background image

Rev. 4245-v3_2_en

 

Step-4 

Activate 

«

Test

»

 

mode in accordance 

with  the  appropriate  Astra-Zitadel 
System  Control  Panel`s

 

Operating 

Manual*

 or using the 

LT

:

 

 

- Press the upper button on the LT;

 

 

-  Direct  the  laser  beam  at  the 
detector LED; 
- Irradiate the LED for 1 second: 
In  5  seconds  make  sure 

«Fire»  notification  appears  on  the 

LED 

– the 

red

  LED  lights  up  for 

10  seconds

.  A 

«Test fire» 

event  is  recorded  in  the  control  panel  (or  MSS  interface) 
event log. 

 

9.3 

To  ensure  the  alarm  system  reliable  operation, 

testing 

and 

maintenance 

of the detector is recommended. 

Testing

 should be carried out as follows:

 

-

  Check  absence/output  of  the 

«Failure»  notification  on  the 

LED at least 

once a week

-

  Check the detector operability by using a laser tester at least   

once a month

Perform 

technical  maintenance

  at  least 

once  in  3  months

 

as follows:  
-  Inspect  the  detector  housing  integrity  and  reliability  of  its 
mounting;  
- Purge the detector from contamination; 

-

  Clean the detector

’s smoke chamber with compressed air. 

Detecting  severe  dust  of  smoke  chamber  (dust  level  value 
greater  than  50  units)  during  the  process  of  testing  or  issuing 
the  "Failure"  notification  requires  unscheduled  cleaning  of  the 
smoke chamber. 
Dust level value is displayed: 
- in the 

“Engineer menu / 2 Wireless network / 5 W/devices 

status

 for 

Astra-Z-812M

 Control Panel; 

-  in  the 

“Wireless  devices  /  Device  type”

  tab  of 

Monitor

 

module  from 

Astra-Z  MSS 

for  Astra-Z-8945  ver.A  Control 

Panel,  or  in  the 

“Wireless  devices  /  Device  type”

  tab  of 

Monitor

 module from 

Astra  Pro  MSS 

for  Astra-8945  Pro and 

Astra-812 Pro Control Panels. Launch test of the detector from 
right-click menu (Launch SD/HD test), observe dust level value 
in the 

“Dust level value / Temperature”

 column.

 

 
 

10  Labeling

 

 

The  following  information  is  marked  on  the  label  attached  to  the 
detector housing: 
- manufacturer trademark; 
- abbreviated detector designation; 
- firmware version; 
- month and year (last two digits) of manufacture; 
- conformity mark (if the conformity certificate is available); 
- bar-code that duplicates textual information. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

11  EC Conformity Declarations

 

 

This product is in conformity with the provisions of: 
R&TTE Directive 1999/5/EC, Article 10.5; 
EN 60950: 2001 Safety of information technology equipment; 
EN  50371  Generic  standard  to  demonstrate  the  compliance  of  low- 
power  electronic  and  electrical  apparatuses  with  the  basic  restrictions 
related  to  human  exposure  to  electromagnetic  fields  (10  MHz  -  300 
GHz) 

– General public;  

EN  301489-17  V1.1.1  (09-2000)  Electromagnetic  Compatibility  and 
radio  spectrum  Matters  (ERM);  Electromagnetic  Compatibility  (EMC) 
standard for radio equipment and services; Part 17: Specific conditions 
for wideband data Hiperlan equipment;  
EN  300220-1  V1.3.1  (2000-09)  Electromagnetic  compatibility  and 
Radio  spectrum  Matters  (ERM);  Short  range  devices;  Technical  cha-
racteristics and test methods for radio equipment to be used in the 25 
MHz  to  1  000  MHz  frequency  range  with  power  levels  ranging  up  to 
500 mW; Part 1: Parameters intended for regulatory purposes. 
Construction of the detector provides for protection class IP41.

 

 

12 

 

Recycling

 

 

12.1  The  detector  poses  no  threat  to  human  life,  health  or  to  the 
environment; after its service life is over, it can be disposed of without 
any special environmental protection measures. 
12.2  Recycling  of  battery  cells  should  be  done  by  delivering  used 
cells to a trading organization, service centre, manufacturer, or to any 
organization accepting used batteries.

 

 

13  Warranty Terms

 

 

13.1 Quality Management System meets provisions of ISO 9001-2011. 
13.2  The  manufacturer  guarantees  the  compliance  of  the  detector  to 
specifications 

if 

the 

user 

observes 

required 

conditions 

of 

transportation, storage, installation and operation. 
13.3  The  storage  warranty  period  is  5  years  and  6  months  from  the 
date of manufacture. 
13.4  The  operating  warranty  period  is  5  years  from  the  startup  date, 
but not more than 5 years and 6 months from the date of manufacture. 
13.5  The  manufacturer  guarantees  replacement  or  repair  of  the 
product during the warranty period. 

13.6  The  warranty 

doesn’t  come  into  effect  in  the  following 

cases

:  

not adherence to the operating manual; 

mechanical damage to the detector;  

repair  of  the  detector  by  any  third-party  service  except  for  the 

manufacturer. 
13.7 

The  warranty  applies  to  the  detector  only.  All  equipment  from 

other  manufacturers  used  with  the  detector,  including  batteries,  is 
covered by its own warranties. 

The  manufacturer  bears  no  responsibility  for  death,  injury, 
property  damage  or  other  incidental  or  premeditated  loss  based 
on  user's  statement  that  the  device  failed  to  implement  its 
functions.

 

 

*  Available  for  free  downloading  from 

www.controlex.eu

 

and/or integrated with configuring software. 

** Available for free downloading from 

www.controlex.eu

.

 

 
 
 
 
 

Sales: 

Controlex GmbH

 

Warranty service and  
technical support: 

ТЕКО-TD 

 

Philosophenweg 31-33 
47051 Duisburg, Germany 
Phone: +49 (0) 203 / 393 91 188 
Fax:     +49 (0) 203 / 393 91 189 
GSM:   +49 (0) 178 / 218 48 22 
E-mail: 

[email protected]

  

Web:    

www.controlex.eu

 

 

Prospekt Pobedy str. 19 
420138 Kazan, Russia 
Phone: +7 (843) 261-55-75 
Fax:     +7 (843) 261-58-08 
E-mail: 

[email protected] 

            [email protected]

 

Web:    

www.teko.biz

  

 

Made in Russia

 

 

 

Reviews: