4
Dual 150A 4/4 TPA/GMT Fuse Alarm Panel
Power
:: 009-8005-3404H
1.4 Installation Procedure
ALERT
!
ALERT! Only qualifi ed personnel may install and maintain this product. Verify that all connections meet
the requirements specifi ed in local electric codes or operating company guidelines before supplying
power. Protect this equipment with a fuse or breaker sufficient to interrupt power levels specifi ed on
preceding page.
Panel brackets provide either fl ush or extended EIA or WECO mounting in a 19" or 23" rack. (See telect.com to
order ETSI brackets.) The panel is confi gured at the factory for fl ush mounting in a 19" rack.
1. If necessary, remove three screws and reposition/re-align the brackets on the sides of the distribution panel,
as shown in Figure 2.
2. Locate an unused rack position and mount the panel using the four screws and lock washers provided, as
shown in Figure 3. (It’s best to mount the panel as high as possible on the rack.)
3. Tighten the screws to 35 in.-lb (4.29 N•m).
Figure 2 - Bracket Orientation
Figure 3 - Rack Mounting
4. Loosen (you need not remove) the two screws securing the rear terminal cover on the back of the panel.
5. Remove the cover.
WARNING
!
WARNING! Failure to properly ground this equipment can create hazardous conditions to installation per-
sonnel and to the equipment.
ALERT
!
ALERT! Only use components and crimping tools approved by agencies or certifying bodies recognized
in your country or region such as Underwriter’s Laboratories (UL), TUV, etc.