nature of work being carried out. Work in confined spaces shall be avoided. The area 
around the workspace shall be sectioned off. Ensure that the conditions within the 
area have been made safe by control of flammable material.
1.4 Checking for presence of refrigerant

The  area  shall  be  checked  with  an  appropriate  refrigerant  detector  prior  to 
and during work, to ensure the technician is aware of potentially flammable 
atmospheres. Ensure that the leak detection equipment being used is suitable for use 
with flammable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.
1.5 Presence of fire extinguisher

lf any hotwork is to be conducted on the refrigeration equipment or any associated 
parts, appropriate fire extinguishing equipment shall be available to hand. Have a 
dry powder or CO2 fire extinguisher adjacent to the charging area.
1.6 No ignition sources

No person carrying out work in relation to a refrigeration system which involves 
exposing any pipe work that contains or has contained flammable refrigerant shall 
use any sources of ignition in such a manner that it may lead to the risk of fire or 
explosion. All possible ignition sources, including cigarette smoking, should be kept 
sufficiently far away from the site of installation, repairing, removing and disposal, 
during which flammable refrigerant can possibly be released to thesurrounding space. 
Prior to worktaking place, the area around the equipment is to be surveyed to make 
sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be 
displayed. 
1.7 Ventilated area

Ensure that the area is in the open or that it is adequately ventilated before breaking 
into the system or conducting any hot work. A degree of ventilation shall continue 
during the period that the work is carried out. The ventilation should safely disperse 
any released refrigerant and preferably expel it extemally into the atmosphere. 
1.8 Checks to the refrigeration equipment

Where electrical components are being changed, they shall be fit for the purpose 
and to the correct specification. At all times the manufacturer’s maintenance and 
service guidelines shall be followed. lf in doubt consult the manufacturer’s technical 
department for assistance. The following checks shall be applied to installations using 
flammable refrigerants: - the charge size is in accordance with the room size within 
which the refrigerant containing parts are installed;
•   the ventilation machinery and outlets are operating adequately and are not 

obstructed;

•   if an indirect refrigerating circuit is being used, the secondary circuit shall be 

checked for the presence of refrigerant;

•   marking to the equipment continues to be visible and legible. Markings and signs 

that are illegible shall be corrected;

•   refrigeration pipe or components are installed in a position where they are 

unlikely to be exposed to any substance which may corrode refrigerant containing 
components, unless the components are constructed of materials which are 
inherently resistant to being corroded or are suitably protected against being so 
corroded.

1. 9 Checks to electrical devices

Repair and maintenance to electrical components shall include initial safety checks 
and component inspection procedures. lf a fault exists that could compromise safety, 
then no electrical supply shall be connected to the circuit until it is satisfactorily dealt 
with. lf the fault cannot be corrected immediately but it is necessary to continue 
operation, an adequate temporary solution shall be used. This shall be reported 
to the owner of the equipment so all parties are advised. lnitial safety checks shall 
include:
•   that capacitors are discharged: this shall be done in a safe manner to avoid 

possibility of sparking;

•   that there no live electrical components and wiring are exposed while charging, 

recovering or purging the system;

•   that there is continuity of earth bonding.

2   REPAIRS TO SEALED COMPONENTS

2.1 During repairs to sealed components, all electrical supplies shall be disconnected 
from the equipment being worked upon prior to any removal of sealed covers, etc. lf 
it is absolutely necessary to have an electrical supply to equipment during servicing, 
then a permanently operating form of leak detection shall be located at the most 
critical point to warn of a potentially hazardous situation.

Summary of Contents for CL 1630

Page 1: ...2 3 4 1 GEBRAUCHSANWEISUNG MANUEL D UTILISATION OPERATING MANUAL GEBRUIKSAANWIJZING 6 26 46 66 CL 1630...

Page 2: ...r Reichweite von Kindern halten L Nicht selbst reparieren 3 S CURIT G N RALE Par mesure de s curit consulter attentivement ce manuel d instructions Les personnes qui ne sont pas familiaris es avec ce...

Page 3: ...extension cord K Keep out of the reach of children L Do not repair 1 VEILIGHEID ALGEMEEN Bestudeer voor de veiligheid deze gebruiksaanwij zing zorgvuldig Personen die met de gebruiks aanwijzing niet v...

Page 4: ...ss Luftabzug Wasserstopp ableitung Luftableitungsschlauch Verbindungsst ck zur Befestigung ber dem Ableitungsschlauch Fernbedienung A B C 4 E F G H I J K 1 LESEN SIE ZUERST DIE BEDIENUNGSANLEITUNG 2 W...

Page 5: ...bedienen und problemlos an einer anderen Stelle aufstellen Sie haben ein Qualit tsprodukt gekauft an dem Sie noch viele Jahre Freude haben werden wenn Sie das Klimager t auf sichere und sachgem e Wei...

Page 6: ...Haushaltsverh ltnissen in Wohnr umen K chen und in Garagen verwendet werden G WICHTIG Benutzen Sie das Ger t auf keinen Fall mehr wenn das Kabel oder der Stecker besch digt sind Klemmen Sie das Kabel...

Page 7: ...Ger ts ob die Netzspannung mit den Angaben auf dem Typenschild bereinstimmt Steckdose und Stromanschluss f r dieses Ger t geeignet sind der Stecker des Ger ts richtig in die Steckdose passt das Ger t...

Page 8: ...l an Sollte keine geeig nete Schuko Steckdose zur Verf gung stehen dann lassen Sie diese von einem Elektro Fachmann anlegen Aus Sicherheitsgr nden bitten wir um u erste Vorsicht mit Kindern in der unm...

Page 9: ...r geisti gen F higkeiten oder einem Mangel an Erfahrung und Wissen verwendet werden wenn sie in die sichere Nutzung des Ger ts eingewiesen wurden und die damit einher gehenden Gefahren verstanden habe...

Page 10: ...tellecks vermieden wird was aufgrund der m glichen Entz ndung des K ltemittels durch elektrische Heizger te fen oder eine andere Entz ndungsquelle andernfalls zu einer Brand oder Explosionsgefahr f hr...

Page 11: ...icher dass die Bedingungen in dem Bereich durch die Kontrolle von entflammbarem Material gesichert wurden 1 4 Pr fung auf K ltemittel Der Bereich ist mit einem entsprechenden K ltemitteldetektor vor u...

Page 12: ...Dies ist dem Besitzer des Ger ts zu melden damit alle Parteien dar ber in Kenntnis gesetzt werden k nnen Die anf nglichen Sicherheitspr fungen m ssen folgende Punkte umfassen Die Kondensatoren sind e...

Page 13: ...entfernen l schen Sollte ein K ltemittelleck festgestellt werden das L tarbeiten erfordert so ist das K ltemittel aus dem System zu lassen oder in einem vom Leck entfernten Teil des Systems mittels Ab...

Page 14: ...er Flasche auch nicht vor bergehend l Wenn die Flaschen ordnungsgem bef llt wurden und der Vorgang abgeschlossen ist stellen Sie sicher dass die Flaschen und das Ger t umgehend vom Betriebsort entfern...

Page 15: ...RSICHT Schlie en Sie den Raum in dem Sie das Ger t benutzen niemals v llig luftdicht ab Damit verhindern Sie Unterdruck in diesem Raum Negative Druck Unterdruck kann den siche ren Betrieb von Durchlau...

Page 16: ...e Schl uche keine Knicks oder scharfe Kurven enthalten Damit das Ergebnis optimal ist m ssen die Luftschl uche w hrend des Betriebs des Klimager ts k rzer als 1 Meter sein C BEDIENUNG 1 2 3 4 5 6 7 8...

Page 17: ...e Temperatur auch wirklich erreicht werden kann h ngt von den Umgebungsbedingungen ab Es ist normal dass die Zimmertemperatur ber der set temp bleibt M glicherweise ist der Raum zu warm ENTFEUCHTEN Mi...

Page 18: ...n das Ger t laufen soll Wenn Sie beispielsweise die Schaltuhr auf 2 einstellen schaltet sich das Ger t nach zwei Stunden automatisch ein G ANMERKUNGEN Zur Verl ngerung der Lebensdauer des Kompressors...

Page 19: ...nn der Wasserbeh lter voll ist leuchtet die Lampe auf und die Meldung E2 erscheint im Display Die Klimaanlage schaltet sich dann auto matisch aus Zum Entleeren des Wasserbeh lters gehen Sie folgenderm...

Page 20: ...etzstecker bevor Sie das Ger t oder den Filter reinigen Das Geh use mit einem feuchten Tuch reinigen Verwenden Sie keine aggressiven Chemikalien Benzin L sungsmittel oder andere Reinigungsmittel Anwei...

Page 21: ...Innenseite des Ger ts erzeugt Dies ist ganz normal Der Kompressor funktioniert nicht Der Hitzeschutz ist m glich aktiviert worden Warten Sie 3 Minuten bis die Temperatur gesunken ist und schalten Sie...

Page 22: ...i auftritt wie etwa der Filter fallen nicht unter die Garantie 5 Die Garantie gilt nur bei Vorlage der mit dem Datum versehenen Originalrechnung und vorausgesetzt es wurden keine nderungen am Produkt...

Page 23: ...ergenommen werden Dieses Ger t enth lt die in der obigen Tabelle aufgef hrte Menge des K ltemittels R290 Lassen Sie das R290 nicht in die Atmosph re entweichen R290 ist ein fluo riertes Treibhausgas m...

Page 24: ...Filtre air Entr e d air vacuation d air Bouchon de drainage Tuyau d vacuation Adaptateur ext rieur 2x fixer sur le tuyau T l commande A B C 4 E F G H I J K 1 LISEZ PR ALABLEMENT LE MANUEL D UTILISATIO...

Page 25: ...seur roulant est tr s facile utiliser et d placer Vous venez d acqu rir un produit de qualit dont vous pourrez profiter pendant de longues ann es condition de l utiliser de fa on ad quate C est pourqu...

Page 26: ...onditions domestiques normales et en int rieur dans un s jour une cuisine ou un garage G IMPORTANT N utilisez jamais l appareil avec un cordon ou une fiche lectrique endommag Ne serrez jamais le cordo...

Page 27: ...signal tique la prise et l approvisionnement en courant sont bien adapt s l appareil la fiche lectrique rentre bien dans la prise de contact l appareil est bien pos sur une surface plane et stable Si...

Page 28: ...rouvent pr s de l appareil Si une ventuelle r paration est n cessaire en dehors des activit s d entretien faites la ex cuter par un technicien agr ou par votre distributeur Dans le cas contraire vous...

Page 29: ...age et de l entretien de l appareil sauf s ils sont encadr s G ATTENTION Ne jamais utiliser l appareil dans une pi ce ferm e herm tiquement sous risque de cr er une sous pression ce qui peut perturber...

Page 30: ...uites de produit r frig rant ce qui entra ne un risque d incendie ou d explosion en raison de l inflammation du fluide r frig rant provoqu par des appa reils de chauffage lectrique des po les ou d aut...

Page 31: ...e avec un d tecteur de fluide frigorig ne appropri avant et pendant l activit de mani re s assurer que le technicien soit conscient des atmosph res potentiellement inflammables Veillez ce que l quipem...

Page 32: ...ue d tincelles Qu il n y ait aucun composant lectrique visible et c blage expos pendant le chargement la r cup ration ou la purge du syst me Qu il y ait continuellement une liaison la terre 2 R PARATI...

Page 33: ...frigorifique pour effectuer des r parations ou d autres fins des m thodes conventionnelles doivent tre utilis es Cependant il est important que la meilleure pratique soit respect e puisque l inflamma...

Page 34: ...ant qu il a t mis hors service et vid de son r frig rant L tiquette doit tre dat e et sign e Veillez ce qu il y ait des tiquettes sur l quipement indiquant que l quipement contient du r frig rant infl...

Page 35: ...environnement humide Pour une bonne circulation de l air gardez un espace minimum de 50 cm autour de l appareil Brancher l l ment de raccordement et le tuyau d vacuation l arri re de l appareil sur l...

Page 36: ...era en mode climatisation Si la temp rature ambiante est inf rieure 25 C l appareil fonctionnera en mode ventilation Avec la touche vous pouvez r gler la fonction souhait e Appuyez plusieurs fois sur...

Page 37: ...sur cette fonction vous avez les possibilit s suivantes Avec la touche vous pouvez r gler la vitesse de ventilation Appuyez plusieurs fois sur la touche pour faire d filer les diff rentes vitesses de...

Page 38: ...e Lorsque la temp rature ambiante remonte audessus de la valeur r gl e le refroidissement reprend COMMANDE DISTANCE A Bouton marche arr t B Boutons de r glage thermostat C Bouton de r glage de la ven...

Page 39: ...ume et l appareil s affiche E2 sur l cran Le climatiseur s arr te alors automatiquement Pour vider le r servoir d eau proc dez comme suit Ne d placez pas l appareil Des mouvements brusques peuvent pro...

Page 40: ...Pour le nettoyage r gulier de l ext rieur de l appareil utilisez exclusivement un chiffon doux et humide Pour l entretien des filtres voir chapitre D Filtre air G REMARQUE N utilisez jamais l apparei...

Page 41: ...issement qui coule l int rieur de l appareil C est normal Le compresseur ne fonctionne pas Protection de surchauffage actionn e Patienter 3 minutes jusqu ce que la temp rature ait baiss et rallumer l...

Page 42: ...de l acheteur 8 Tout d g t caus par l utilisation du climatiseur sans filtre ou avec un filtre d une autre marque que Tectro n est pas couvert par la garantie Pour viter des d penses inutiles nous vo...

Page 43: ...tilateur 2 Max niveau de puissance sonore sound power level sound pressure level dB A 65 55 59 8 Dimensions l x h x p mm 330 x 680 x 280 Poids kg 18 Unit protection IP 20 Commande distance oui Conform...

Page 44: ...Caster Air filter Air inlet vent Exhaust hose connector Drain plug Exhaust hose Adaptor to fit over the exhaust hose Remote control A B C 4 E F G H I J K 1 READ THE DIRECTIONS FOR USE FIRST 4 44 2 IN...

Page 45: ...obile air conditioner is extremely easy to operate and move You have acquired a high quality product that will provide you with many years of pleasure on condition that you use it responsibly Reading...

Page 46: ...ged power cord plug cabinet or control panel Never trap the power cord or allow it to come into contact with sharp edges The installation must be completely in accordance with local regulations ordina...

Page 47: ...it Never cover the air inlets and outlets Empty the water reservoir through the water drain before moving it Never allow the device to come into con tact with chemicals Do not insert objects into the...

Page 48: ...or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children sho...

Page 49: ...er than those recommended by the manufacturing com pany The appliance must be placed in an area without any continuously sources of igni tion for example open flames gas or elec trical appliances in o...

Page 50: ...a room with a floor area larger than 4 m2 The appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specified for operation INSTRUCTIONS FOR REPAIRIN...

Page 51: ...ct specification At all times the manufacturer s maintenance and service guidelines shall be followed lf in doubt consult the manufacturer s technical department for assistance The following checks sh...

Page 52: ...for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need recalibration Detection equi...

Page 53: ...s before recovery takes place i Start the recovery machine and operate in accordance with manufacturer s instructions j Do not overfill cylinders No more than 80 volume liquid charge k Do not exceed t...

Page 54: ...ositioned upright and on a level surface Do not operate the unit inside the bathroom shower or in any other very humid environment Please keep a distance of 50 cm between the unit and the wall or othe...

Page 55: ...13 Low fan speed indicator 14 Timer setting indicator 15 Remote control receiver Insert the plug into the wall outlet Press the button to switch on the air conditioner If the ambient temperature is hi...

Page 56: ...ntire length The air conditioner will now de humidify as long as the room temperature is above the set value The device will be unable to de humidify if the room temperature drops below the set value...

Page 57: ...combination with the control panel Aim the front end of the remote control at the control panel The maximum operating distance from the air conditioner is approximately 5 metres Place 2 pieces of 2xAA...

Page 58: ...ppropriate tray on the floor underneath the drain hole Remove the drain knob and rubber plug 8 from the drain tube and let the water run out 0 8 litres Replace the rubber plug 8 and the drain knob and...

Page 59: ...petrol detergents or other cleansing solutions For maintenance of the filters refer to Chapter D Air Filter G NOTE Never use the air conditioner without screenfilter H STORAGE Empty the internal wate...

Page 60: ...aused by refri gerant circulating inside the unit This is normal The compressor does not work Overheat protection probably activated Wait 3 minutes until the tem perature has decreased and turn on the...

Page 61: ...olved during the transportation of the air conditioner or air conditioner components shall always be for the account of the purchaser 8 Damage caused by not using suitable filters is not covered by th...

Page 62: ...t range C 16 31 Fan speeds 2 Max Sound power level sound pressure level dB A 65 55 59 8 Dimensions w x h x d mm 330 x 680 x 280 Weight kg 18 Unit protection IP 20 Remote control Yes Conform EN 14511 M...

Page 63: ...63 4...

Page 64: ...ADPLEEG BIJ TWIJFEL UW DEALER 1 64 Bedieningspaneel Luchtuitlaat Handvat Wiel Luchtfilter Luchtinlaat Luchtafvoer Waterstop afvoer Luchtafvoerslang Verbindingsstuk 2x om over de afvoerslang te plaatse...

Page 65: ...e verrijdbare airconditioner is uiterst gemakkelijk te bedienen en te verplaatsen U heeft een kwaliteitsproduct aangeschaft waar u nog vele jaren plezier van zult hebben mits u de airconditioner veran...

