Telefire
ADR-3000 – System Introduction
Revision 1.10 4 November 2004
2.5 ADR-3003 Display and Keyboard Module
The ADR-3003 Display and Keyboard Module includes
system indicators, display and keyboard. System
indicators and keyboard conform to both EN 54 and
UL 864 standards.
The alphanumeric display is a 4 row by 40 characters
backlit Liquid Crystal Display (LCD).
ADR 3000
Figure 5
ADR-3003 Keyboard and display
2.6 ADR-4004TSW Switching Power Supply
The ADR-4004TSW is a standard switching power supply that is common to the
ADR-3000, GSA-1000, and the TPS-34A.
The ADR-3000 should be connected to a separate dedicated 230 V
AC
fire alarm circuit,
labeled “FIRE ALARM”. The primary power circuit must be
connected to the line side of the main power feed of the
protected premises. No other appliance may be connected to
the “FIRE ALARM” circuit. The power cables must run directly,
without disconnecting devices, from the power source to the
control panel. Wires, circuit breaker or any over-current
protection device should comply with local electrical wiring
codes.
POWER OUT
JP1
230VAC
JP2
BAT
F1
6.3A
Main Fuse
3.15A
L
N
The power cable should enter the control panel through either
the top left or bottom left knockout hole. Use a plastic bushing
that fits the opening.
Connect the Live and Neutral wires to the proper terminal.
Connect the ground wire to the ground terminal.
Figure 6
ADR-4004 Power supply module
2.7 LON-3000 Network Communication Module
The LON-3000 is a communication module that
enables connection between control panels to
establish a network. A two-wire copper cable
connection is required to interconnect between the
control panels. Optionally fiber-optic connection is
made possible with additional module. The length
of the wires depends on the connection topology
and media type (copper or fiber optic). Please
refer to the LON-3000 technical manual for further
details.
J2
J1
SW1
SW2
JP1
FREE
BUS
Connector to other
LON-3000
(polarity insignificant)
Connector to
LON-COM on
main board
Termination
jumper
D1
D14
D2
Figure 7
LON-3000 Networking communication module
2.7.1 Topology
An ADR-3000 LonWorks network can connect from 2 and up to as many as 32
ADR-3000 control panels in a peer-to-peer network. The physical topology of the
network may be bus (figure 8), ring (figure 9) or free (figure 10) topology. Logical
hierarchy may be peer-to-peer – where all messages are reported in all control panels,
– Page 5 –