- Data Brochure

Difference Setpoint Control 156

The Difference Setpoint Control 156 is designed to operate an on/off pump to transfer heat from a heat source to a storage 
tank. The control operates based on a setpoint temperature difference (ΔT). The relay turns on when the ΔT rises above 
the setpoint and turns off when the ΔT falls below the setpoint less the differential. The Source Minimum and Storage 
Maximum settings turn off the relay when heat transfer is no longer desirable. Potential applications include using solar 
collectors or a wood boiler as a heat source.

Additional functions include: 

24 V (ac) OR 24 V (dc) power supply
Monitor Minimum & Maximum temperatures for Source & Storage
Displays number of running hours of the relay
Displays ΔT• hours to perform energy calculation
CSA and UL certified for use in the USA and Canada

NEW Solar Sensor 085 immersion type sensor included!





Difference Setpoint
Control 156  

On / Off

 

Item

Dat

e Code

Power:  24 V (ac) ±10% 50/60 Hz 3 VA
 

24 V (dc) ±10% 0.03 A

Relay:  240 V (ac) 10 A 1/3 hp
 

tektra 906-12

Meets Class B:
Canadian ICES
FCC Part 15

ΔT

Source

Maximum

Minimum

Storage

ΔT • hours

Diff’l

1

2

3

4

C

R

5

Com

6

Src

7

Stor

No Power

Signal wiring must be

rated at least 300V

Made in Canada

Power

Relay

H30

10

B

Input

Universal Sensor

Included

Input

Solar Sensor

Included

Output

Primary

Pump

Input

24 V (ac or dc)

Power Supply

Summary of Contents for Difference Setpoint Control 156

Page 1: ...a heat source Additional functions include 24 V ac OR 24 V dc power supply Monitor Minimum Maximum temperatures for Source Storage Displays number of running hours of the relay Displays T hours to per...

Page 2: ...e 156 has three push buttons Item for selecting viewing and adjusting settings When programming the control record settings in the PRGM menu table which is found in the second half of this brochure It...

Page 3: ...that follows will explain the on and off points of the relay T Source Maximum Minimum Storage T hours Diff l Item Number Field Displays the current value of the selected item Item Field Displays the c...

Page 4: ...low the Minimum Source Setpoint the relay is turned off The relay remains off until the source temperature rises above the Minimum Source Setpoint plus the Minimum Source Differential The Source Minim...

Page 5: ...429 50 29 34 C 446 60 70 F 57 C 411 60 55 48 C 425 Table 1 K values at 120 F 49 C for different heat transfer solutions based on glycol K increases with temperature Improper installation and operation...

Page 6: ...and sensors Test the Sensors In order to test the sensors the actual temperature at each sensor location must be measured A good quality digital thermometer with a surface temperature probe is recomme...

Page 7: ...he control These terminals are to be used as a switch to either make or break the pump circuit When the 156 requires the pump to run it closes the contact between terminals 3 and 4 Sensors and Un powe...

Page 8: ...s Diff l 76 to 284 F 60 to 140 C STORAGE TEMPERATURE Current storage temperature as measured by the storage sensor HEAT is displayed if the relay is closed T Source Maximum Minimum Storage T hours Dif...

Page 9: ...down buttons for 1 second T Source Maximum Minimum Storage T hours Diff l 0 to 999 999 hr RELAY RUNNING HOURS Number of Relay running hours since this item was last cleared The control will display t...

Page 10: ...Default 40 F 4 C SOURCE MINIMUM SETPOINT If the Source temperature drops below this setpoint the relay is turned off T Source Maximum Minimum Storage T hours Diff l 2 to 45 F 1 to 25 C Default 10 F 6...

Page 11: ...f l EEPROM READ ERROR The control was unable to read a piece of information from its EEPROM This error can be caused by a noisy power source The control will load the factory defaults and stop operati...

Page 12: ...ether direct indirect special secondary incidental or consequential arising from ownership or use of the product or from defects in work manship or materials including any liability for fundamental br...

Reviews: