Installation Instructions 

 

WARNING! DO NOT MOUNT THE UNIT YET! 

 

This unit is a cellular communications device. 

THE ANTENNA MUST NOT BE INSTALLED IN THE BASEMENT! 

 

1.  Connect the power. 

Connect the Telguard TG-9 to the 12v DC power output from the alarm panel or to a 9-15v 
DC (250 mA minimum) power supply. Ensure that the LEDs come on. 

Important:

 

The 2.5mm port on the side of the TG-9 is for programming and 
diagnostics only. It is not a power input and installer shall not insert 
any type of jack or other device into this port.

 

 

2.  Check the signal strength. 

Look at LED 1 and compare it to the following chart. 

 
 

 
 
 

 
If the light is not green flashing or green solid, move the unit or antenna around until a green 
flashing or green solid is achieved. 
 

 

3. Activate 

the 

unit. 

Short Trip Input 6 (the bottom two terminals). LED 2 should go from 

RED

 to 

SOLID GREEN

This indicates that the unit is registered and active. This may require up to 3 minutes. 

Note

If using Bell input, Bell must be connected per Table 1 on page 5 before 
activating. Make sure there are no Bell alarms in progress before activating.

 

 
If a 

FLASHING RED 

appears on LED 2, the unit has failed registration. This usually indicates 

that the Activation Form has not been completed. If this occurs, call Telular Technical 
Support at 

800-229-2326. 

 

4.  Connect the trip inputs. 

The trip inputs on the TG-9 should be connected according to the TG-9 Operation Profile 
selected for the unit. (Consult the installation diagram on the opposite page.) All zone inputs 
require an E.O.L. resistor (supplied). 

Note:

  

If zone 1 is programmed as a bell input, do not connect E.O.L. resistor.

 

 

5.  Send test signals.  

Trip zones on the system, and confirm that signals are received at the central station. 

 

6.  Connect the relay output to the alarm panel. (Optional) 

The STC relay output is a Normally Closed (N.C.) contact. The zone on the panel should be 
programmed as a 24-Hour Supervisory Zone. 
 

7.  Permanently mount the Telguard TG-9 

Green Solid 

Good Signal Strength 

Green Flashing 

Acceptable Signal Strength 

Yellow Flashing 

Weak Signal Strength 

Red 

No Signal Strength 