Tekmar D 270 Data Brochure Download Page 16

© 2010          D 270 - 08/10 

16 of 24 

 Test The Power Supply

Make sure exposed wires and bare terminals are not in contact with 
other wires or grounded surfaces. Turn on the power and measure 
the voltage between the 

Power L

 and 

Power N

 terminals (5 and 6) 

using an AC voltmeter, the reading should be between 103.5 and 
126.5

 

V

 

(ac).

Test the Powered Inputs

Boiler Demand

If a boiler demand is used, measure the voltage between the 

Boil Demand

 terminals (1 and 2). When the boiler demand device 

calls for heat, between 20 and 260

 

V

 

(ac) should be measured at the 

terminals. When the boiler demand device is off, less than 5

 

V

 

(ac) 

should be measured.

DHW Demand

If a DHW demand is used, measure the voltage between the 

DHW Dem

 and the 

Com Dem

 terminals (2 and 3). When the DHW 

demand device calls for heat, between 20 and 260

 

V

 

(ac) should be 

measured at the terminals. When the DHW demand device is off, 
less than 5

 

V

 

(ac) should be measured.

TEST THE OUTPUTS

Primary Pump (Prim P1)

If a primary pump is connected to the 

Prim P1

 terminal (4), make sure that power to the terminal block is off and install a jumper 

between the 

Power L

 and 

Prim P1

 terminals (5 and 4). When power is applied to the 

Power L

 and 

Power N

 terminals (5 and 6), 

the primary pump should start. If the pump does not turn on, check the wiring between the terminal block and pump and refer to 
any installation or troubleshooting information supplied with the pump. If the pump operates properly, disconnect the power and 
remove the jumper.

Boiler Pmp P2

If a boiler pump is connected to the 

Boiler Pmp P2

 terminals (9 and 10), 

make sure that power to the terminal block is off and install a jumper 
between the terminals. When power is applied to circuit, the boiler 
pump should start. If the pump does not turn on, check the wiring 
between the terminal block and pump and refer to any installation or 
troubleshooting information supplied with the pump. If the pump oper-
ates properly, disconnect the power and remove the jumper.

DHW Pump Or Valve (DHW Pmp / Vlv)

If a DHW pump or DHW valve is connected to the 

DHW  Pmp / Vlv

 

terminals (7 and 8), make sure the power to the pump or valve circuit 
is off and install a jumper between those terminals. When the DHW 
circuit is powered up, the DHW pump should turn on or the DHW valve 
should open completely. If the DHW pump or valve fails to operate, 
check the wiring between the terminals and the pump or valve and refer 
to any installation or troubleshooting information supplied with these 
devices. If the DHW pump or valve operates correctly, disconnect the 
power and remove the jumper.

6

Power

5

V

103.5 to 126.5 V (ac)

N

L

20 to 260 V (ac)

2

1

Boil

Dem

Com

Dem

20 to 260 V (ac)

3

2

Com

Dem

DHW

Dem

10

Boiler

9

Pmp P2

L

N

24 to 230 V (ac)

8

DHW

7

Pmp/Vlv

L

N

24 to 230 V (ac)

Summary of Contents for D 270

Page 1: ...Indr UnO Boil Com Sw Boiler Control 270 One Modulating Boiler DHW Boiler Pmp P2 DHW Pmp Vlv H2039A Menu Item Boiler Demand DHW Demand Modulation DHW Priority Override Test o not testing red testing r...

Page 2: ...sh buttons Menu Item for selecting and adjusting settings As you program your control record your settings in the ADJUST menu table which is found in the second half of this brochure Menu All of the i...

Page 3: ...gs Burner Displays when Relay 1 is turned on Warning Displays when an error exists or when a limit has been reached Pump Displays when the primary or boiler pump is operating Lock Unlock Displays when...

Page 4: ...m The supply water temperature is based on outdoor reset or a fixed temperature for DHW Outdoor Reset When a boiler demand signal from the heating system is present the control operates the boiler s t...

Page 5: ...calculates a boiler target temperature that is below the Boiler Minimum setting the boiler target temperature is adjusted to at least the Boiler Minimum setting During this condition if the boiler is...

Page 6: ...ut signal range of the 270 control The Minimum Modulation setting limits the control output range in order to match the boiler s input range To calculate the Minimum Modulation use the following formu...

Page 7: ...residential cast iron boilers or steel tube boilers The Med Mass setting provides a moderate response to the heating system Hi 3 The Hi setting is selected if the boiler that is used has a high therm...

Page 8: ...of time that the primary pump continues to run is adjustable using the Primary Pump Purge setting The primary pump continues to run until either the purging time has elapsed or the boiler supply temp...

Page 9: ...ight periods INDOOR SENSOR With the indoor sensor connected the control is able to sense the actual room temperature Indoor temperature feedback fine tunes the supply water temperature in the heating...

Page 10: ...on the WWSD pointer in the display When the control is in WWSD the Boiler Demand pointer is displayed if there is a boiler demand However the control does not operate the heating system to satisfy thi...

Page 11: ...contact is opened until the heating system has recovered before returning to DHW operation This mode can be used if a DHW tank is piped in direct return and a DHW valve is installed DHW MODE 4 Extern...

Page 12: ...heat from the boiler into the DHW tank The control continues this purge for a maximum of four minutes or until the boiler supply water temperature drops 20 F 11 C below the boiler target temperature d...

Page 13: ...or Sensor 070 One Universal Sensor 082 Data Brochures D 270 D 070 D 001 Application Brochure A 270 Note Carefully read the details of the Sequence of Operation to ensure that you have chosen the prope...

Page 14: ...power supply must be used to power both the DHW Demand and the Boiler Demand circuits since they both share the Com Dem terminal Output Connections Primary Pump Contact Prim P1 The Prim P1 output term...

Page 15: ...When these two terminals are shorted together the control registers an unoccupied UNOCC signal Connection to Operate Modulating Boiler 11 12 Mod V dc V dc STEP FIVE TESTING THE WIRING General Each ter...

Page 16: ...e wiring between the terminal block and pump and refer to any installation or troubleshooting information supplied with the pump If the pump operates properly disconnect the power and remove the jumpe...

Page 17: ...oth with water and wring out prior to wiping control Do not use solvents or cleaning solutions DIP Switch Settings GENERAL The DIP switch settings on the control are very important and should be set t...

Page 18: ...measured by the boiler supply sensor 22 to 266 F 30 to 130 C Boiler Target Boiler target temperature is the temperature the control is currently trying to maintain at the boiler supply sensor of the...

Page 19: ...F 82 C B1 Boiler Minimum The minimum allowed boiler target temperature Check the boiler manufacturer s manual for a recommended setting OFF 80 to 180 F OFF 27 to 82 C Default 140 F 60 C B1 Boiler Maxi...

Page 20: ...C Default 180 F 82 C DHW Exchange Unoccupied Selects whether or not a DHW demand will be responded to during the UnOccupied period OFF On Default OFF WWSD Occupied The system s warm weather shut down...

Page 21: ...essed again to advance to the next step This can also be used to rapidly advance through the test sequence To reach the desired step repeatedly press and release the Test button until the appropriate...

Page 22: ...ystem start up in order to purge air from the piping To enable the Max Heat feature use the following procedure 1 Press and hold the Test button for more than 3 seconds At this point the control flash...

Page 23: ...to read the boiler supply sensor due to a short circuit The control will not operate the boiler until the sensor is repaired Locate and repair the problem as described in the Data Brochure D 070 To cl...

Page 24: ...AND FITNESS FOR A PARTICULAR PURPOSE DURA BILITY OR DESCRIPTION OF THE PRODUCT ITS NON INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS AND ITS COMPLIANCE WITH OR NON VIOLATION OF ANY APPLICABLE EN...

Reviews: