STEP FOUR
ELECTRICAL CONNECTIONS TO THE CONTROL
General
The installer should test to confirm that no voltage is present at any of the wires. Push the control into the base and slide it down
until it snaps firmly into place.
Powered Input Connections
115 V (ac) Power
Connect the 115 V (ac) power supply to the
Power L
and
Power N
terminals (5 and 6).
This connection provides power to the microprocessor and display of the control.
As well, this connection provides power to the
Prim P1
terminal (4) from the
Power L
terminal (5).
Boiler Demand
To generate a
Boiler Demand
, a voltage between 24 V (ac) and 230 V (ac) must be
applied across the
Boil Dem
and
Com Dem
terminals (1 and 2).
DHW Demand
To generate a
DHW Demand
, a voltage between 24 V (ac) and 230 V (ac) must be
applied across the
Com Dem
and
DHW Dem
terminals (2 and 3).
Caution:
The same power supply must be used to power both the DHW Demand and
the Boiler Demand circuits since they both share the
Com Dem
terminal.
Output Connections
Primary Pump Contact (Prim P1)
The
Prim P1
output terminal (4) is a powered output. When the relay in the control
closes, 115 V (ac) is provided to the
Prim P1
terminal (4) from the
Power L
terminal (5).
To operate the primary pump, connect one side of the primary pump circuit to terminal 4
and the second side of the pump circuit to the neutral (
Power
N
) side of the 115 V (ac)
power supply.
DHW Pmp / Vlv Contact
The
DHW Pmp / Vlv
terminals (7 and 8) are an isolated output. There is no power
available on these terminals from the control. These terminals are to be used as a
switch to either make or break power to the DHW pump or the DHW valve. Since this
is an isolated contact, it may switch a voltage between 24 V (ac) and 230 V (ac).
Boiler Pmp P2 Contact
The
Boiler Pmp P2
terminals (9 and 10) are isolated output in the control. There is no
power available on these terminals from the control. These terminals are to be used
as a switch to either make or break power to a boiler pump. Since this is an isolated
contact, it may switch a voltage between 24
V
(ac) and 230
V
(ac).
10
9
24 to 230 V (ac)
L
N
Boiler
Pmp P2