![Telect GMT Series Installation Manual Download Page 6](http://html.mh-extra.com/html/telect/gmt-series/gmt-series_installation-manual_1080055006.webp)
© Telect, Inc. All rights reserved. 3.6.17 v.2
1.509.926.6000 :: telect.com
Low-Current 20/20 GMT Series Fuse Panels
Power :: Models 06004-01 & 06004-11 Installation Guide
3
1.2 Specifications
Physical:
Specifications:
Dimensions (nominal without bracket)*
Width:
17 in. (432 mm)
Height:
1.75 in. (44.4 mm)
Depth:
9.25 in. (235 mm)
Weight
8.5 lb (~3.8 kg)
Ground terminals
Screws:
#10-32 Phillips** panhead
Torque:
20 in.-lb (~2.26 N•m), max.
Wire:
Same size as input terminals
Ring Lug:
Burndy T1010, 12 AWG, no insulation; AMP 35771,
12-10 AWG, no insulation
Material††
Cold-rolled steel, powder-coat telcom grey
* See “1.7 Schematics” on page 12 for complete dimensions
** Screws with cross-recessed heads
†† Custom color/finish available
Mechanical:
Specifications:
Input terminals
Type:
Screw-tight, wire-clamping
Wire:
14 to 6 AWG, copper wire
Torque:
16 in.-lb (1.80 N•m), max.
Output terminal
Type:
Screw-tight, wire clamping
Wire:
22 to 14, copper wire
Torque:
4.5 in.-lb (0.51 N•m), max.
Alarm terminals–Wire wrap
.045 in. square wire-wrap pins on .200 in. centers.
Use 18 to 22 AWG copper
Environment:
Specifications:
Temperature range, ambient
-17°C to 49°C (0°F to 120°F)
Humidity
0% to 90%, non-condensing