TDVN Series Direct Vent Gas Fireplace

20007636

1

2

3

4

Max. 8' (2.4m)

FP1245

through the roof

90 & 45 degree 

12/02

1 + 2 + 3 + 4 = 270°

FP1245

Fig. 29

  Typical offset application.

This Gas Fireplace has been approved for:

• 

Vertical installations up to 40’ (12 m) in height. Up 
to a 10’ (3 m) horizontal vent run can be installed 
within the vent system using a maximum of two 90° 
elbows. (Fig. 28)

Vertical Through-the-Roof Applications

Max. 10' (3m)

Max. Height

40' (12m)

Min. Height

7

¹⁄₂

' (2.3m)

FP1244

through the roof

max/min dims

12/02

Pipe Straps Every 

3’ (914mm)

FP1244

Fig. 28

  Support straps for horizontal runs.

• 

Up to two 45° elbows may be used within the   
horizontal run. For each 45° elbow used on the  
horizontal level the maximum horizontal length must 
be reduced by 18” (457 mm). 

  Example: Maximum horizontal length
  0  x  45° elbows  =  10’ (3 m)
  1  x  45° elbows  =  8

¹⁄₂

’ (2.6 m)

  2  x  45° elbows  = 7’ (2.1 m)

• 

A minimum of an 8’ (2.4 m) vertical rise.

• 

Two sets of 45° elbows offsets within these vertical  
installations. From 0 to a maximum of 8’ (2.m) of 
vent  pipe can be used between elbows. (Fig. 29)

• 

7DVCS must be used to support offsets. (Fig. 34) 
This application will require that you first determine 
the roof pitch and use the appropriate starter kit. 
(Refer to Venting Components List)

• 

The minimum height of the vent above the highest 
point of penetration through the roof is 2’ (61mm). 
(Fig. 14)

 

Roof Pitch 

H (Min.)

 

Flat to 6/12 

12”  (305 mm)

 

6/12 to 7/12 

15”  (381 mm)

 

Over 7/12 to 8/12 

18”  (457 mm)

 

Over 8/12 to 16/12 

24”   (610 mm)

 

Over 16/12 to 21/12 

36”  (914 mm)

H

12

x

T183

typical straight up 

installation

12/3/03   djt

Vent Cap

Lowest Discharge 

Opening

Gas Vent

Roof Pitch 

is X/12

H (Min.) - Minimum height 

from roof to lowest dis-

charge opening

T183

Fig. 14

  Vertical termination location.

Summary of Contents for 33TDVN

Page 1: ...ION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE INSTALLER CONSUMER SAFETY INFORMATION FOR YOUR SAFETY Installation and service must be performed by a qualified installer service agency or the gas supplier Builder Top Vent Direct Vent Zero Clearance Gas Fireplace Heater Models 33TDVN 36TDVN 39TDVN 7636 TDVN cover 5 ...

Page 2: ...Restrictor Plate 33TDVN only 19 Venting Components 21 Operating Instructions Glass Information 22 Louvre Removal 22 Window Frame Assembly Removal 22 Glass Cleaning 22 Installation of Logs Lava Rock Ember Material 23 Flame Temperature Adjustment 24 Flame Characteristics 24 Lighting Operating Instructions 25 Troubleshooting 26 Fuel Conversion Instructions 29 Maintenance Unit Adjustment 32 Maintenanc...

Page 3: ...ur fireplace for at least ten four 4 hours the first time you use it If the optional fan kit has been installed place the fan switch in the OFF position during this time For high altitude installations refer to Unit Adjustment on Page 32 WARNING Check with your electronics manufacturer before installing a television or other electronic de vice above this fireplace 4 Under no circumstances should this...

Page 4: ... vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carb...

