WARRANTY CONDITIONS 

 

TROUBLESHOOTING 

 

 

CAUSES AND SOLUTIONS

 

The control unit does not switch on and the supply 
to terminals 40-42 is correct. 

Check that: the connector is correctly inserted into its housing, the wires 
are  tightened,  there  is  no  evidence  of  burning  on  the  connectors. 
Disconnect the power supply, carry out the above and reconnect. 

CH4 is in FAULT because of FOC  
(only the 3 Pt100 sensors are connected) 

Programming  error  of  the  CH4  /  YES  control  unit. 

Check  and  repeat 

programming as per page 13-14, select CH4 / NO.

 

One of the three/four channels is in FAULT due 
to FOC/FCC 

Check  the  connections  of  the  Pt100  sensors,  check  the  instructions 
given in the paragraphs: 

measurement signal transfer and temperature 

sensor diagnostics on page 14-15.

 

When turning on, the display shows 

“ECH” 

Strong  interference  damaged  the  stored  data.  See  the  paragraph 
Programmed data diagnostics on page 16. 

All the Pt100 sensors are in FCC. 

Incorrect  sensor  connection,  the  terminal  block  has  been  inserted 
upside down. 

Check the connections and the terminal board.

 

The temperature shown by one or more channels 
is wrong. 

Contact the 

TECSYSTEM

 Technical Department. 

Sudden trip of the main switch. The temperature 
is  on  standard  levels.  Just  one  channel  has 
caused the trip. 

Check  the  temperatures  recorded  in  T-MAX,  check  the  instructions 
given in the paragraphs: 

measurement signal transfer and temperature 

sensor diagnostics on page 16. Activate the FCD function.

 

FCD warning  

See the FCD function on page 19. 

 
During  the  operation  of  the  web  server  it  is  not 
possible to display the date and time and also the 
graphics screen does not work.   

 

In the 

Access point

 mode select settings/Options and enter the date 

and time in the 

Set data/time (AP mode)

 box 

In 

Station

 mode, select settings/Networking and enter time.google.com 

in the 

Server NTP

 box

  

The web server has been set in Access Point 
mode but the network cannot be identified. 
 

 
With the control unit off, keep the access point button pressed, then 
power the device and release the button after approximately 5 
seconds. The TECSYSTEM network (S/N + YEAR) will appear and 
connect to the network using the TECSYSTEM password. Open your 
browser and type in the address 192.168.8.8 use the web server bar 
to enter the Settings page, press the Network setting button and 
check: the ACCESS POINT selection, the settings SSID and 
Password, press save.     
 

The web server has been set in Station mode 
but the web server cannot be accessed. 

 
With the aid of a device with a Wi-Fi connection (PC, Smartphone or 
Tablet) with the control unit off, keep the access point button pressed, 
then power the device, and release the key after approximately 5 
seconds. Launch the search for the Wi-Fi network from your device. 
The TECSYSTEM network will appear (S/N + YEAR), connect to the 
network using the TECSYSTEM password. Open your browser and 
type in the address 192.168.8.8, use the web server bar to enter the 
Settings, page, press the Network setting button and check:  
STATION selection, settings: IP 

– GATEWAY -SUBNET MASK – NET 

WORK SSID 

– PASSWORD, press Save.     

Contact the TECSYSTEM Technical Department if the problem persists.

 

 

 

 

Summary of Contents for NT935 WS

Page 1: ...ith the ISO9001 certified quality system http www tecsystem it R 1 3 26 11 20 Translations of the original instructions INSTRUCTION MANUAL NT935 WS TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fa...

Page 2: ...35 WS PROGRAMMING NOTES 14 TEMPERATURE SENSORS 15 MEASUREMENT SIGNAL TRANSFER TEMPERATURE SENSOR DIAGNOSTICS 16 VOTING FUNCTION PROGRAMMED DATA DIAGNOSTICS TEMPERATURE DIAGNOSTICS COOLING FAN CONTROL...

Page 3: ...2 TECSYSTEM WEB SERVER 21 WEB SERVER MANAGEMENT BAR 22 HOME SCREEN SETTINGS SCREEN 23 NETWORK SETTINGS 24 OPTIONS 25 GRAPHICS SCREEN 26 EVENTS SCREEN 27 GRAPHIC VIEW NOTES 28 EXPORT NOTES CSV FILE PIN...

Page 4: ...netrates the control unit disconnect immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit using a dry cloth without any solvent or detergent a...

Page 5: ...orque 0 5Nm 1 relay terminal 12 poles pitch 5 Code 2PL0361 Screw tightening torque 0 5Nm 1 Pt100 sensors terminal 12 poles pitch 3 81 Code 2PL0420 Screws tightening torque 0 25Nm 1 external Wi Fi SMA...

Page 6: ...s FAN 1 and FAN 2 SPST Output relays with 10A 250Vca res COS 1 contacts Wi Fi Connection protocol 802 11 b g n frequency 2 4 GHz with removable external antenna Max 100m in open field DIMENSIONS 100 x...

Page 7: ...l 4 2 ON OFF thresholds for FAN 1 and FAN 2 Sensor diagnostics Fcc Foc Fcd Data memory diagnostics Ech Access to programming through front keyboard Automatic exit from programming display and and test...

Page 8: ...LED 5 FAULT red LED 16 3 digit channel display 6 FAN 1 yellow LED 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode selection key 19 Auto mode selecti...

Page 9: ...und in the measurement circuit The temperature values displayed might be incorrect Return the control unit to TECSYSTEM for repairs 4 Pt Err This message appears when it is detected that one or more P...

Page 10: ...ly after suitably fixing the device 1 Control unit 2 Panel hole dimensions 0 8 mm tolerance 3 Identification label 1 Control unit 3 Fixing screw 2 Fixing blocks 4 Cross head screwdriver 1X100mm MOUNTI...

Page 11: ...point key 2 Power supply 85 260Vac dc 50 60Hz 5 Antenna and Wi Fi connector 3 Relays FAN2 FAN1 ALARM TRIP FAULT 1MN0095 REV 0 Output relay with 10A 250Vac res COS 1 contacts COS 1 STOP SYSTEM ALARM C...

Page 12: ...FAULT contact programmed in failsafe mode default YES opens 11 12 when the equipment is supplied only if the unit detects no fault on switching on and stays in this condition until one of the followi...

Page 13: ...INT If INT is selected read function notes page 17 8 CH4 is displayed CH4 enabling 9 Select YES or NO with YES CH4 is enabled with NO CH4 is disabled 10 The ALARM threshold for CH4 is displayed the Al...

Page 14: ...ect YES or NO Default YES 36 END is displayed End of programming 37 Press ENT to save the set data and exit programming Err incorrect programming of the LED values note 6 38 Return to step 1 PROGRAMMI...

Page 15: ...mm 4 The cable screening must be grounded only with a termination preferably on the unit side 5 The sensors signal transfer cable must not be near electrical cables either low or medium high voltage 6...

Page 16: ...emperature values recorded on the monitored CH1 CH2 CH3 channels and enables the switching of the TRIP disconnect contact only if the TRIP threshold has been exceeded on at least two channels over the...

Page 17: ...ration and their control apparatus periodically By setting NO this function is inhibited To enable the HFN function read the programming section on pages 13 14 INTELLIFAN FUNCTION What it is used for...

Page 18: ...imits are reached preset temperature or for device s power supply lack FAULT Setting YES Fail safe the contact 11 12 is positioned as normally open switches closed when a fault condition is identified...

Page 19: ...signal transfer on page 15 Identification of a sensor fault or faulty connection In case of a faulty connection or sensor fault a quick positive or negative variation in temperature might occur leadin...

Page 20: ...l network key TECSYSTEM in the network key window repeat the operation in the network key confirmation window Click on CONNECT Once the connection is established your device will indicate Connected TE...

Page 21: ...ice will follow a chronological order but will not have the date time data available Accessing the Options page it will be possible to set the date time data manually see page 24 NOTE in the Access po...

Page 22: ...or fault indications activation of the F1 F2 ALARM TRIP alarms WEB SERVER MANAGEMENT BAR The web manager management bar allows the user to identify the cabin and to select the various screens The foll...

Page 23: ...g of the NT935 WS control unit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 As for the panel programming also for programming through WEB SERVER it is necessary to follow these rules AL ALARM TRIP FAN FAN OFF...

Page 24: ...erification 4 Subnet mask 7 Server NTP address automatic time and date update 1 Selection ACCESS POINT mode settings 8 Access Point SSID default TECSYSTEM network name modification 9 Password default...

Page 25: ...IN CODE settings and operation at page 28 Selection Duration in days months Selection Duration in days months 5 min 91 days 3 months 20 min 365 days 12 months 10 min 182 days 6 months 30 min 547 days...

Page 26: ...5 View key 3 Data availability DA yy mm dd Time hh mm ss 6 Export key VIEW button Pressing the VIEW button will update the chart according to the dates selected FROM TO FROM box It allows the user to...

Page 27: ...time clock set to last saved Reset date and time automatic from the last saving W02 Real time clock manually set Manual date and time setting W03 diagnostic button pressed the access point key has be...

Page 28: ...nce universal coordinated time Following the exporting of the CSV file recorded TEMPERATURE VALUE the last 300 recorded points will be contained in the file if there are less than 300 points in memory...

Page 29: ...s wrong Contact the TECSYSTEM Technical Department Sudden trip of the main switch The temperature is on standard levels Just one channel has caused the trip Check the temperatures recorded in T MAX ch...

Page 30: ...CONTACTS The product NT935 4 WS has born as a technical evolution of the NT935 WS model it maintains the main features of the NT935 WS increasing its programming flexibility 1 The 4 channels CH1 CH2 C...

Page 31: ...MASS OF THE EQUIPMENT 0 45 Kg INPUT SUPPLY 100 240 Vac Vdc 10 50 60 Hz 7 5VA max PROTECTION External switch or circuit breaker OUTPUTS RELAYS 5 relay output 10A 250Vac res COS 1 PORT Wifi Suitable for...