6
High Air -
will be displayed if the airflow is more than the High air alarm point.
This display will alternate on/off with the velocity reading
Set-back
- will be displayed if the night set-back function is activated ( when
enabled )
This display will alternate on/off with the velocity reading
Disabled
- will be displayed if the alarm disable function is activated ( when
enabled )
This display will alternate on/off with the velocity reading
LED Indicators
---- the alarm unit has three LED indicators :-
Red
-- Low
Amber
-- Caution
Green
-- Normal
Audible Alarm sounder
-- the alarm has an audible alarm sounder with local or
remote Mute facility
Enter
--- the alarm has an Enter button -- this is multi-functional as follows :-
Press
Enter
momentarily when alarm is sounding will mute the alarm.
The horn can be permanently disabled using the configuration menu.
When this option is selected the Horn Icon with the word OFF will
permanently appear on the display.
Press
Enter
for 5 secs will gain access to
Calibration
and
Configuration
menus ( both menus password protected )
+ / -
-- the alarm has + / - buttons that can be used to scroll through the
calibration and
configuration menu or to select options or values