Kona Home Sensor TRM
T0005370_TRM
Version Rev-C 1.0
TEKTELIC Communications Inc.
Confidential
Page 15 of 34
3.4
Sensor Application Configuration
Note
: Care must be taken to avoid stranding the Sensor during reconfiguration. If all Sensor
transducers are disabled, the Sensor cannot be reconfigured.
3.4.1
Periodic Tx Configuration
All periodic transducer reporting
is synchronized around ‘ticks’. A
tick
is simply a user
configurable time-base that is used to schedule transducer measurements. For each transducer,
the number of elapsed
ticks
before transmitting can be defined.
Note:
Certain transducer types, such as accelerometer and light, need to be enabled for
periodic reporting. Details are available in each
transducer’s
respective section. Table 3-3 shows
a list of registers used to configure the Sensor’s periodic transmissions.
Table 3-3: Periodic Transmission Configuration Registers
Address Access Value
Size
[bytes]
Description
0x20
R/W
Seconds per
tick
4
Sets the
tick
for periodic events. A value of 0
disables all periodic transmissions.
0x21
R/W
Ticks
per Battery
Tx
2
Ticks
between Battery reports. A value of 0
disables periodic battery reports.
0x22
R/W
Ticks
per
Temperature Tx
2
Ticks
between Temp reports. A value of 0
disables periodic Temp reports.
0x23
R/W
Ticks
per RH Tx
2
Ticks
between Humidity reports. A value of 0
disables periodic Humidity reports.
0x24
R/W
Ticks
per Digital
Input Tx
2
Ticks
between Digital Input reports. A value of
0 disables periodic Digital Input reports.
0x25
R/W
Ticks
per Light Tx
2
Ticks
between Light reports. A value of 0
disables periodic Light reports.
0x26
R/W
Ticks
per
Accelerometer Tx
2
Ticks
between Accelerometer reports. A value
of 0 disables periodic Accelerometer reports.
0x27
R/W
Ticks
per MCU
Temp Tx
2
Ticks
between MCU Temp reports. A value of
0 disables periodic MCU Temp reports.
0x28
R/W
Ticks
per PIR Tx
2
Ticks
between PIR reports. A value of 0
disables periodic PIR reports.