VRT300 SERIES

 

 

 
 

 

 

 

VRT300 and VRT300 U 

 

 

 

 

STEP

 

 

PRESS

 

 

EFFECT

 

 

PRESS

 

 

NOTES

 

 

 

 
 

 

 

 
 

Programming start

 

 

 
 

Keep pressing for 5 seconds until the ON 

PRG LED switches ON. 

 

 

 
 

 

 

 
 

Programming 

“%In”

 

 

 

Set the maximum current variation allowed as a 

percentage (5-10-20-30%) of the In. rated 

value. 

 

Default 5% 

 

 

 

 

Going to the 

"start 

d."

 programming step 

 

Start delay: fan start time during which no 

alarm is generated 

 

 

 
 

 

 

 

Selection of the time in seconds 

"

start d."

 

 

 

Select the desired time                       

(5-10-20-30 sec.) 

 

Default 5 

 

 

 

 

 

 

Going to the 

"trip d."

 

programming step 

 

 

Trip delay: time during which the 

alarm persists, necessary  

for signalling 

 

 

 
 

 

 

 

Selection of the time in seconds  

“trip d.”

 

 

 

Select the desired time (5-10-

20-30 sec.) 

 

Default 5 

 

 

 
 
 
 

 

 

 
 
 

 

Motor start 

for automatic calibration 

CAL LED ON 

 

 

To perform the "automatic calibration" all motors 

must be connected as per final configuration. 

At the START the motors are 

switched ON for 60 seconds, the 

CAL LED flashes and LEDs 0-5-10-

20-30 light up in sequence. 

When the calibration is completed, the 

control unit resets and goes  

into REMOTE mode 

 

 

 
N.B.: any connection or programming errors might cause fan malfunctions. 
 

 

 
 
        ATTENTION:  
 

We recommend you check the control unit before starting the device. 
  
The default parameters set by TECSYSTEM might not suit your requirements.    
  

Programming the device is the end user’s responsibility: the set alarm thresholds and the enabled functions 
described in this manual must be checked (by a specialized technician) referring them to the application and 
system characteristics on which the control unit is installed.

 

PROGRAMMING  

Summary of Contents for VRT300 Series

Page 1: ...ISO9001 2008 certified quality system http www tecsystem it R 1 0 16 09 13 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 VRT300...

Page 2: ...NUAL IS VALID AND COMPLETE FOR THE VRT300 AND VRT300 U VERSIONS PAGE 1 SAFETY REQUIREMENTS 3 2 ACCESSORIES 4 3 TECHNICAL SPECIFICATIONS 5 4 FRONT PANEL 7 5 INSTALLATION 8 6 ELECTRICAL CONNECTIONS 9 VR...

Page 3: ...0 and never touch with wet or humid hands during storms If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cle...

Page 4: ...3 2 Supply and relay terminals 3 poles pitch 5 Code 2PL0367 1 motor line terminal 6 poles pitch 5 Code 2PL0372 1MN0030 REV 2 The above terminals are optional according to the configuration purchased A...

Page 5: ...max Connections on extractable terminal blocks OUTPUTS 1 fault sensor or operating failure FAULT relay SPDT Output relay with 5A 250Vac res COS 1 contacts 3 M1 M2 M3 outputs 250Vac max 10 5A max 50 6...

Page 6: ...C Humidity 90 non condensing Housing NORYL 94 _V0 Absorption 4VA max Electronic protection only on customer s request Polycarbonate IP65 front DISPLAY AND DATA MANAGEMENT LED s alarm undercurrent over...

Page 7: ...red 15 M1 motor in over current LED red 5 M3 motor in under current LED yellow 16 Current variation LED yellow 6 M2 motor in under current LED yellow 17 Fans local management LED red 7 Fixing block 18...

Page 8: ...eet 2 1 3 1MN0063 REV 0 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0008 REV 0 1 Control unit 3 Fixing screw...

Page 9: ...signal 2 Remote enabling contact ENABLE 5 Fan line supply 250Vac 10 15 amp max 50 60Hz 3 Control unit supply 230 Vac 10 50 60 Hz 4VA Note with the power to the unit ON the FAULT relay switches contact...

Page 10: ...AULT relay fault signal 2 Remote enabling contact ENABLE 5 Fan line supply 250Vac 10 15 amp max 50 60Hz 3 Control unit supply 12Vac dc 10 4VA Note with the power to the unit ON the FAULT relay switche...

Page 11: ...W TO CHECK THE ALARM STATUS Running LED OFF no ventilation activation control Running LED ON REMOTE or LOCAL ventilation activation Over and under current LEDs OFF motor operating correctly Over curre...

Page 12: ...lt 5 7 Motor start for automatic calibration CAL LED ON To perform the automatic calibration all motors must be connected as per final configuration At the START the motors are switched ON for 60 seco...

Page 13: ...M1 M2 M3 under current yellow LED ON Check the condition of the fans the cables and the supply Re program the device All the LEDs are flashing Memory error press RESET and repeat the programming proc...

Page 14: ...14 VRT300 SERIES TECHNICAL INFORMATION ufficiotecnico tecsystem it COMMERCIAL INFORMATION info tecsystem it PRODUCT INFORMATION CATALOGUES DOWNLOAD CONTROL UNIT MANUALS ACCESSORIES USEFUL CONTACTS...

Reviews: