Dual 150A 4/4 TPA/GMT Fuse Alarm Panel

Power

  ::  009-8005-3404H  ::  009-8005-3404HRC

User Manual

© Telect, Inc.,  All Rights Reserved, 143252-1 A0
1.509.926.6000  ::  telect.com

Applies to

 :  009-8005-3404H and 009-8005-3404HRC

Summary of Contents for 009-8005-3404H

Page 1: ...ual 150A 4 4TPA GMT Fuse Alarm Panel Power 009 8005 3404H 009 8005 3404HRC User Manual Telect Inc All Rights Reserved 143252 1 A0 1 509 926 6000 telect com Applies to 009 8005 3404H and 009 8005 3404HRC ...

Page 2: ... Accessories 10 1 7 Schematic Drawing 11 1 8 Assembly Drawing 12 List of Figures Figure 1 Model 009 8005 3404H HRC 1 Figure 2 Bracket Orientation 4 Figure 3 Rack Mounting 4 Figure 4 Ground Lug Connection 5 Figure 5 Input Lugs 5 Figure 6 Disengaging a TPA Fuse Holder 6 Figure 7 Alarm Indicators 6 Figure 8 Alarm Terminals 6 Figure 9 Output Lug Connections 7 Figure 10 Installing TPA Fuses 7 Figure 11...

Page 3: ...re is included for flush or extended mounting in 19 in or 23 in relay racks Visit our website for ordering Telect accessories and replaceable parts TPA fuses 3A 50A GMT fuses 15A ETSI mounting kit and more Model 009 8005 3404H is UL listed File E139903 V1 S9 Model 009 8005 3404HRC is RoHS 6 6 compliant 1 2 Inspection Please read and understand all instructions before starting installation If you h...

Page 4: ... max Input Wire Size 8 AWG to 2 0 AWG TPA Outputs Max Output Interrupt Device 50A Max Continuous Output Load 40A Max Total Output Load 120A Output Terminals 16 8 32 terminal screws max lug width of 0 378 9 60 mm Torque to 15 in lb 1 69 N m max Output Wire Size 16 AWG to 8 AWG GMT Outputs Max Output Interrupt Device 15A Max Continuous Output Load 12A Max Total Output Load 24A Output Terminals 16 8 ...

Page 5: ... Nominal Width 17 25 438 2 mm Height 1 72 43 7 mm Depth 9 76 247 1 mm Mounting Capability 19 482 6 mm or 23 584 2 mm EIA WECO Weight Without Packaging and Accessories 14 lbs 6 4 kg Weight Shipping 15 lbs 6 8 kg Material Cold rolled steel Color White powder coat Environment Operating Temperature Range 5 C 23 F to 55 C 131 F Humidity 0 to 90 and non condensing Note Wire sizes are recommended based o...

Page 6: ...nting in a 19 rack 1 If necessary remove three screws and reposition re align the brackets on the sides of the distribution panel as shown in Figure 2 2 Locate an unused rack position and mount the panel using the four screws and lock washers provided as shown in Figure 3 It s best to mount the panel as high as possible on the rack 3 Tighten the screws to 35 in lb 4 29 N m Figure 2 Bracket Orienta...

Page 7: ...ecting input power cables make sure input power to panel is turned off 9 Tighten the KEPS nuts to 25 in lb 2 82 N m 10 Make sure the input power is off open breaker dummy fuse or open the fuse holder at the power distribution unit PDU before connecting this panel s input cables to the PDU 11 For input wiring wiring used as inputs to this distribution panel crimp the dual hole compression lugs onto...

Page 8: ...t with all other LEDs off failure operation test the power fail relay contacts at the rear of the panel Expect an open circuit 00Ω between Terminals C and NC Expect continuity 0Ω between Terminals C and NO 19 Also test the fuse alarm relay contacts at the FUSE ALARM terminals on the rear of the panel Expect continuity 0Ω between Terminals C and NC Expect an open circuit 00Ω between Terminals C and...

Page 9: ... terminal 27 Tighten the screw to 15 in lb 1 69 N m Figure 9 Output Lug Connections ALERT ALERT Local electrical and operating company guidelines recommend that the individual load not exceed 80 of over current device capacity for example 50A TPA fuse x 80 40A max load Total load for all TPA GMT outputs on each side must not exceed 150A 28 Connect the other end of the output wire to load 29 Make s...

Page 10: ...C Expect continuity 0Ω between Terminals C and NO Re install the operable TPA fuse before pro ceeding Likewise replace one of the operable GMT fuses with a blown fuse to verify that the FUSE ALARM LED and FUSE ALARM terminals are also as specified above Re install an operable GMT fuse before proceeding 32 If desired connect remote external audio visual alarm indicator wires solid or tinned wires 2...

Page 11: ...e Ground Lugs 1 4 Dual Holes on 5 8 in Centers Uninsulated 8 AWG 6 AWG 4 AWG 2 AWG T B 256 30695 1356 T B Die Code 24 Burndy YA8LC 2TC14 90 Die Code 49 YA6CL 2TC14 90 Burndy Die Code 7 YA4C 2L 90 Burndy Die Code 8 YA2CL2NT14 90 Burndy Die Code 10 Panduit LCD8 14AF L Die Code 21 LCD6 14AF L Die Code 24 LCDN2 14AF Q Die Code 33 Narrow tongue Telect assumes no liability from the application or use of...

Page 12: ... Description Part Number TPA Fuses 5A 124818 10A 124819 15A 124820 20A 124821 25A 125244 30A 122734 40A 122738 50A 122739 GMT Fuses A Violet VIO 100151 A Red RED 004001 A Brown BRN 004008 1A Gray GRY 100991 11 3A White WHT 004006 1 A White Yellow WHT YEL 004011 2A Orange ORN 004002 3A Blue BLU 004012 4A White Brown WHT BRN 004013 5A Green GRN 004014 7 A Black White BLK WHT 004010 10A Red White RED...

Page 13: ...BATT A1 A2 A3 A4 A1 A2 A3 A4 TPA OUTPUT BATT A TPA OUTPUT TPA OUTPUT TPA OUTPUT BATT B INPUT B PWR A PWR B FUSE ALARM TPA FUSE HOLDER LEDS TPA FUSE HOLDER LEDS C GND INPUT A NO C NC NC C NO B1 B3 B2 B4 B3 B1 B2 B4 B5 B6 B7 B8 A8 A6 A7 A5 GMT OUTPUT GMT OUTPUT GMT OUTPUT B6 B5 BATT B B8 B7 GMT OUTPUT BATT A A7 A8 A6 A5 FUSE ALARM POWER FAIL 1 7 Schematic Drawing ...

Page 14: ... 4TPA GMT Fuse Alarm Panel Power 009 8005 3404H 1 8 Assembly Drawing 22 31 56 67 23 00 58 42 18 31 46 51 17 25 43 82 19 0 48 3 1 72 4 37 1 00 2 54 730 1 85 625 1 59 375 0 95 313 0 79 641 1 62 8 38 21 28 44 1 10 1 01 2 57 10 0 25 10 20 25 89 4 00 10 16 8 screw 1 4 stud 1 4 stud 8 screw ...