![Telect 009-8005-3404H User Manual Download Page 4](http://html.mh-extra.com/html/telect/009-8005-3404h/009-8005-3404h_user-manual_1080052004.webp)
© Telect, Inc., All Rights Reserved, 143252-1 A0
1.509.926.6000 :: telect.com
2
Dual 150A 4/4 TPA/GMT Fuse Alarm Panel
Power
:: 009-8005-3404H
1.3 Specifi cations
Inputs
Voltage Range (Nominal Voltage)
-40V to -60V (Nominal -48Vdc)
Max. Input Load Rating
150A per feed
Power Dissipation at Full Load
0.2 Watts/Amp per bus
Percentage of Full Load Power Dissipation at
Nominal Voltage
Less than 1%
Max. Input Interrupt Device
187A
Input Terminals
Two pairs of 1/4"-20 studs on 5/8" centers per terminal
(max. lug width of 0.64” [15.7 mm]). Torque nut (using
7/16 in. or 12 mm wrench) to 50 in.-lb (5.65 N·m), max
Input Wire Size
#8 AWG to 2/0 AWG
TPA Outputs
Max. Output Interrupt Device
50A
Max. Continuous Output Load
40A
Max. Total Output Load
120A
Output Terminals
16, #8-32 terminal screws (max. lug width of 0.378"
[9.60 mm]). Torque to 15 in.-lb (1.69 N·m), max.
Output Wire Size
#16 AWG to #8 AWG
GMT Outputs
Max. Output Interrupt Device
15A
Max. Continuous Output Load
12A
Max. Total Output Load
24A
Output Terminals
16, #8-32 terminal screws (max. lug width of 0.378"
[9.60 mm]). Torque to 15 in.-lb (1.69 N·m), max.
Output Wire Size
#16 AWG to #8 AWG
Grounding
Chassis GND Terminals
1/4"-20 studs on 5/8" centers. Torque nut (using 7/16 in.
or 12 mm wrench) to 25 in.-lb (2.82 N·m), max.
GND Wire Size
#10 AWG to #4 AWG
Alarms
Alarm Relay Contacts
2A @ 24Vdc
0.6A @ 48Vdc
1A @ 120Vac
Max. Alarm Power Rating
@48V: 130 mA (6.2 W)