![Tecumseh Argus Installation Instructions Manual Download Page 25](http://html.mh-extra.com/html/tecumseh/argus/argus_installation-instructions-manual_1073101025.webp)
23
Remote Condensing Unit Installation Instructions
©2019 Tecumseh Compressor Company LLC. All rights reserved.
TPC Part #71511 | Rev A 05/13/2019
www.tecumseh.com
TABLE 4 – Recommended Remote Condenser Line Sizes
Net Evaporator
Capacity
Total Equiv.
Length
R-407A/C/F, R-448A & R-449/A
R-507 & R-404A
Discharge Line O.D.
Liquid Line Cond.
To Receiver O.D.
Discharge Line O.D.
Liquid Line Cond.
To Receiver O.D.
3,000
50
3/8
3/8
3/8
3/8
100
3/8
3/8
3/8
3/8
6,000
50
3/8
3/8
1/2
3/8
100
1/2
3/8
1/2
3/8
9,000
50
1/2
3/8
1/2
3/8
100
1/2
3/8
1/2
3/8
12,000
50
1/2
3/8
1/2
3/8
100
5/8
3/8
5/8
1/2
18,000
50
5/8
3/8
5/8
1/2
100
5/8
3/8
7/8
1/2
24,000
50
5/8
0
5/8
1/2
100
7/8
1/2
7/8
5/8
36,000
50
7/8
1/2
7/8
5/8
100
7/8
5/8
7/8
7/8
48,000
50
7/8
5/8
7/8
5/8
100
7/8
7/8
1-1/8
7/8
60,000
50
7/8
5/8
7/8
7/8
100
1-1/8
7/8
1-1/8
7/8
72,000
50
7/8
7/8
1-1/8
7/8
100
1-1/8
7/8
1-1/8
1-1/8
90,000
50
1-1/8
7/8
1-1/8
7/8
100
1-1/8
7/8
1-1/8
1-1/8
120,000
50
1-1/8
7/8
1-1/8
1-1/8
100
1-3/8
1-1/8
1-3/8
1-3/8
Summary of Contents for Argus
Page 1: ...Remote Condensing Unit Installation Instructions ...
Page 35: ...NOTES ...