Základní dokumentace modulů CP-1000
independently from Mosaic development environment.
2)
Due to possible higher interference on analog inputs we do not recommend to connect the
common wire of input switches to AGND clamp – use GND clamp on terminal C.
Parameters of relay outputs DO0 - DO1
Notation
DO0 – DO1
Number of outputs
1+1
Galvanic isolation
from internal circuits, among groups
Diagnostics
indication of closed output on module panel
Output type
electromechanical relay, non-protected output
Contact type
making contact
Switching voltage
max. 250 V, min. 5 V
Switching current
max. 3 A, min. 10 mA
Short time overload capacity of output
max. 4 A
Switch on period
typ. 10 ms
Switch off period
typ. 4 ms
Limit values for switching load
for resistance load
max. 3 A at 30 V DC or 230 V AC
for inductive load DC13
max. 1 A at 30 V DC
for inductive load AC15
max. 3 A at 230 V AC
Switching rate without load
max. 300 /min.
Switching rate with nominal load
max. 20 /min.
Mechanical lifetime
min. 5 000 000 cycles
Electric lifetime at max. load
for resistance load
min. 100 000 cycles
for inductive load DC13
min. 100 000 cycles
for inductive load AC15
min. 100 000 cycles
Short-circuit protection
no
Inductive load treatment
external - RC element, varistor, diode (DC)
Insulation voltage
between inputs and internal circuits
3750 V AC
between groups of outputs
3750 V AC
Parameters of analog inputs AI0 – AI3
1)
Number of inputs
4
Galvanic isolation from internal circuits
no
Diagnostics
overloaded input and disconnected or short-circuited
sensor indication in a status word
Common pole
minus
External power supply
no
Converter type
approximating
Numerical resolution
12 bits
Protection type
integrated over voltage protection
Filtration
low-pass filter
Internal calibration
no
Resistance temperature detectors
Pt1000, W
100
= 1.385
–90 to +270 °C
Pt1000, W
100
= 1.391
–90 to +270 °C
TXV 110 00
11