Telemark TT Cheetah Series Power Supply Instruction Manual
13
Figure 4-C Suggested Ground Installation
Interlock Connections
It is extremely important for operator and equipment safety that the external interlocks are
appropriately installed (see page 20 and section 7, Figures 8-A through 8-E).
Symbol Definitions
Protective Conductor Terminal
Indicates where to connect safety ground conductor for
AC line source and system ground.
Caution: Risk of Electric Shock
Indicates that high voltages, capable of causing injury, are present on the
output connector.
Caution: Refer to Manual for Further Instructions
Directs user to manual for further detailed instructions on installation and
operation.
CAUTION!!!
The instrument rack (for TT-3/6/8)
must not block air passages located on the unit’s
front and
rear panels. Fans in the lower center of the rear panel pull in air for the power tube and fans
in the upper corners extract air from the unit. Allow for ample clearance for adequate air flow.
The rear of the instrument rack in the area of the HVPS MUST NOT be closed in order not to
obstruct air flow to/from the fans.
The HVPS cabinet (TT-10/15/20) must be placed in such a way that neither the air intake at
the front panel, nor the air intakes and exhausts by the fans on the rear panel are obstructed.
Ample clearance (at least 20 inches or 500mm) must be kept from both front and rear panel.
Power Tube Installation
The TT-3 and TT-6 are equipped with an indirectly heated oxide cathode power tetrode that
can be left in the power supply during shipping.
Sweep
Power Supply
Power Supply
Controller
Filament
Transformer