General Information
TFM-1190 Analogue Addressable Conventional Zone and Siren Module, is a module designed to be used with
TFP-12xx series addressable fire alarm panels and allows the use of conventional devices in the addressable
system, which can transmit alarm and fault informations via the loop in a zonal sense and gives a siren
output. For the conventional input status, the user can choose between the event types "Alarm, Evacuation,
Reset, Silent, Fault, None". It is also possible to select from "Siren, General Siren, General Fault, Zonal Alarm,
Zonal Siren, Zonal Fault, None" event types for siren output. The module has 24V external power supply
input. The external supply is used for the supply of conventional devices and the siren outputs. The external
supply is supervised for interruptions on power.
The TFM-1190 modules are addressed by the TFCM-1801 Addressing Module. With the use of the module,
address repetition error is prevented. The addressed detector can be used quickly and easily by adding on a
loop as described in the "TFP-12xx Series Analogue Addressable Fire Alarm Control Panel Installation &
Operation Manual".
General features
•
Adjustable short circuit, open circuit and alarm current values
•
Adjustable reset time
•
32 detectors per zone or manual call points.
•
Zone input information can be assigned as alarm, evacuate, fault, reset, silent
•
Siren output can be activated in a zonal alarm, general alarm or fault conditions
•
Two processor and isolated hardware design
•
2 LED indicators for power and communication / alarm
•
Suitable for wall and rail mounting
Technicial Specifications
Operating Temperature Range
-10
C ~ 55
C (14
F ~ 131
F)
Humidity
95% RH (max)
Dimensions (mm)
110x76x32mm
Housing Material
White Color, ABS Plastic
Weight
140 gr
Loop
Poop Voltage
18V
–
32VDC
Average Current
150uA (@32V)
Maximum Alarm Current
1.5mA (@32V)
Communication Protocol
Flashlink
Power Input
Supply Voltage
22V
–
26VDC
Average Current
20mA (@24V) + Zone C Siren Current
Alarm Current
40mA (@24V) + Zone C Siren Current
Zone
Number of Detectors
32 detectors per zone or manual call points.
Default Alarm Current
20mA
Cable Resistance
40ohm (max)
Cable Length
1,5km 1,5m
m²
(max)
Cable Type
2 x 1,5mm² J
-
Y(St)Y…Lg (
Recommended)
Siren
Output Current
500mA (F1 Fuse)
End of Line Resistor
4K7 ohm, %5, 1/4W
Cable Type
2 x 1,5mm² J
-
Y(St)Y…Lg (
Recommended)
Indications
Red Led (It is constantly lit)
Indicates conventional alarm input
Red Led (Blinks for 4s)
Indicates that the siren output is active
Blue Led (Blinks for 20s)
Indicates module-to-loop communication
Blue Led (Blinks for 4s)
Indicates that the module has any error conditions (short circuit,
open circuit, power supply)
Greenl Led (It is constantly lit)
Indicates that the external power supply is normal condition
Note: When the blue led and the red led are lit at the same time, a purple color appears.
Mounting and Connection
You can use the "WALL MOUNTING TEMPLATE" on the right side of the mounting page with the marking
purpose to fix the product wall.
Accessory
The TFM-1190 is designed properly for rail mounting. To mount the rail, you must use the TFA-0190 DIN Rail
Mounting Kit. The appliance should be fixed by the two screw holes on the back of the product.
W
AL
L AS
SE
M
BL
Y T
EM
PL
AT
E
Warning:
The product only works with TFP-121x, TFP-122x and TFP-123x Analogue Addressable
Fire Alarm panels.