Error Messages

Error Messages & Troubleshooting

Applications using Multiple 480 and 481 Together

Multiple User Switches 480 and 481 can be used together 
when:

1) 

Applications require more than 3 User Buttons.

2) 

Applications require both input demands and output 
relay contacts.

3) 

User Switches with the same functionality are required 
at different locations.

Each tN4 bus cannot exceed 24 devices. Devices include 
thermostats, setpoint controls, mixing expansion modules, 
and user switches.

When using multiple User Switches at the same location, 
they can be installed adjacent to each other in the same 
switch box.

Applications requiring more than 3 User Buttons

When more than 3 User Buttons are required, two or more 
User Switches can be located next to each other in a double 
switch box. Each button can be programmed to either select 
a scene or provide a setpoint enable.

Application Example:

Applications that select more than three scenes or setpoint 
device enables will require two or more User Switches.

Symptom

Cause

Corrective Action

3 Buttons 
Flashing Red

User

Button

1

User

Button

2

User

Button

3

User Switch 
disconnected from 
tN4 bus.

• 

• 

Check tN4 and common 
wires for loose wire 
connections.

• 

• 

Ensure the tN4 controls have 
power.

• 

• 

Check R and C wires for 
correct polarity.

1 Button 
Flashing Red

User

Button

1

User

Button

2

User

Button

3

User

Button

1

User

Button

2

User

Button

3

User

Button

1

User

Button

2

User

Button

3

or

or

The User Button 
is configured for 
setpoint device 
enable operation 
and there is no 
response from the 
tN4 setpoint control.

• 

• 

Ensure the setpoint device 
has power and is connected 
to the tN4 bus.

• 

• 

Ensure the setpoint device 
enable number of the 
User Button and of the tN4 
setpoint control match.

Applications with both input demands and output 
relay contacts

Applications that require input demands and output contacts 
require a 480 and a 481. The 480 provides the input demands 
and the 481 provides the output contacts.

Application Example:

A third party telephone switch device allows a user to 
change the scene from 1 to 2 (Away) through the demand 
input on the 480. Should a critical or non-critical error 
occur on the tN4 system, a 481 can close an alert contact 
to allow a third party telephone switch to page a service 
technician.

User Switches with the same functionality at 
different locations

There may be applications where there are two or more 
User Switches installed in a building. Each of the User 
Switch User Buttons can be programmed with the same 
functionality. When an User Button is pressed, User Buttons 
with the same functionality will all light green at the same 
time.

Application Example:

A User Switch is installed in the garage and another User 
Switch is installed in the master bedroom.

Summary of Contents for tekmarNet4 User Switch 480

Page 1: ...s 3 programmable buttons that allow users to easily change the operating scene or allow users to enable disable tN4 setpoint devices on a tN4 system Multiple User Switches are required if more than 3 scenes or setpoint enable disables are desired The 480 has 3 demand inputs that allow for connection of a tN4 system to a third party automation system or telephone switch This allows users to remotel...

Page 2: ... 8 Warranty 8 Table of Contents User Interface The User Switch has a total of 5 buttons User Buttons 1 2 and 3 allow for users to select the operation of the tN4 system Buttons A and B allow the installer to program the operation of User Buttons 1 2 and 3 User Button 1 User Button 2 User Button 3 BUTTON A BUTTON B Factory Defaults User Button 1 Scene 1 Label Normal User Button 2 Scene 3 Label Unoc...

Page 3: ...cial users a simple way to allow staff to override the night setback setup schedule on the tN4 system Current Scene Press the Same Button New Scene Perm Scene 1 No Change Perm Scene 2 Away Selects Scene 1 Perm Scene 3 Unoccupied Selects Scene 1 Perm Scene 4 Selects Scene 1 Perm Scene 5 Selects Scene 1 Tmpy Scene 6 Occupied Selects previous perm scene Tmpy Scene 7 Selects previous perm scene Tmpy S...

Page 4: ...epeat 5 Times 5 5 Red Off Repeat 6 Times 6 3 hr Temporary Occupied 6 Red Off Repeat 7 Times 7 4 hr Temporary 7 Red Off Repeat 8 Times 8 8 hr Temporary 8 Red Off Repeat User Button 1 User Button 2 User Button 3 STEP 2 Press button A once using a blunt object to begin programming mode Each of the 3 User Buttons will begin to flash to indicate the current program setting Red flashes indicate the User...

Page 5: ...een Off Repeat STEP 5 Press button B to finalize the User Button setting and exit the programming mode Note To return to Step 2 without saving the setting press button A STEP 6 Repeat steps 2 through 5 to program each User Button User Button 1 User Button 2 User Button 3 PRESS BUTTON B STEP 8 Replace the trim bezel User Button 1 User Button 2 User Button 3 STEP 7 Included with the User Switch are ...

Page 6: ...efore the user switch responds to further demand inputs For a list of suggested third party devices that can connect to the user switch please contact your tekmar sales representative Application Examples A third party telephone switch has a normally open contact that connects to the User Switch demand 1 input This allows a user to place a telephone call to the telephone switch to change the tN4 s...

Page 7: ...r correct polarity 1 Button Flashing Red User Button 1 User Button 2 User Button 3 User Button 1 User Button 2 User Button 3 User Button 1 User Button 2 User Button 3 or or The User Button is configured for setpoint device enable operation and there is no response from the tN4 setpoint control Ensure the setpoint device has power and is connected to the tN4 bus Ensure the setpoint device enable nu...

Page 8: ...ifferent from or in excess of the tekmar Limited Warranty are the Purchaser s sole responsibility and obligation Purchaser shall indem nify and hold tekmar harmless from and against any and all claims liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers The pass through Limited Warranty does not appl...