© Telect, Inc., All Rights Reserved, 132505-5 A0
1.509.926.6000 :: telect.com
8
Dual-Feed 350A 8/8-TPA & 10/10
GMT Fuse Alarm Panel
Power
:: 009-8005-0810
35.
Make sure the load devices are switched off and
then install the fuses:
NOTE: Under load, TPA modules are disconnect
devices only and must not be used to reconnect
power to enabled equipment loads. Reconnecting a
TPA module under power with an enabled load may
damage the TPA module.
• For a TPA fuse, pull out TPA fuse carrier and insert
operable fuse, as shown in Figure 9.
• For a GMT fuse, pull out the dummy fuse, and
insert an operable fuse, as shown in Figure 10.
36.
Test power and polarity at input of each equipment load.
37.
If possible:
• Temporarily replace one of the operable TPA fuses
with a blown fuse to check that the TPA Fuse LEDs
light red. Also, check the
FUSE
alarm terminals on
the rear of the panel:
− Expect an open circuit (00Ω) between Terminals
C
and
NC
.
− Expect continuity (0Ω) between Terminals
C
and
NO
.
Re-install the operable TPA fuse before proceeding.
• Likewise, replace one of the operable GMT fuses
with a blown fuse to verify that the
FUSE
alarm
terminals are also as specified above. Then re-install
the operable GMT fuse before proceeding.
38.
If desired, connect the remote external audio/visual
alarm indicator wires (solid or tinned wires, #26 to
#20 AWG) to the
PWR
and
FUSE
alarm terminals,
as implied in Figure 11.
39.
Carefully re-install the rear cover.
40. Record the TPA and GMT output destinations in
accordance with operating company procedures
and guidelines.
41.
Turn on equipment loads one at a time to verify the
proper operation of the loads.
TPA Fuse
TPA Fuse Holder
Dummy
Fuse
GMT Fuse
NC
C
A
PWR
B
PWR
FUSE
NO
NC
C
NO
NC
C
NO
A
B
FUSE
To Alarm System
To Alarm System
Figure 9 - Installing TPA Fuses
Figure 10 - Installing GMT Fuses
Figure 11 - Wirewrap Alarm Terminal