Installation (Continued)

HORIZONTAL PIPING FROM WELL TO
PUMP

1. Pump performance will be decreased

if less than 1

1

2

” pipe is used as suction

pipe on 4RJ41, 4RJ42 and 4RJ44, and
if less than 2” pipe is used as suction
pipe on 4RJ40 and 4RJ43.

2. To aid priming on well point

installations, install line check valve.
Be sure check valve flow arrow points
toward pump.

DISCHARGE PIPE SIZES

Discharge pipe size should be increased
to reduce pressure losses caused by
friction on long pipe runs.

• Up to 100' (30.5 m) run: Same size as

pump discharge port.

• 100' - 300' (30.5 - 91.4 m) run:

Increase one pipe size.

• 300' - 600' (91.4 - 182.9 m) run:

Increase two pipe sizes.

LAWN SPRINKLING APPLICATION

This pump is designed for lawn
sprinkling. Delivers plenty of water at
full sprinkler pressure. Pumps from
pond, cistern, or well points.

Pump discharge can be divided to
supply 4 or more sprinkler systems.

Do not use in booster pump
applications.

PUMP/PIPING INSTALLATION

If turning pump on and off by pressure,
a pressure switch and tank are required.
For proper installation and operation
instructions, call Customer Service.

Use rigid pipe. Do not use hose or
plastic tubing. See “Well Pipe
Installation” for more information.

NOTE: 

Use only Teflon tape or Teflon

based joint compounds for making all
threaded connections to the pump
itself. Make sure that all pipe joints in
the suction pipe are air tight as well as
water tight. If the suction pipe can suck
air, the pump will not be able to pull
water from the well.

1. Bolt pump to solid, level foundation

(See Figure 4). 

2. Support all piping connected to

pump (See Figure 5).

3. Wrap 1

1

2

to 2 layers of Teflon tape

clockwise (as you face end of pipe)
on all male threads being attached to
pump. 

4. Tighten joints hand tight plus 1

1

2

turns. 

Do not overtighten.

5. Replacing the priming plug with a

pressure gauge (purchased
separately) will aid in sizing zones,
troubleshooting, and following the
pump performance chart.

NOTE: 

Install pump as close to well

head as possible. Long piping runs and
many fittings create friction and reduce
flow.

NOTE: 

For long horizontal pipe runs,

install a priming tee between check
valve and well head (See Figure 2). For
driven point installations, install check
valve. Be sure that check valve flow
arrow points 

toward 

pump.

4

Teel Operating Instructions and Parts Manual

4RJ40, 4RJ41, 4RJ42, 4RJ43 and 4RJ44

Teel Professional Self-Priming
Centrifugal Pump

®

E

N
G

L

I

S

H

AWG WIRE SIZE

3/4

115/230

11.6/5.8

20/15

14/14 

10/14 

8/14 

6/14 

6/12 

1

115/230

14.2/7.1

20/15

12/14 

8/14 

6/14

6/12 

4/10 

1

1

2

115/230

18.0/9.0

25/15

10/14 

8/14 

6/12

6/12

4/10

2

230

10.4

15

14 

14 

12

10

10 

2

1

2

230

11.7

15

14 

14 

12

10

10

WIRING CHART – RECOMMENDED WIRE AND FUSE SIZES

Max. Load

Branch Fuse*

Distance in Feet from Motor to Supply

Motor HP

Volts

Amp

Rating Amps

0 - 100 

101 - 200 

201 - 300 

301 - 400 

401 - 500 

(*) Fusetrons are recommended instead of fuses on all motor circuits.

L17

6-35P

Figure 4 – Bolt Pump to Foundation

L17

6-35P

Figure 5 – Support All Piping Connected
to Pump

Summary of Contents for 4RJ40

Page 1: ...manual and on pump 4RJ40 Fiberglass Reinforced Thermoplastic Engineered Polymer Viton Polypropylene 4RJ41 Fiberglass Reinforced Thermoplastic Engineered Polymer Viton Polypropylene 4RJ42 Fiberglass R...

Page 2: ...d tools and equipment Keep visitors at a safe distance from the work areas Make workshop childproof with padlocks master switches and by removing starter keys Know the pump application limitations and...

Page 3: ...s WELL PIPE INSTALLATION NOTE Use installation method below which matches your well type CASED WELL DUG WELL INSTALLATION 1 Inspect foot valve to be sure it works freely Inspect strainer to be sure it...

Page 4: ...ight If the suction pipe can suck air the pump will not be able to pull water from the well 1 Bolt pump to solid level foundation See Figure 4 2 Support all piping connected to pump See Figure 5 3 Wra...

Page 5: ...expected power application 4 Ground the pump permanently using a wire of the same size as that specified in wiring chart Page 4 Make ground connection to green grounding terminal in motor junction box...

Page 6: ...ll and try again NEVER run pump against closed discharge To do so can boil water inside pump causing hazardous pressure in unit risk of explosion and possibly scalding persons handling pump See Figure...

Page 7: ...or Remove rotating half of seal by placing two screwdrivers under back half of pump body and carefully prying up See Figure 12 Back half of pump body will slide off shaft bringing seal with it NOTE Be...

Page 8: ...automatically locate seal in correct position 10 Remount diffuser on pump body half with five screws 11 Reinstall motor canopy and tighten three capscrews to hold it INSTALLING HEAT SINK 2 AND 21 2 HP...

Page 9: ...ear ring C1 258PCASS C1 258PCASS C1 258PCASS 1 9 8 32 x 1 Screw stainless steel 3 10 Clamp C19 54SS C19 54SS C19 54SS 1 11 Pump body C176 66P C176 66P C176 66P 1 12 1 4 NPT Drain plug WC78 40T WC78 40...

Page 10: ...SA 1 9 8 32 x 1 Screw stainless steel 2 10 Clamp C19 37A C19 37A 1 11 Pump body C176 62P C176 62P 1 12 Priming plug WC78 39T WC78 39T 1 13 1 4 NPT Drain plug WC78 40T WC78 40T 1 14 Diffuser O Ring U9...

Page 11: ...foot valve or check valve 4 Pipe size too small 4 Re pipe using size of suction and discharge ports on pump Pump has lost prime through In installation already in use 5 Air leaks 5 Check all connecti...