![Telect GMT Series Installation Manual Download Page 7](http://html.mh-extra.com/html/telect/gmt-series/gmt-series_installation-manual_1080055007.webp)
© Telect, Inc. All rights reserved. 3.6.17 v.2
1.509.926.6000 :: telect.com
Low-Current 20/20 GMT Series Fuse Panels
Power :: Models 06004-01 & 06004-11 Installation Guide
4
Electrical Interface:
Specifications:
Operating voltages, nominal
-24 VDC to -48 VDC
Current capacity
06004-01 20A per bus (40A total for both buses), max. with 20A ceramic input
fuse (Type ABC)
06004-11 15A per bus (30A total for both buses), max. with 20A ceramic input
fuse (Type ABC)
Fuse capacity
20 (each side)
Maximum output interruption device rating
10A GMT fuse
Maximum continuous output load rating
7A for a 10A fuse
Alarm contact relay
2A @ 30 VDC
Panel heat dissipation per 20A bus
3.9W (13.3 Btu/hr) @ 0% load
Percentage of full load heat dissipation at
nominal voltage
Less than 1% of total load wattage
Reliability:
MTBF
200,000 hr
1.3 Inspection
Please read these instructions carefully before beginning installation. If you need assistance, call Telect at
509-926-6000 or email Telect at [email protected].
Inspect equipment after unpacking and compare it to the packing list.
Immediately report any shipping damage, defects or missing parts to Telect at 509-926-6000.
Keep all documentation that comes with your shipment.
Telect is not liable for shipping damage. If the product is damaged, notify the carrier and call Telect at 509-926-6000 or
email Telect at [email protected]
NOTE
: For service or warranty information, please visit the Telect website at www.telect.com, email inquiries to
[email protected] and click on the “Support” tab, or phone Telect at 509-926-6000.