teel 4RK45A Operating Instructions & Parts Manual Download Page 4

4

Teel Operating Instructions and Parts Manual

4RK45A, 4RK46A, 4RK47A, 4RK48A, 4RK49A, 4RK62A and 4RK63A

Teel Submersible Effluent and
Sewage/Solids Handling Pumps

®

E

N
G

L

I

S

H

Installation (Continued)

THREE PHASE MOTORS: 230V TO
460V CONVERSION

1. Remove the hex head screws (Ref.

No. 13, Figure 7, Page 8) holding the
capacitor cover (Ref. No. 2). Remove
the capacitor cover and O-Ring.
Disconnect the motor lead wires
from the power cord set (the wires
and connector are color coded for
reassembly). Be careful not to spill
any motor oil.

2. Reconnect the power cord to the

motor leads as shown in Table III,
Page 5, under “Stator Leads: 12
Wire 460V”. 

3. Reassemble the capacitor cover and

O-Ring and tighten the screws. Be
sure you do not damage the O-Ring.

4. Momentarily start the pump to

check rotation. Look at the impeller
through the intake opening of the
volute (the pump suction), Ref. No.
22. The rotation should be CCW
(

).

5. If the rotation is 

not 

CCW, remove

the cover again and interchange any
two incoming power leads to the
motor. Rotation will now be CCW.

Operation

NOTE:

Do not allow pump to run in a

dry sump. It will void the warranty and
may damage the pump.

An automatic overload protector in
the motor will protect motor from
burning out due to overheating/
overloading. When motor cools down,
overload protector will automatically
reset and start motor.

Maintenance

Risk of electrical
shock. Can burn or

kill. Do not lift pump by power cord.

1. Attempting to lift or support pump

by power cord can damage cord and
cord connections.

2. Cord may pull apart, exposing bare

wires with possibility of fire or
electrical shock.

3. Lifting or supporting pump by

power cord will void warranty.

4. Use lifting ring on top of pump for

all lifting/lowering of pump.
Disconnect power to pump before
doing any work on pump or
attempting to remove pump from
sump.

IMPELLER, SEAL, AND CAPACITOR
REPLACEMENT 

Refer to Figure 7, Page 8 –
Replacement Parts Illustration for
Models 4RK45AA, 4RK46AA, 4RK47AA,
4RK48AA,and 4RK49AA. Refer to
Figure 8, Page 9 – Replacement Parts
Illustration for Models 4RK62AA and
4RK63AA.

Hazardous voltage.

Can shock, burn, or

cause death. Before servicing pump,
disconnect electrical power to pump and
control switch.

Risk of electrical

shock. Can burn or

kill. Do not lift pump by power cord (See
Figure 1).

After removing basin cover and
necessary discharge piping, lift pump
out of basin by the handling ring. 

Place pump in an area where it can be
cleaned thoroughly. Remove all scale
and deposits on pump.

Submerge pump in disinfectant
(chlorox or chlorine) for at least one
hour before disassembling pump.

The pump motor housing contains a
special lubricating oil. Keep oil clean
and free of water at all times.

NOTE: 

Whenever motor cover is being

removed for service, remove oil and
replace with new oil at reassembly. Use
only oil listed in parts list (Part No.
U197-8A). When filling with new oil,
DO NOT overfill. To allow room for
expansion, oil level with cold motor
should be about 1/4" (6 mm) above
top of motor assembly.

TABLE II – Tether Dimensions

Tether length

3.5

6

10

13

Pumping differential  –

Pump down

7

10

16

21

Dimension

Measurement in Inches

This chart is only a guide. The pumping ranges are based on testing in non-
turbulent conditions. The range may vary due to water temperature and cord
shape.

NOTE: 

Pumping range increases as the tether length increases.

Risk of flooding. Inspect the tether strap to be sure that it is
tightly fastened and will not allow the float cord to slip in either

direction.

Figure 1

Summary of Contents for 4RK45A

Page 1: ...ameter Length Weight 4RK45A 1 230 1 8 5 15 130 F Sewage solids handling 3 4RK46A 1 230 460 3 8 5 4 1 15 15 130 Sewage solids handling 3 4RK47A 11 2 230 1 12 0 15 130 Sewage solids handling 3 4RK48A 11...

Page 2: ...to install pump with a magnetic motor starter wired to interrupt power to all three incoming phases Three phase pumps are intended for permanent connection only Provide strain relief at control box fo...

Page 3: ...fications on Page 1 OVERLOADS SINGLE PHASE In single phase units an automatic overload protector in the motor will protect motor from burning out due to overheating overloading When motor cools down p...

Page 4: ...d will void warranty 4 Use lifting ring on top of pump for all lifting lowering of pump Disconnect power to pump before doing any work on pump or attempting to remove pump from sump IMPELLER SEAL AND...

Page 5: ...motor cover from seal plate Ref No 10 Remove through bolts Ref No 15 from motor assembly Ref No 8 Remove motor and shaft from seal plate 10 Working from back of seal plate tap primary seal head out of...

Page 6: ...ress or imply a warranty that the products are MERCHANTABLE or FIT FOR A PARTICULAR PURPOSE or that the products will necessarily conform to the illustrations or descriptions Except as provided below...

Page 7: ...el is not high enough 2 Check that fluid level is high enough to activate to activate switch or controller switch or controller 3 Plugged vent hole in discharge pipe 3 Check to be sure that the 3 16 v...

Page 8: ...62SS U30 62SS U30 62SS U30 62SS 4 14 1 4 20 x 1 Capscrew U30 475SS U30 475SS U30 475SS U30 475SS U30 475SS 4 15 Motor through bolts U30 941 U30 941 U30 941 U30 941 U30 941 4 16 3 16 x 3 4 Impeller ke...

Page 9: ...U30 475SS U30 475SS 4 15 Motor through bolts U30 941 U30 941 4 16 Shaft seal U9 394SS U9 394SS 1 17 Retaining washer PW43 5SS PW43 5SS 1 18 Retaining ring U9 353SS U9 353SS 1 19 Lip seal U9 417 U9 417...

Page 10: ...Notes Teel Operating Instructions and Parts Manual 4RK45A 4RK46A 4RK47A 4RK48A 4RK49A 4RK62A and 4RK63A E N G L I S H Manufactured for Dayton Electric Mfg Co Niles Illinois 60714 U S A...

Reviews: