Tekmar RTU 062 Data Brochure Download Page 2

© 2007 

  D 062 - 05/07 

2 of 4 

STEP THREE 

 WIRING THE RTU

Run 18 AWG twisted pair or similar wire between the RTU and the control. Insert the wires 
through the hole provided in the back of the RTU enclosure and connect them to the Com 
and the tekmar Net™ (tN1) terminals. Do not run the wires parallel to telephone or power 
lines as this may interfere with the operation of the RTU. If the RTU wires are located in an 
area with strong sources of electromagnetic noise, shielded cable should be used or the 
wires can be run in a grounded metal conduit.

NOTE:

 Do not apply power to the RTU. The RTU is powered by the control. The connection 

between the control and the RTU is polarity sensitive. The Com terminal of the RTU must 
be connected to the Com terminal of the control and the tekmar Net™ (tN1) terminal of the 
RTU must be connected to the appropriate tekmar Net™ (tN1) terminal of the control. If the 
wires are reversed, the display on the RTU will remain blank and the control will display a 
short circuit error for the tekmar Net™ (tN1) device.

STEP TWO 

 MOUNTING THE RTU

The RTU should be installed on an interior wall of the desired zone to be controlled. Do not 
mount the RTU in a location that may be affected by localized heat sources or cold drafts. 
It may be necessary to install a draft barrier behind the enclosure in order to prevent air 
from blowing through the wiring hole and affecting the RTU reading.

Mount the RTU directly to the wall using two #6-1” screws. The screws are inserted through 
the mounting holes and must be securely fastened to the wall. If possible, at least one of 
the screws should enter a wall stud or similar surface. If local code requires that the RTU 
be mounted to a 2” x 4” electrical box, order an Adapter Plate 007. This plate will mount to 
the electrical box and the RTU will then mount to the plate. Ensure that the electrical box 
does not provide cold air to the RTU.

To Control

#6 1” screws

Reviews: