background image

 

FRONT PANEL 

 

 

 

 

1.  Zone in Fire Leds 
2.  Zone Fault/ Disable / Test 
3.  Alarm Set / Reset Button 
4.  Silence Button 
5.  Disable Mode Button  
6.  Enter Button 
7.  Test mode Button 
8.  Reset Button 
9.  Keypad Lock 
10. General Alarm Led 
11. General Error Led 
 

12. System Error Led 
13. Siren Error Led 
14. Supply Error Led 
15. Earth Error Led 
16. Battery Error Led 
17. Energy Led 
18. System On Led 
19. Test Mode Led 
20. Disable Mode Led 
21. Access Level Led 
22. Comm. Mode Led 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for TFP3304

Page 1: ...ed technical stuff only All cabling should be done as indicated this manual Do not attempt to change wiring while system under power tension The panel must be earthed NEVER APPLY 230V CITY MAINS NETWORK VOLTAGE on any terminal of the electronic board DEVICE FEATURES Supports 4 or 8 Zone Has separate fire trouble off line test LEDs for each zone Has General fault LED System fault LED siren status L...

Page 2: ...back and top of the panel are available for easy mounting Firstly open the panel front cover by removing indicated screws Necessary key which take off the screws will provide with device Fix the panel on surface with provided screw apparatus by using four holes which is indicated by arrows Do not move mount of the panel from its place should be fixed steady POWER CONNECTION Make the electrical con...

Page 3: ...rn to its initial position of active relay fire condition must be ended and press on Reset button onto the panel Trouble Relay It changes contact and get active position during trouble warning and without power panel Trouble Relay returns to its initial position automatically as soon as trouble condition ends Power Output AUX There is 1 pc 24VDC 500mA lik mA power output with automatic fuse In cas...

Page 4: ...uses 2 pieces 12V 7AH batteries Zone Input Zone inputs supply to detector and button powers 24 V DC and provide to conduct signals such as fire short circuit and open circuit Each zone is capable of connecting up to 32 detectors and buttons Use 1x2x0 8 0 8JY st Y coded cable for connections between 0 500m Use 1x2x1 5 1 5J Y st Y coded cable for connections between 500 1500m Please make detectors a...

Page 5: ...e Button 6 Enter Button 7 Test mode Button 8 Reset Button 9 Keypad Lock 10 General Alarm Led 11 General Error Led 12 System Error Led 13 Siren Error Led 14 Supply Error Led 15 Earth Error Led 16 Battery Error Led 17 Energy Led 18 System On Led 19 Test Mode Led 20 Disable Mode Led 21 Access Level Led 22 Comm Mode Led ...

Page 6: ... error NO NO Supply error NO Indicates any supply error No supply Supply low or high voltage error Earth Error NO Indicates any earth error High voltage error Low voltage error Battery error NO Indicates any battery error No battery Low battery voltage Energy Indicates system powered by any supply NO NO NO System On Indicates device working properly NO NO NO Test Indicates one or more zone and sir...

Page 7: ... when test and disable turned off Turn on or turn off disable In this case disabled zones and sirens shown on the panel Enter NO Show details of errors During disable or test operation acknowledge or disacknowledge siren disable or test for the current zone NO Test Right direction Test buzzer and led Show zones and sirens in test for 3 seconds Change current zone or siren when disable is activated...

Page 8: ...hen Mains cable or the plug is harmed Contact of device with a fluid Exposure of rain and water Fell down of device or harmed outer cover Serious performance fall on the device Depending on the instructions stated in manual if your device not working properly further usage or possible wrong usage may cause other malfunctions Contact with your authorized service in such terms SPARE PART If the repa...