Telguard TG-7FP Installation & Operating Guide
24
56052401 Rev A
Appendix 4 Commercial Fire 6-hour Supervision
The NFPA 72 2013 Edition updated the requirement to supervise the transmission path at least once
every 6 hours, from an earlier version of 24 hours. This requirement is upheld in 2016 and 2019
edition as well. Telguard commercial fire products support this feature, and it must be enabled for
each panel that uses more than one path, by selecting 6-hour supervision during registration.
Appendix 5 Compliance with UL and ULC Standards
UL
Comm
Burg
UL
Comm
Fire
UL
Comm
Fire/Burg
ULC
Comm
Burg
ULC
Comm
Fire
Yes
Optional
Yes
Optional
Optional
UL/ULC/cUL Listed Bell and
Bell Housing
*
Yes
Optional
Yes
Yes
Optional
Enclosure tamper Switch
connected to 24-hour circuit
Yes
Yes
Yes
Yes
Yes
Antenna cable in flexible
conduit concealed
No
No
No
Optional
Yes
Radio Frequency warning
label placed on outside of
front cover
Optional
Yes
Yes
Optional
Yes
Flexible or Rigid conduit
required to protect
connections #
NOTES:
*
Use Mercantile Listed bell and bell housing
# All conductors of a fire alarm system shall be installed in metal raceway of the totally enclosed
type or incorporated in a cable having a metal armour or sheath; these metal elements must be
grounded