantels and other combustibles. 

                 Demonstrate correct operation of the product to the consumer.  Note:  LP models must not be operated if fuel tank is less than 
                 1/4 full. 

                 Observe the consumer operating the product properly. 

                 Explain and demonstrate proper periodic maintenance. 

                 Explain that operation with logs positioned other than as described in the manual voids the warranty and will cause      p

o

o

                 combustion and sooting. 

                 Verify the consumer’s understanding that warranty service work that is not pre-approved by the manufacturer’s Technical 
                 Service Department (other than routine maintenance) may not qualify for reimbursement. 

                 Answer any questions the consumer may have about 

TEMCO 

vent-free products. 

Vent-Free Gas Logs Only 

                

Verify that the fireplace in which the logs are to be installed is either a solid-fuel burning fireplace (either factory-built or 

                 masonry) with a working flue system connected to it or an approved vent-free firebox. 

                 Verify that the fireplace has been thoroughly cleaned by a professional chimney sweep.  If solvents have been used to clean 
                 the hearth, they must be allowed to evaporate before proceeding with installation. 

                 Check firebox dimensions for adequate height, width, and depth. 

                 Verify that the grate assembly is attached to the firebox floor. 

                 Verify that any ash dump or outside air inlets are permanently sealed to avoid drafts within the firebox. 

                 Verify that no additional logs, ornaments, or non-approved blower devices have been added. 

                 Repair any broken or damaged logs prior to operation. 

                 Check mantel clearances and verify installation of canopy if necessary. 

                 Glass doors must be removed or opened completely during operation of logs. 

 

Please sign below that checklist has been completed and understood.  DATE INSTALLED ______/______/______ 

 

 

Installer                                            Phone                        Consumer                                          Phone 

 

Summary of Contents for ADF36-PN

Page 1: ...by a qualified gas installer service agency or the gas supplier Do not attempt to install this appliance yourself WHAT TO DO IF YOU SMELL GAS Do not light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If the information in this manual is not followed exactly a fi...

Page 2: ...tect your hands and eyes when installing servicing your fireplace No outside air kit is required inside firebox area Refer to the log set manual for combustion air requirements NOTE Authorities having jurisdiction i e building inspectors fire marshals etc should be consulted before installation to determine the need to obtain a permit FAILURE TO FOLLOW THESE INSTRUCTIONS WILL VOID YOUR WARRANTY AN...

Page 3: ...ustion chamber and adequate accessibility clearance for servicing and proper operation Never obstruct the front opening of the fireplace Any safety screen or guard removed for servicing the fireplace must be replaced prior to operating the fireplace This fireplace may be installed in an after market manufactured mobile home where not prohibited by state or local codes After market Completion of sa...

Page 4: ...th the face of the fireplace Only the header see figure 4 may rest on the standoffs on top of the firebox When the fireplace is installed over carpeting vinyl tile or any combustible material other than wood flooring it must be installed on a metal or wood panel extending its full width and depth Alternatively the carpeting vinyl tile etc may be removed beneath the fireplace before installing COMB...

Page 5: ...t directly in front of the opening and then sliding it into the proper position STEP 3 LEVEL THE FIREBOX Check the level of the firebox by placing a level on the top edge of your fireplace face Shim with sheet metal if necessary Do not use wooden shims STEP 4 SECURE THE FIREBOX Secure the fireplace to the framing Nailing flanges on the firebox will make securing it quick and easy Use appropriate s...

Page 6: ...inted metal faces of the fireplace Combustible wall coverings such as paneling or wallboard may not overlap the black face of the fireplace The space between the wall covering and the fireplace should be sealed with a heat resistant material such as rock wool insulation or mortar see figure 6 and 7 MANTEL CLEARANCES With the firebox installed the lower edge of the mantel piece must not be less tha...

Page 7: ... operation Always check for gas leaks after servicing A list of available replacement parts follows Always include the correct name part number and model number of the fireplace when ordering service parts If you desire to communicate with the factory write to TEMCO Fireplace Products P O Box 1349 Manchester TN 37349 or TEMCO Fireplace Products P O Box 1148 Perris CA 92572 REPLACEMENT PARTS See Th...

Page 8: ... codes and ordinances The logs must be placed strictly in accordance with the arrangement described in the installation instructions The Product must be operated and maintained according to the instructions furnished Alteration of the Product in any way is prohibited and voids any and all warranties Removal of the data plate alters the Product and voids the warranty The installer must have complet...

Page 9: ...ODS and front and rear burners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer Note LP models must not be operated if fuel tank is less than 1 4 full Observe the consu...

Page 10: ...f ODS and front and rear burners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer Note LP models must not be operated if fuel tank is less than 1 4 full Observe the con...

Page 11: ... have followed all codes and regulations and adhered to the TEMCO installation instructions I have completed the proper installation and startup checklist Installers Signature Print Installer s Name Purchaser Address Phone Retailer Address Phone Date of Purchase WARRANTY REGISTRATION Please Answer the Following Questions Check Box 1 Type of Home Single Family Duplex Apt Mobile Home Cabin Vacation ...

Reviews: