6.  Program 

 

Function 

Display 

Possible actions 

Comments 

Access / Exit 

 

Push 

Pro

 for 3 seconds 

 

All settings and calibration 
will be stored in non volatile 
memory only when exiting 
the program by pushing 

Pro

 for 3 seconds 

Do not power off the unit 
before doing this or all 
values will be lost. 

Language 
selection 

 

l anguage 

ENGLISH 

 

 

 

 

 

to modify value 

 

 

Pro

 to validate and go to next screen 

 

 
Select your language 

Autofilling 
option 

 

Aut of il l  

yes 

 

 

 

 

 

to select YES or NO 

 

 

Pro

 to validate and go to next screen 

 

 
If set to NO, the autofilling 
program will be disabled. 

Empty Tank 
calibration 

 

Ad empt y 

10 adc 

 

 

 

 

 

to modify value 

 

CLR to calibrate automatically, the new 

measured value is displayed. 

 

Pro

 to validate and go to next screen 

 

 
This is the sensor value 
when tank is empty  
( display 0 litre) 
 
 

Minimum tank 
content 
 

 

Min vol  

20 l t  

 

 

 

 

 

to modify value 

 

Pro

 to validate and go to next screen 

 

 
This is the minimum tank 
content that will be used for 
the tank shape calibration. 
 
 

Minimum tank 
calibration 

 

Ad mini 

76 adc 

 

 

 

 

 

to modify value 

 

CLR to calibrate automatically, the new 

measured value is displayed. 

 

 

Pro

 to validate and go to next screen 

 

 
This is the sensor value 
when tank is at minimum  
(see previous step) 
 
 

Maximum tank 
content 
 

 

Max vol  

3200 l t  

 

 

 

 

 

to modify value 

 

Pro

 to validate and go to next screen 

 

 
This is the maximum tank 
content. Tank content 
display and filling will be 
limited to this value.  
 