General Safety Information

When built-in
overheating

protection is not provided, use with an
approved overload equipped motor
control that matches motor input in full
load amps. Select or adjust overload
elements in accordance with control
instructions.

When built-in overheating protection is
provided, use with an approved motor
control that matches motor input in full
load amperes.

Hazardous
pressure.

Submersible pumps can develop very high
pressure in some situations. To prevent
tank blowup, install a pressure relief
valve able to pass full pump flow at 75
PSI. Install relief valve between pump and
tank.

Do not allow pump,
pressure tank,

piping, or any other system component
containing water to freeze. Freezing may
damage system, leading to injury or
flooding. Allowing pump or system to
freeze will void warranty.

1. Be sure all plumbing and wiring

conform to national and local codes
and ordinances.

2. Since most submersible pump

problems are electrical, all electrical
work must be done properly.

Therefore, have all electrical
hookup work or electrical
service done by a qualified
electrician or serviceman only!

3. The power supply for a submersible

pump should be a separate circuit,
independent of all other circuits. Be
sure it is equipped with a fuse and
disconnect box of ample capacity.

4. On rural installations it is better to

have the power supply be free of
any buildings, preferably on a direct
line from the transformer, so that in
case of fire the wires will be
protected from burning off and the
water supply will not be cut off.

5. Before working on motor, its

connected load or control box and
wiring, disconnect electrical power.
If disconnect switch is out of sight of
work location, lock switch in the
open position and tag it to prevent
unexpected application of power.

6. Shut off power when voltage drops

below 105 volts on 115 volt
installations and 210 volts on 230
volt installations to prevent motor
damage.

7. Be sure to provide adequate

ventilation for pressure switch and

control box to prevent moisture
damage to components.

8. Periodically check well seal at top of

well to prevent surface water
contamination.

9. Have a competent serviceman check

the installation at three year
intervals for preventive maintenance
on electrical controls.

10. PROTECT power cable from

scratches, cuts, or abrasions from
sharp objects or scraping on well
casing when lowering pump into
well.

11. Do not kink or cut power cable. Do

not allow power cable to come into
contact with oil, grease, hot
surfaces, or chemicals.

12.

To reduce risk of electrical shock

,

installation must comply with most
recent National Electrical Code (NEC)
Article 250 (Grounding).

Motor is supplied with a green
ground wire. Connect green motor
ground wire to a grounded metal
raceway system or building ground
system. Bond together and ground
all metal components in installation
(well casing, metal well pipe, motor,
etc.) to building ground system.

Models 4P847A thru 4P851A, 4P852 thru 4P865, 4RH01 thru 4RH06,
4RG76 thru 4RG84, 4RG94 thru 4RG97 and 4RG99

3

Teel Operating Instructions and Parts Manual

®

E

N
G

L

I

S

H

Performance Chart

4P863

20

30.2

28.8

27.0

25.1

23.3

20.8

17.9

12.5

4.5

4P839

4P846

30

28.4

26.7

24.8

22.9

20.9

18.0

13.0

5.0

4RK67

4RG94

40

26.4

24.7

22.7

20.7

18.4

14.0

5.9

4RG96

50

24.2

22.4

20.1

17.9

14.1

6.1

60

21.9

19.9

17.2

13.0

6.7

4P865

20

31.2

30.2

29.0

27.6

26.2

24.5

22.7

20.6

18.5

10.1

4P839

4RG95

30

30.0

28.8

27.4

26.0

24.7

22.8

20.9

18.7

15.3

3.0

4RK67

4RG97

40

28.6

27.2

25.8

24.3

22.9

21.0

18.8

15.4

11.2

50

27.0

25.7

24.1

22.7

21.1

18.9

15.5

11.4

5.0

60

25.2

23.9

22.3

20.9

19.1

16.1

9.5

5.5

20 GPM Series Pumps For High Capacity Wells

Model

Tank

Gallons Per Minute at Vertical Depth To Water (Not Pump Setting Depth)

Suggested

No.

PSI

20’

40’

60’

80’

100’

125’

150’

200’

250’

300’

350’

400’

500’

Tank**

(**) Suggested tanks are sized to provide drawdown sufficient to allow approximately 2 minute cycles at 80 ft. 

depth to water. For shallower wells, use next size larger tank.

Summary of Contents for 4P847A

Page 1: ...94 thru 4RG97 and 4RG99 are thermoplastic discharge Pumps 4P847A thru 4P851A and 4P852 thru 4P856 are cast iron discharge E N G L I S H Printed in U S A 09319 0798 116 E3 4P847A 1 3 10 3 4P840 5 115 6...

Page 2: ...RK69 4P854 40 9 5 7 5 4 3 50 7 2 3 8 60 3 7 4P855 20 15 6 14 8 14 0 13 0 11 8 10 2 8 2 2 1 4P837 4P856 30 14 6 13 7 12 8 11 6 10 3 8 3 6 0 4RK69 4P857 40 13 6 12 6 11 5 10 1 8 6 6 1 2 8 4P858 50 12 5...

Page 3: ...on 230 volt installations to prevent motor damage 7 Be sure to provide adequate ventilation for pressure switch and control box to prevent moisture damage to components 8 Periodically check well seal...

Page 4: ...its are supplied with extra label for above ground pump identification Place label in conspicuous location on control box etc for future reference 2 Check electrical supply for correct fusing wire siz...

Page 5: ...time selector switch is changed 2 Clip one ohmmeter lead to bare cable end 3 Clip the other lead to edge of steel tank in which pump and cable are submerged If pump is already in the well clip lead t...

Page 6: ...2 If replacing a jet pump expect to set the submersible deeper in the well because the submersible will pump more water than the jet pump Be sure the new submersible is set at least ten feet above the...

Page 7: ...astic pipe adapter in the pump discharge tapping using pipe joint compound or teflon tape Models 4P847A thru 4P851A 4P852 thru 4P865 4RH01 thru 4RH06 4RG76 thru 4RG84 4RG94 thru 4RG97 and 4RG99 7 Teel...

Page 8: ...he pipe f If you have not already done so splice the electrical cable to the motor wire leads according to the directions under Sections 5 6 and 7 in Preinstallation g Unroll electrical cable alongsid...

Page 9: ...the pipe to eliminate rubbing against well casing Leave four to five feet of slack at the upper end to allow for plastic pipe stretch 5 Tie safety rope to top of pump in holes provided Tape end of ro...

Page 10: ...Use ONLY submersible cable to pump 7 Two wire pump hookup Wire the fused electrical disconnect box to water system pressure switch and from pressure switch to motor See Figures 15 and 16A Power cable...

Page 11: ...230 1 3 6 0 7 4 26 1 32 32 1 39 4 4 6 4 6 0 15 5 4P853 4P849A 4RG99 230 1 2 4 2 5 2 16 7 20 5 20 9 25 7 6 0 6 0 0 15 7 4P856 4RG76 4P851A 4RH01 230 3 4 3 0 3 6 11 0 13 4 14 0 17 0 8 0 8 0 0 20 9 4P85...

Page 12: ...itively identified proceed as follows 1 Disconnect all three drop cables from the control box For temporary identification tie a numbered tag to each cable 1 2 3 2 Using an ohmmeter check the resistan...

Page 13: ...l rights which vary from jurisdiction to jurisdiction LIMITATION OF LIABILITY To the extent allowable under applicable law Dayton s liability for consequential and incidental damages is expressly disc...

Page 14: ...L10P4DS WG 4P860 1D125 L10P4DS WG 4P861 1D133 4P845 L10P4ES WG 4P862 1D134 4P846 L10P4FS WG 4P863 1D133 4P845 L20P4ES WG 4P864 1D126 L20P4ES WG 4P865 1D134 4P846 L20P4FS WG 4RG99 1D131 4P843 L5P4CJL W...

Page 15: ...one minute intervals no water 2 Gas or air in well water 2 Connect hose to service valve Run water thru hose submerged in water in clear jar Observe for air bubbles from hose outlet If tank is standar...

Page 16: ...t circuit breakers may trip or fuses blow Ventilate or shade box Move away from heat source 5 If problem has not been found check motor and control box Use test procedures that follow Ground Insulatio...