020-032-UK
25/07/2012
Page 5 of 6
6. Program
Function
Display
Possible actions
Comments
Access / Exit
Push
Pro
for 3 seconds
All settings and calibration
will be stored in non volatile
memory only when exiting
the program by pushing
Pro
for 3 seconds
Do not power off the unit
before doing this or all
values will be lost.
Language
selection
l anguage
ENGLISH
to modify value
Pro
to validate and go to next screen
Select your language
Autofilling
option
Aut of il l
yes
to select YES or NO
Pro
to validate and go to next screen
If set to NO, the autofilling
program will be disabled.
Empty Tank
calibration
Ad empt y
10 adc
to modify value
CLR to calibrate automatically, the new
measured value is displayed.
Pro
to validate and go to next screen
This is the sensor value
when tank is empty
( display 0 litre)
Minimum tank
content
Min vol
20 l t
to modify value
Pro
to validate and go to next screen
This is the minimum tank
content that will be used for
the tank shape calibration.
Minimum tank
calibration
Ad mini
76 adc
to modify value
CLR to calibrate automatically, the new
measured value is displayed.
Pro
to validate and go to next screen
This is the sensor value
when tank is at minimum
(see previous step)
Maximum tank
content
Max vol
3200 l t
to modify value
Pro
to validate and go to next screen
This is the maximum tank
content. Tank content
display and filling will be
limited to this value.