Conduit Installa
ƟŽŶ
Improper sealing of connec
Ɵ
ons may damage the transmi
Ʃ
er due to excess moisture
accumula
Ɵ
on. Mount the transmi
Ʃ
er with electrical housing posi
Ɵ
oned downward so
that the excess of moisture is condensed and drained out from the casing. Secondly,
install wiring with a drip loop and ensure the bo
Ʃ
om of the drip loop is mounted lower
than the conduit connec
ƟŽ
ns or the transmi
Ʃ
er housing to avoid moisture accumula
Ɵ
on
in the housing.
NOTE
Conduit thread must be engaged with a minimum of 5 thread connec
Ɵ
ons
3.3 Mou
ŶƟ
ng Requirements
Impulse piping c
ŽŶĮŐ
ura
ƟŽŶ
and transmi
Ʃ
er posi
ƟŽŶ
depends on speci
Į
c measurement
condi
Ɵ
ons. Follow the procedure below while installing transmi
Ʃ
er for liquid, gases or
steam processes.
Liquid Measurement
x
Place the taps to the side of the line/pipe to prevent residue deposits on the
transmi
Ʃ
er process isolators
x
Mount the transmi
Ʃ
er beside or below the taps so gases can vent into the process
line
x
Mount drain/vent the valve upward to allow gases to vent