TELEFRANG AB

SIOX Climate Controller Module T05

General Description

T05 is a general microprocessor controller
with enhanced PLC programmability and
SIOX field bus communication. It
comprises two analog outputs and two
inputs. Analog input 1 handles voltage /
current or thermistor input. Analog input 2
is preconnected for thermistor input.
Three digital inputs, two outputs, two
power relays and one alarm relay are
included.
T05 can work standalone or together with
other SIOX I/O modules communicating
over a common wire pair for climate
control, energy optimisation and alarm
handling.

Versions

:  T05, SIOX Climate Controller with 2 relay outputs, four cable

glands and built-in NTC thermistor at AI2 for local temperature
measurement.

T05-1,  SIOX Climate Controller with 3 relay outputs, 3-6 DI, 0-
2 DO, 2-3 AI and 2 AO. A 230 V mains transformer is included.

T05-3, SIOX Heat Exchange Controller with 4 relays, 5 DI, 2 AI
and 2 AO.

T05-4, SIOX Heat Exchange Controller with 4 relays, 5 DI, 2 AI,
2 AO and a Setpoint potentiometer / Mode button.

H:\T05\Man\T05man.wpd/2008-04-07/TF

                   T05 CLIMATE CONTROLLER MODULE  p 2

328/287

General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Installation and Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Address Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Analog Output Overrange / Underrange . . . . . . . . . . . . . . . . . . . . . . . 6

Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Digital Outputs / Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Indicator LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

SIOX Message Transfer for T05 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Parameter Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Parameter Specifics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Summary of Contents for SIOX T05

Page 1: ...hermistor at AI2 for local temperature measurement T05 1 SIOX Climate Controller with 3 relay outputs 3 6 DI 0 2 DO 2 3 AI and 2 AO A 230 V mains transformer is included T05 3 SIOX Heat Exchange Controller with 4 relays 5 DI 2 AI and 2 AO T05 4 SIOX Heat Exchange Controller with 4 relays 5 DI 2 AI 2 AO and a Setpoint potentiometer Mode button H T05 Man T05man wpd 2008 04 07 TF T05 CLIMATE CONTROLL...

Page 2: ...ti Surge HRC High Rupture Capacity fuses T05 CLIMATE CONTROLLER MODULE p 4 T05 1 can alternatively be powered from 230 V mains via a built in transformer This connection is shown on next page and must use a separate Pg16 cable gland and include an external power switch and a fuse of max 10 A The current of the two digital outputs are however limited to some 10 mA each by the transformer capacity I...

Page 3: ...in the RAM parameter 0 1 and used for all subsequent communications until this parameter is changed or a new power up is performed Changing the RAM address can be done from the master or from the local PLC program in the module but make absolutely certain to avoid collision with other modules on the bus T05 CLIMATE CONTROLLER MODULE p 6 A special feature is added to help recover lost modules i e w...

Page 4: ...arameter 3B retains the last reading T05 CLIMATE CONTROLLER MODULE p 8 Digital Inputs Four digital inputs sensing contact closures are available marked DI1 DI3 and DI6 They can be manipulated in software to provide a 0 to 1 or 1 to 0 change only when their level has been stable for more than a preset time from 1 ms to 1 s This debounce time is preset in EEPROM parameter nr 3 refer to page 17 Digit...

Page 5: ...ical communication for setting the analog value for channel 2 parameter 0 D in String Mode will be From central C0 0 9 38 44 30 38 30 30 BE 74 Address 9 write 0 D 0 8 0 0 Sign off Set AO2 to 5 V Checksum Answer from T05 30 38 30 30 BE 79 0 8 0 0 Sign off Checksum Value 0 80 0 hex T05 CLIMATE CONTROLLER MODULE p 10 To permanently change the output range to 2 10 V a write data 0 0 40 to EEPROM param...

Page 6: ... no debounce i e 1 ms between readings TT 01 to FF debounce in 4 ms steps from 4 ms to 1 s T05 CLIMATE CONTROLLER MODULE p 12 Pos Value Function hex hex 0 4 0 5 4xxx 2 10 V 0 4 2 V 4 20 mA Range for AI1 AI2 28xx Potentiometer Linearisation 0 20 k for AI1 AI2 20 xx 0 2 V Range for AI1 AI2 18xx NTC Temperature Linearisation 50 150 C 0 8xx 0 20 mA Range for AI1 AI2 0 0 xx 0 10 V Range for AI1 AI2 xx4...

Page 7: ...CONTROLLER MODULE p 14 Pos Value Function hex hex 3C 3F Free Memory for PLC use Optional extra counters 40 6F Communication Parameter Pairs for Spy or PLC use 70 71 0 0 0 1 10 V Range Trim Gain for AI1 AI2 10 0 0 Min gain 0 0 0 1 1 4096 FFFF No adjustment 10 0 0 or 0 0 0 0 1 Max gain FFFF 65535 4096 72 73 0 0 0 1 20 mA Range Trim Gain for AI1 AI2 10 0 0 Min gain 0 0 0 1 1 4096 FFFF No adjustment 1...

Page 8: ...ication Data Mode uses only parity checking for maximum efficiency To avoid stray errors to set a digital output setting this flag requires new data to the outputs to be sent twice before the change is carried out T05 CLIMATE CONTROLLER MODULE p 16 Parameter 0 3 DI Debounce Time Setting this parameter to a non zero value eliminates noise from bouncing contacts or electrical interference which othe...

Page 9: ...ices located in immediate connection to the unit and adequately marked must be installed in the mains and relay circuits to provide protection against electric shock hazard during installation and service Likewise a disconnect device must be provided for the power supply when powering the unit with a 18 35 V DC supply The disconnect devices must be able to disconnect all connections to the unit wi...

Page 10: ... Operating Storage Temperature 20 55 C Mechanical Specifications Case Size 130 x 94 x 58 mm Weight 380 g Assistance on safety and technical matters is available from TELEFRANG AB Varbergsgatan 8 S 412 65 GÖTEBORG SWEDEN Tel 46 31 40 30 60 Fax 46 31 40 20 25 E mail info telefrang se ...