Page 5: ... 6 152 mm 7 181 mm 7 190 mm I 5 149 mm 6 171 mm 6 159 mm J 7 200 mm 10 254 mm 8 213 mm K 11 297 mm 13 343 mm 12 318 mm L 1 18 mm 1 18 mm 1 18 mm Framing Dimensions M 29 737 mm 35 889 mm 35 889 mm N 33 851 mm 36 927 mm 39 1003 mm O 14 368 mm 16 419 mm 16 419 mm P 49 1264 mm 55 1403 mm 56 1422 mm Q 24 632 mm 28 714 mm 28 718 mm R 35 894 mm 39 1010 mm 40 1016 mm 7636 TDVN specs 5 04 F N Rough Opening...

Page 6: ...a bay window trim kit does not effect the distances and reference points referred to in the diagram and chart Noncombustible mantels and legs may be installed at any height and width around the appliance When using paint or lacquer to finish the mantel such paint or lacquer must be heat resistant to prevent discoloration Clearance to Combustibles A B C D E V W X Y Z Fireplace CFM146 DV Mantel Chart...

Page 7: ... facing material of the wall The strips are adjustable to 1 2 13 mm 5 8 16 mm or 3 4 19 mm Fig 4 5 Screw through the slotted holes in the drywall strip and into the pre drilled holes in the fireplace side Measure from the face of the fireplace to the face of the drywall strip to confirm the final depth High Elevations Input ratings are shown in BTU per hour and are certified without deration for elevat...

Page 8: ...Code ANSI Z223 1 NFPA 54 in the USA Gas Line Installation FP297A INSTA VENT FREE UVHB26 GAS SUPPLY 7 1 98 FP297A 1 2 Gas Supply 1 2 NPT X 1 2 Flare Shut off Valve 3 8 Flex line from valve Fig 5 Typical gas supply installation 5 For natural gas a minimum of 3 8 iron pipe with a gas supply pressure of 4 5 w c from the gas me ter Consult with local gas utility and ANSI Z223 1 NFPA 54 if any questions...

Page 9: ...ground wire of the supply line to the green screw of the socket assembly 8 Refit the socket assembly back into the electrical box and replace the cover plate Secure the cable with the clamp on the outside of the EB 1 base plate and refit the EB 1 assembly to the unit with the screw removed in step 1 EB 1 Electrical Box It is strongly suggested that the wiring of the EB 1 Electrical Junction Box be c...

Page 10: ...rates the use of flex venting shall have an inclining slope from the unit of 1 25 mm per 24 610 mm General Venting There must not be any obstruction such as bushes garden sheds fences decks or utility buildings within 24 from the front of the termination hood Do not locate termination hood where excessive snow or ice build up may occur Be sure to check vent termi nation area after snow falls and cl...

Page 11: ...tlet 3 91 cm 3 91 cm J Clearance to nonmechanical air supply inlet 6 15 cm for appliances 10 000 6 15 cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30 cm for 10 000 Btuh 3kW 9 other appliances appliances 10 000 Btuh 3kW and 23 cm for appliances 10 000 100 000 Btuh 30kW 36 91 cm Btuh 3kW and 50 000 Btuh for appliances 100 000 Btuh 30kW 15kW 12 30 cm for appliances 50 ...

Page 12: ...ly High Tem perature Sealant Hose Clamp FP1471a Fig 10 Apply high temperature sealant to 4 and 7 pipes Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors G Combustible 6 152 mm Noncombustible 2 51 mm F Combustible 6 152 mm Noncombustible 2 51 mm G Balcony with no side wall M Combustible Noncombustible 12 305 mm M B...

Page 13: ...from the floor of the fireplace is 11 3 4 m the horizontal run to the face of the outer wall must not exceed 14 4 3 m Example B If the vertical dimension from the floor of the unit is 7 2 14 m the horizontal run to the face of the outer wall must not exceed 8 2 6 m Horizontal dimension from the outside face of the wall to the center of the fireplace vent flange Sidewall vent graph showing the relations...

Page 14: ... 12 02 FP1237 Fig 14 Maximum horizontal vent run 7 5 2 3m A B A B 17 5 2m Max 1 x 90 elbow in horizontal plane 3 914mm FP1238 Fig 15 Maximum vent run with elbows The maximum number of 45 elbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the horizontal run MUST b...

Page 15: ...ews 2 8 Screws 2 Adjustable Zero Clearance Sleeve 8 Screws 2 Adjustable Zero Clearance Sleeve ZCS101 Fig 18 Adjustable zero clearance sleeve Firestop VO584 100 Vent Opening 2 99 djt Vent Opening for Combustible Wall 9 240mm 9 240mm Fireplace Hearth Framing Detail Opening for Noncombustible Wall 7 190mm VO584 100 Fig 17 Locate vent opening on wall STEP 3 Place fireplace into position Fig 19 Measure ...

Page 16: ... mm with metal pipe straps Make sure the horizontal vent pipe is in stalled on a level horizontal plane Vertical Sidewall Installation Flex Vent Pipe NOTE The 40 1016 mm flex vent is used for 90 off the top of the unit then out the back wall Follow Step 1 and 2 on Page 14 Step 3 Install the four 4 spacer springs on the 4 flex vent pipe When installing the spacer springs around the 4 pipe stretch the...

Page 17: ... mm Clearance Min Window Well Gravel Drain BG402 Fig 26 Below grade installation Zero Clearance Sleeve if required A minimum of 24 610mm ver tical pipe must be installed when using the 7TDVSNORK Kit The 22 559 mm vertical rise center to center of the snorkel may be included for calculationof max horizontal run 24 610 mm Minimum Screws Foundation Wall 6 165mm FP1475 flex 90 bend 4 04 djt FP1475 Fig...

Page 18: ...Example Maximum horizontal length 0 x 45 elbows 10 3 m 1 x 45 elbows 8 2 6 m 2 x 45 elbows 7 2 1 m A minimum of an 8 2 4 m vertical rise Two sets of 45 elbows offsets within these vertical installations From 0 to a maximum of 8 2 m of vent pipe can be used between elbows Fig 29 7DVCS must be used to support offsets Fig 34 This application will require that you first determine the roof pitch and use...

Page 19: ... mm 4 Proceed to plumb for additional openings through the roof In all cases the opening must provide a minimum of 1 25 mm clearance to the vent pipe i e the hole must be at least 9 x 9 240 x 240 mm 5 Place fireplace into position 6 Place firestop s 7DVFS or Attic Insulation Shield 7DVAIS into position and secure Fig 33 7 Install roof support Fig 34 and roof flashing making sure upper flange of flashin...

Page 20: ...nstalled on both the bottom and the top side of the ceiling joists If an attic is above ceiling level a 7DVAIS Attic Insulation Shield must be installed The enlarged ends of the vent section always face downward Fig 35 CFM190 TTR Ternim 2 1 25 02 sta CFM190 Fig 36 Minimum termination to roof clearance Min 2 610 mm ...

Page 21: ...g Twist Lock Pipe Model 7FDVSK Sidewall Venting Flex Vent Pipe Starter Kit Model 7TDVSKV Vertical Venting for 7TDVSKV A order 1 12 to 6 12 roof pitch for 7TDVSKV B order 7 12 to 12 12 roof pitch for 7TDVSKV F order flat roof Starter Kit for Below Grade Installation Model 7TDVSKS Snorkel Kit Twist Lock Pipe Model 7FDVSKS Snorkel Kit Flex Vent Pipe 45o Elbow 7TDV45 for Rear Vent to Vertical Vent or V...

Page 22: ...n the glass It is therefore recommended that the glass be cleaned two or three times with a non ammonia based household cleaner and warm water We recommend gas fireplace glass cleaner within the first few weeks of operation After the initial cleaning process the glass should be cleaned two or three times during each operating season depending on the environment in the house The use of any non approv...

Page 23: ...ons provided with pins on back logs and grooves on the center log 6 Place platinum embers loosely along top surface of burner along entire length of ported area of front burner DO NOT place embers on back portion of burner Use individual pieces of embers no larger than dime size about 1 16 thick fluffed up thick ness Use a single layer of embers and DO NOT overlap pieces Ember material should be flu...

Page 24: ...isual check of the pilot and burner flames Compare them to Figure 43 If the flame patterns appear abnormal contact a qualified service provider for service and adjustment Flame Characteristics Flame Temperature Adjustment LO H I FP390 FLAME ADJUSTMENT KNOB 11 21 96 Turn counterclockwise to increase flame height Turn clockwise to decrease flame height Fig 42 Flame adjustment knob for SIT valve FP1229 ...

Page 25: ...e instruc tions exactly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any fireplace Do not touch any electric switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone To Turn Off Gas To Heater L...

Page 26: ... functioning adjust the inlet pressure regulator to supply gas to the appliance within design parameters of the appliance manufacturer Typically 7 NG 11 LPG Pilot adjustment screw not After the pilot has been lit for approximately three minutes properly adjusted and only the thermo generator wire connected to the main operator head measure the voltage across TPTH and TP This open circuit voltage s...

Page 27: ...rically open Replace the valve Defective Safety Magnet Verify operation of safety magnet in the following Millivolt system manner A Remove all wires from the terminals of the main operator B Measure the electrical voltage between the termi nals TPTH and TP If the voltage is above 110mv and the safety magnet does not hold replace the valve Pilot orifice blocked Replace orifice with a new orifice of th...

Page 28: ... below 300mv Record read ing B Remove jumper wire from the TPTH and TH con nections and reconnect the thermostat wires to the same terminals Take the closed circuit voltage as described in the previous step If the mv reading drops below 150mvm excessive resistance existsin the thermostat circuit and must be isolated and eliminated Thermostat wall switch Defective wall switch Repeat the above troub...

Page 29: ...e see the appropriate parts list for your model for parts included with the fireplace Check the items in the kit with the parts list Notify the supplier of any items that are missing before installing the conversion kit 1 Turn off gas supply 2 Turn off the electrical supply to the appliance if so equipped Replace Burner Orifice 1 Remove the two 2 screws holding the pilot to the burner bracket 2 Remo...

Page 30: ...llen wrench into the end of the injector Insert the injector into injector journal and rotate the injector clockwise until a torque of 9 in lbs is achieved Replace the pilot hood by aligning the tab on the base of the hood with the slot in the side of the pilot journal Push the hood down directly onto the pilot bracket Fig 47 The hood must sit squarely on the bracket for proper operation Check to ...

Page 31: ...alve will give manifold pressure Min Input Max Input 33TDVP 13 000 18 000 36TDVP 14 500 20 000 39TDVP 16 500 22 000 FC107 SIT820 valve conversion 10 03 A B C OFF P I L O T O N FC107 Fig 49 Remove mounting screws pressure regulator tower and diaphragm assembly and discard D E F FC108 SIT regulator conversion 10 03 OF F P I L O T O N FC108 Fig 50 Replace regulator Gas Supply Pressure inches w c Mini...

Page 32: ...11 0 14 0 Manifold Pressure inches w c Normal HI Normal Low Natural Gas 3 5 1 6 LP Propane 10 0 6 3 High Altitude When installing this fireplace at an elevation between 0 and 2000 feet 0 610m in the USA and 0 and 4500 feet 0 1370m in Canada the input rating does not need to be reduced When installing this fireplace at an elevation above 2 000 feet in the United States it may be necessary to decrease...

Page 33: ...rs contact your near est dealer to get the appliance serviced Alternatively the appliance can be cleaned by removing all the logs Handle the logs gently so as not to damage them Always lift each log by holding it carefully at each end Maintenance After the logs are removed allowing access to the burn er area use a vacuum cleaner to carefully remove dust and loose particles from the base logs and f...

Page 34: ...5 w c 45 DMS 36TDVP 14 500 20 000 10 0 w c 55 DMS 39TDVN 15 000 22 000 3 5 w c 43 DMS 39TDVP 16 500 22 000 10 0 w c 54 DMS Conversion Kits Change Natural Change Propane Model to Propane to Natural 33TDVN 33DVCKP 33TDVP 36TDVN 36DVCKP 36TDVP 39TDVN 39DVCKP 39TDVP IMPORTANT Always check for gas leaks with a soap and water solution Do not use open flame for leak testing Air Shutter Settings Opening Mo...

Page 35: ...TDVN Series Gas Fireplace Heater Units GF1AT1 GF1AT2 GF1AT3 Ref Description 33TDVN 36TDVN 39TDVN 1 Log Set Complete 20008173 20007629 20008629 1a Log Front 20008190 76895 76895 1b Log Back 20007630 20007630 20007630 1c Log Top Right Twig 75318 75318 75318 1d Log top Left Twig 75319 75319 75319 2 Lava Rock Package 1lb Bag 10001454 10001454 10001454 3 Embers Platinum 78037 78037 78037 4 Burner Tube ...

Page 36: ...002500 20002500 18 Piezo Ignitor SIT 820 Valve 52464 52464 52464 19 Gas Valve SIT 820 RN 52677 52677 52677 20 Conversion Kit Nat to LP not shown 33DVCKP 36DVCKP 39DVCKP 21 Fan Assembly w Bracket FK24 Option 54103 54103 54103 22 Electrical Cord FK24 Option not shown 51865 51865 51865 23 Fan Temperature Sensor FK24 Option not shown 51704 51704 51704 24 Fan Speed Control FK24 Option not shown 51738 5...

Page 37: ...o a conveniently located wall socket Method B Using EB 1 Receptacle Box The EB 1 receptacle box Pt ZA1200 may be hard wired into the house supply The fan lead is then plugged into the EB 1 box For instruction on wiring the EB 1 Electrical Junction Box see the earlier chapter in the Installation section of this manual FK12 This auxiliary fan system increases the efficiency of the circulation of the ...

Page 38: ...iring Instructions Black White Ground FP394 WIRING DIAGRAM 11 20 96 Fan Temperature Sensor Speed Control FP1025 Fig 53 FK24 fan wiring Ceramic refractory panels are available in kit form for the RDV TDV series appliances Discard small angular panels 5 Place the rear refractory panel in place 6 Slide the side refractory panels into place to hold the rear panel secure Adjust the top adjustable tabs ...

Page 39: ...liances Do not remove existing window frame assembly Remove all plastic from brass trims 1 Let the fireplace cool down if it has been operating 2 Remove existing top louvre from fireplace by lifting up and pulling out 3 Hang Bay Window Screen Frame Assembly over top of existing window frame assembly FP1234 Bay window 11 02 Top Louvre Bay Window Frame Ceramic Refractory Ceramic Refractory Screws Bott...

Page 40: ...ed Alteration of the Product in any way is prohibited and voids any and all war ranties Removal of the data plate alters the Product and voids the warranty The installer must have completed the installation and Startup Checklist a copy of which must be sub mitted along with proof of purchase to obtain prior approval for warranty repair or replacement and to affect a warranty claim The Checklist is...

Page 41: ... size adequate for input rating BTU s per hour of fireplace per National Fuel Gas Code NFPA54 in the case of USA installations or Installation Code CAN 1 149 in the case of Canadian installations Make following checks Gas line integrity at supply line connection Glass front panel position Correct gas pressure Inlet Pressure __________ inches w c Manifold Pressure __________ inchesw c Piezo ignitor ...

Page 42: ...e adequate for input rating BTU s per hour of fireplace per National Fuel Gas Code NFPA54 in the case of USA installations or Installation Code CAN 1 149 in the case of Canadian installations Make following checks Gas line integrity at supply line connection Glass front panel position Correct gas pressure Inlet Pressure __________ inches WC Manifold Pressure __________ inchesWC Piezo ignitor functi...

Page 43: ...dotted line To register your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products Attn Warranty Registration 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Model ______________________________________ I certify that I have followed all codes and regulations and adhered to the TEMCO installation instructions I have completed the proper installa...

Page 44: ... Model EnerGuide Ratings Fireplace Efficiency 33TDVN 54 2 33TDVP 54 2 36TDVN 54 89 36TDVP 54 89 39TDVN 61 8 39TDVP 61 8 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation ...

Reviews: