13
NT935BH
PITCH
PRESS
EFFECT
PRESS
NOTES
1
Press and hold the PRG button until the display shows
SET PRG
2
Select PRG SET to proceed with programming or PRG 1
to load the default values
PRG 1 default data
3
The ALARM threshold for (CH 1-2-3) is displayed.
Set the desired threshold, the Alarm LED flashes
Default 90°C
4
The TRIP threshold for (CH 1-2-3) appears and the Trip
LED flashes.
5
Set the desired threshold
Default 119°C
6
The display shows FAN1 TRBH (CH 1-2-3)
the led Fan1 flashes.
Default YES
7
Select YES/NO
8
The display shows (CH4)
Enabling CH4
9
Select YES or NO
with YES the CH4 is enabled
with NO the CH4 is disabled
10
The ALARM threshold for (CH4) is displayed,
the Alarm led flashes.
If CH4=NO jump to step 16,
Default NO
11
Set the desired threshold
Default 120°C
12
The TRIP threshold for (CH4) is displayed,
The Trip led flashes
13
Set the desired threshold
Default 140°C
14
The display shows FAN2 for (CH4)
Default Yes
15
Select YES/NO
16
B-M is displayed
The FAN1 led flashes
Default B2-M3
17
Select the desired TRBH configuration,
TRBH notes on page 17
TRBH:
B1-M1
B1-M2
B1-M3
B2-M1
B2-M2
B2-M3
18
The display shows ON (CH 1-2-3)
the FAN1 led flashes
Default 70°C
19
Set the desired threshold FAN1 ON
20
The display shows ON (CH4)
the FAN 2 LED flashes
Default 45°C
21
Set the desired threshold FAN2 ON
If FAN 2 NO is selected skip to
step 24
PROGRAMMING
NT935BH D