Page 66: ...huishoudelijke omstandighe den G BELANGRIJK Gebruik het apparaat nooit met een beschadigd snoer of stekker Klem het snoer nooit af en voorkom contact met scherpe kanten De installatie moet volledig in...

Page 67: ...tabiele en vlakke ondergrond staat Laat de elektrische installatie controleren door een erkend vakman als u er niet zeker van bent dat alles in orde is De airconditioner is een veilig apparaat Het is...

Page 68: ...ig onderhoud om altijd uitvoe ren door een erkend servicemonteur of uw leverancier anders kan dit leiden tot het vervallen van de garantie Haal altijd de stekker uit het stopcontact als het apparaat n...

Page 69: ...einiging en onderhoud dient niet te wor den uitgevoerd door kinderen waarop geen toezicht wordt gehouden G LET OP De ruimte waarin dit apparaat wordt gebruikt nooit volledig luchtdicht afsluiten Dit v...

Page 70: ...erd gebruikt of bewaard wordt in een niet geventileerde ruimte moet deze ruimte geschikt zijn om de ophoping van koelmiddel te voorkomen Een risico op brand of een explosie kan het gevolg zijn vanwege...

Page 71: ...ebracht worden van het werk dat uitgevoerd wordt Werken in besloten ruimtes zal vermeden worden De omgeving rond de werken zal afgezet worden Verzeker dat de toestand in de ruimte veilig is en vrij is...

Page 72: ...len Indien er een fout aanwezig is die de veiligheid in het gedrang kan brengen zal er geen voeding op het circuit aangesloten worden tot wanneer dit probleem opgelost is Als de fout niet onmiddellijk...

Page 73: ...Vloeistoffen voor lekdetectie zijn geschikt voor gebruik voor de meeste koelmiddelen maar het gebruik van detergenten die chloor bevatten zal vermeden worden omdat het chloor kan reageren met het koe...

Page 74: ...ijderd kan worden h Verzeker dat de fles op de weegschaal staat v r aanvang van de recuperatie i Start de recuperatiemachine en bedien deze volgens de instructies van de fabrikant j Overvul de flessen...

Page 75: ...an uw airconditioner moet deze minimaal 2 uur rechtop hebben gestaan De airconditioner is verplaatsbaar en kan gemakkelijk ergens anders worden geplaatst Let daarbij op het volgende Zorg dat het appar...

Page 76: ...C zal het apparaat gaan koelen Wanneer de kamertemperatuur lager is dan 25 C zal het apparaat enkel ventileren Met de toets kunt u de gewenste functie instellen Door op de toets te drukken verspringt...

Page 77: ...eze functie ingesteld is kunt u de volgende handelingen verrichten Met de toets kunt u de gewenste ventilatorsnelheid instellen Door op de toets te drukken verspringt de ventilatorsnelheid als volgt H...

Page 78: ...e afstandsbediening op het bedieningspaneel De maximale afstand tot de airconditioner is ca 5 mtr Plaats voor gebruik 1 CR 2025 3V mee geleverd batterijen D LUCHTFILTER De airconditioner is uitgerust...

Page 79: ...r normale condities het con denswater via de luchtafvoerslang afgevoerd ONTVOCHTIGEN Als het apparaat vrijwel uitsluitend als ontvochtiger wordt gebruikt breng dan de luchtafvoerslang 9 niet aan en la...

Page 80: ...waarde Stel een andere temperatuur in Het apparaat is lawaaiig Apparaat staat op een onef fen ondergrond Zet het apparaat op een effen ondergrond minder trilling Het geluid wordt veroorzaakt door het...

Page 81: ...anwijzing of door verwaarlozing 7 De verzendkosten en het risico van het opsturen van de airconditioner of onder delen daarvan komen altijd voor rekening van de koper 8 Schade veroorzaakt door het nie...

Page 82: ...ilatorsnelheden 2 Max geluidsniveau sound power level sound pressure level dB A 65 55 59 8 Afmetingen b x h x d mm 330 x 680 x 280 Gewicht kg 18 Beschermingsklasse IP 20 Afstandsbediening Ja Conform E...

Page 83: ...83 1...

Page 84: ...numaras n www qlima com www Qlima com Distributed in Europe by PVG Holding B V D Ben tigen Sie weitere Informationen oder treten Probleme auf besuchen Sie bitte unsere Website www pvg eu oder setzen S...

Reviews: