Rev. 4245-v3_2_en
4
Step-4
Activate
«
Test
»
mode in accordance
with the appropriate Astra-Zitadel
System Control Panel`s
Operating
Manual*
or using the
LT
:
- Press the upper button on the LT;
- Direct the laser beam at the
detector LED;
- Irradiate the LED for 1 second:
In 5 seconds make sure
«Fire» notification appears on the
LED
– the
red
LED lights up for
10 seconds
. A
«Test fire»
event is recorded in the control panel (or MSS interface)
event log.
9.3
To ensure the alarm system reliable operation,
testing
and
maintenance
of the detector is recommended.
Testing
should be carried out as follows:
-
Check absence/output of the
«Failure» notification on the
LED at least
once a week
;
-
Check the detector operability by using a laser tester at least
once a month
.
Perform
technical maintenance
at least
once in 3 months
as follows:
- Inspect the detector housing integrity and reliability of its
mounting;
- Purge the detector from contamination;
-
Clean the detector
’s smoke chamber with compressed air.
Detecting severe dust of smoke chamber (dust level value
greater than 50 units) during the process of testing or issuing
the "Failure" notification requires unscheduled cleaning of the
smoke chamber.
Dust level value is displayed:
- in the
“Engineer menu / 2 Wireless network / 5 W/devices
status
”
for
Astra-Z-812M
Control Panel;
- in the
“Wireless devices / Device type”
tab of
Monitor
module from
Astra-Z MSS
for Astra-Z-8945 ver.A Control
Panel, or in the
“Wireless devices / Device type”
tab of
Monitor
module from
Astra Pro MSS
for Astra-8945 Pro and
Astra-812 Pro Control Panels. Launch test of the detector from
right-click menu (Launch SD/HD test), observe dust level value
in the
“Dust level value / Temperature”
column.
10 Labeling
The following information is marked on the label attached to the
detector housing:
- manufacturer trademark;
- abbreviated detector designation;
- firmware version;
- month and year (last two digits) of manufacture;
- conformity mark (if the conformity certificate is available);
- bar-code that duplicates textual information.
11 EC Conformity Declarations
This product is in conformity with the provisions of:
R&TTE Directive 1999/5/EC, Article 10.5;
EN 60950: 2001 Safety of information technology equipment;
EN 50371 Generic standard to demonstrate the compliance of low-
power electronic and electrical apparatuses with the basic restrictions
related to human exposure to electromagnetic fields (10 MHz - 300
GHz)
– General public;
EN 301489-17 V1.1.1 (09-2000) Electromagnetic Compatibility and
radio spectrum Matters (ERM); Electromagnetic Compatibility (EMC)
standard for radio equipment and services; Part 17: Specific conditions
for wideband data Hiperlan equipment;
EN 300220-1 V1.3.1 (2000-09) Electromagnetic compatibility and
Radio spectrum Matters (ERM); Short range devices; Technical cha-
racteristics and test methods for radio equipment to be used in the 25
MHz to 1 000 MHz frequency range with power levels ranging up to
500 mW; Part 1: Parameters intended for regulatory purposes.
Construction of the detector provides for protection class IP41.
12
Recycling
12.1 The detector poses no threat to human life, health or to the
environment; after its service life is over, it can be disposed of without
any special environmental protection measures.
12.2 Recycling of battery cells should be done by delivering used
cells to a trading organization, service centre, manufacturer, or to any
organization accepting used batteries.
13 Warranty Terms
13.1 Quality Management System meets provisions of ISO 9001-2011.
13.2 The manufacturer guarantees the compliance of the detector to
specifications
if
the
user
observes
required
conditions
of
transportation, storage, installation and operation.
13.3 The storage warranty period is 5 years and 6 months from the
date of manufacture.
13.4 The operating warranty period is 5 years from the startup date,
but not more than 5 years and 6 months from the date of manufacture.
13.5 The manufacturer guarantees replacement or repair of the
product during the warranty period.
13.6 The warranty
doesn’t come into effect in the following
cases
:
-
not adherence to the operating manual;
-
mechanical damage to the detector;
-
repair of the detector by any third-party service except for the
manufacturer.
13.7
The warranty applies to the detector only. All equipment from
other manufacturers used with the detector, including batteries, is
covered by its own warranties.
The manufacturer bears no responsibility for death, injury,
property damage or other incidental or premeditated loss based
on user's statement that the device failed to implement its
functions.
* Available for free downloading from
www.controlex.eu
and/or integrated with configuring software.
** Available for free downloading from
www.controlex.eu
.
Sales:
Controlex GmbH
Warranty service and
technical support:
ТЕКО-TD
Philosophenweg 31-33
47051 Duisburg, Germany
Phone: +49 (0) 203 / 393 91 188
Fax: +49 (0) 203 / 393 91 189
GSM: +49 (0) 178 / 218 48 22
E-mail:
Web:
www.controlex.eu
Prospekt Pobedy str. 19
420138 Kazan, Russia
Phone: +7 (843) 261-55-75
Fax: +7 (843) 261-58-08
E-mail:
Web:
www.teko.biz
Made in Russia