UNIVERSAL BAR DIAM.80
Should it be necessary, modify the wiring or disconnect the connectors.
Using a 2.5mm slotted screwdriver, press the PUSH spring
under the connector. Move the socket connector slightly left
and right and pull.
Using a 2.5mm slotted screwdriver, press the internal
spring of the connector. Pull out the conductor.
Insert the socket con assembled casing (1) inside the plug connector (2) arranged on the bar.
1
2
POWER SUPPLY
Before connecting the ventilation bar to the power supply, always check that: the voltage and frequency parameters shown
on the fan label correspond to the values available on the system.
ENVIRONMENTAL CONDITIONS OF USE
Absence of fine dusts.
Absence of flammable or corrosive gases.
Relative humidity:90% non-condensing (for short periods).
N.B.: maximum temperature as prescribed by the IEC 60076-11 standard.
Installation in a marine environment is not recommended, unless after specific treatment of the metal parts.
NOTE: failure to comply with the assembly notes and possible use in extreme environmental conditions such as:
lengthy periods of standstill, high humidity, high temperatures, excessive dustiness and excessive vibrations, can
anticipate deterioration of the mechanical parts of the fans.
MAINTENANCE
In order to maintain the efficiency of the fans, clean them periodically (every 6 months) using only compressed air. Do not
use lubricants or greases of any kind.
Any prolonged standstill of the fan could cause malfunctions. Installation of the fans combined with the Tecsystem
thermometric control units avoids any prolonged shutdowns. By enabling the HFN function present in the Tecsystem
control units, it is possible to program fan activation cycles from 1 to 200 hours, recommended setting every 24 hours (for
further information on the HFN function, check the manual of the control unit purchased).
NOTE: Periodic maintenance and activation of the HFN will allow you to extend the efficiency of the fans.
Maintenance operations on the fans must be scheduled according to the environmental conditions in which they
operate.