15
7.7.3 Battery Mode Switch Delay
Settings > Battery settings > Set switch delay
• A delay for returning to mains mode from battery mode. This is
meant for avoiding the blinking of emergency lights in a situation
where mains power is restored and lost several times in a short
period of time (as is often the case during a power failure). Set
the time, and press the selection button long to save and exit.
7.7.4 Battery Test Date
Settings > Battery test date
• Set a date for battery test. The test starts on said date, 00:00.
Note!
Take into accout local laws and legistlations concerning
battery tests. Full battery test may not be allowed to be ran
if there is people in the buiding. It may be a good idea, for
example, to time the battery test to a national holiday.
7.7.5 Password Protection
Settings > Setup password
• Set a four-digit password with the selection button. Save the pass-
word and exit by pressing the selection button long. If you want
to disable the password, set 0000 as the password.
• When the system is password protected, only the main view is
visible without the password. This means, that checking CBU
status and errors can be done without logging in.
• If you forget your password, contact Teknoware Technical Service.
7.7.6 Local Address
Settings > Local address
• This is the local address of the CBU, for ACM use.
• Set an address (1-150) with the selection button. If there are
more than one CBU in the system, make sure you write down the
address and the physical location of the CBU: this will be impor-
tant when setting the CBU location to the ACM map view.
BATTERY TEST
AUTOMATIC START
ON 01.01.2019
˄˄
BATTERY SWITCH DELAY
00 MINUTES
SETUP PASSWORD
■
***
LOCAL ADDRESS 1