Technical data 

1. DISPLAY :  

5 digit, 0.56" (14.2 mm) variable intensity red sunlight readable 
(-19999 to 99999) 
 

2. POWER : 

AC Versions: 
AC Power: 85 to 250 VAC, 50/60 Hz, 21 VA 
Isolation: 2300 Vrms for 1 min. to all inputs and outputs. 
DC Versions: (Derate operating temperature to 40° C if three plug-in option 
cards are installed.) 
DC Power: 18 to 36 VDC, 13 W 
AC Power: 24 VAC, ± 10%, 50/60 Hz, 16 VA 
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working). 
Must use a Class 2 or SELV rated power supply 
 

3. ANNUNCIATORS : 

A - Programmable Display 
B - Programmable Display 
C - Programmable Display 
SP1 - Setpoint alarm 1 is active 
SP2 - Setpoint alarm 2 is active 
SP3 - Setpoint alarm 3 is active 
SP4 - Setpoint alarm 4 is active 
Units Label - Optional units label backlight 
 

4. KEYPAD : 

3 programmable function keys, 5 keys total 

 

5. A/D CONVERTER : 

16 bit resolution 

 
6. 

UPDATE RATES 

A/D conversion rate: Adjustable 5.3 to 105 readings/sec. 
Step response: (to within 99% of _nal readout value with digital _lter disabled) 

                         

 

Display update rate: adjustable 1 to 20 readings/sec. 
Setpoint output on/o_ delay time: 0 to 3275 sec. 
Analog output update rate: 0 to 10 sec 
Max./Min. capture delay time: 0 to 3275 sec. 
 

7. DISPLAY MESSAGES : 

“OLOL” - Appears when measurement e signal range. 
“ULUL” - Appears when measurement exceeds - signal range 
“. . . .” - Appears when display values  display range. 
“- . . .” - Appears when display values exceed - display range. 
 

8. SENSOR INPUTS : 

 
 
 

 
 
 
 
 
 
 
 

* After 20 minute warm-up. Accuracy is speci_ed in two ways: Accuracy over 
an 18 to 28°C and 10 to 75% RH environment; and accuracy over a 0 to 50°C 
and 0 to 85% RH (non-condensing environment). Accuracy over the 0 to 
50°C range includes the temperature coe_cient e_ect of the meter. 
 

9. EXCITATION POWER : 

Transmitter Power: 18 VDC, ±20%, unregulated, 70 mA max. per 
input channel. 
 

10. LOW FREQUENCY NOISE REJECTION : 

Normal Mode: (digital _lter o_) 
 
 
 
 
 
 
 
 
 
 
 

*

Note: 19.8 Hz Input Rate provides best rate  

performance and simultaneous 50/60 Hz rejection. 
Common Mode: >100 dB @ 50/60 ±1 Hz (19.8 or 20 Input Rate) 

 
 
 
 
 
 
 
 
 
 
 
 

11. USER INPUTS :  

Three programmable user inputs 
Max. Continuous Input: 30 VDC 
Isolation To Sensor Input A Common: 500 Vrms for 1 min; 
Working Voltage: 50 V 
Isolation To Sensor Input B Common: Not isolated. 
 
 
 
 
 
 
Response Time: 20 msec. max. 
Logic State: Jumper selectable for sink/source logic 
 

12. TOTALIZER : 

Function: 
Time Base: second, minute, hour, or day 
Batch: Can accumulate (gate) input display from a user input 
Time Accuracy: 0.01% typical 
Decimal Point: 0 to 0.0000 
Scale Factor: 0.001 to 65.000 
Low Signal Cut-out: -19,999 to 99,999 
Total: 9 digits, display alternates between high order and low order readouts 
 

13. CUSTOM LINEARIZATION : 

Data Point Pairs: Selectable from 2 to 16 
Display Range: -19,999 to 99,999 
Decimal Point: 0 to 0.0000 
 

14. MEMORY :  

Nonvolatile memory retains all programmable parameters and display values. 
 

15. CERTIFICATIONS AND COMPLIANCES : SAFETY 

UL Recognized Component, File #E179259, UL6101A-1, CSA C22.2 No. 
1010-1 
Recognized to U.S. and Canadian requirements under the Component 
Recognition Program of Underwriters Laboratories, Inc. 
UL Listed, File #E137808, UL508, CSA C22.2 No. 14-M95 
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards 
Type 4X Enclosure rating (Face only), UL50 
IECEE CB Scheme Test Certi_cate #US/8843A/UL 
CB Scheme Test Report #04ME11209-20041018 
Issued by Underwriters Laboratories, Inc. 
IEC 61010-1, EN 61010-1: Safety requirements for electrical 
equipment for measurement, control, and laboratory use, Part 1. 
IP65 Enclosure rating (Face only), IEC 529 
IP20 Enclosure rating (Rear of unit), IEC 529 
Torque: 4.5 inch-lbs (0.51 N-m) max. 
 

15. 

CERTIFICATIONS AND COMPLIANCES (Cont’d) : 

ELECTROMAGNETIC COMPATIBILITY 

Emissions and Immunity to EN 61326: Electrical Equipment for 
Measurement, Control and Laboratory use. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Notes: 
1. Criterion A: Normal operation within speci_ed limits. 
2. Criterion B: Temporary loss of performance from which the unit selfrecovers. 
Refer to EMC Installation Guidelines section of the bulletin for additional 
information. 
 

16. ENVIRONMENTAL CONDITIONS : 

Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in 
option cards installed) 
Storage Temperature Range: -40 to 60°C 
Operating and Storage Humidity: 0 to 85% max. RH non-condensing 
Altitude: Up to 2000 meters 

 
17. CONNECTIONS :  

High compression cage-clamp terminal block 
Wire Strip Length: 0.3" (7.5 mm) 
Wire Gage: 30-14 AWG copper wire 
Torque: 4.5 inch-lbs (0.51 N-m) max. 

 
18. CONSTRUCTION :  

This unit is rated for NEMA 4X/IP65 outdoor use. 
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece 
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and 
mounting clip included. 

 
19. WEIGHT : 

10.4 oz. (295 g) 

 

 
 
 
 
 
 