![Tecomat Foxtrot CP-1000 Manual Download Page 10](http://html1.mh-extra.com/html/tecomat/foxtrot-cp-1000/foxtrot-cp-1000_manual_1072617010.webp)
Základní dokumentace modulů CP-1000
1)
In indoor conditions (i.e. such conditions, where using of radio and TV sets can be supposed in a
distance of 10 m from the mentioned equipment), the product can cause radio disturbances. It might
be required in such cases that the user takes necessary measures to avoid this.
2)
Fc test according to ČSN EN 60068-2-6 (idt IEC 68-2-6:1995), 10 cycles in each axe.
1.3
SYSTEM PARAMETERS
Real time circuit (RTC)
yes
Memory of user program and tables
192 + 64 KB
EEPROM program backup memory
yes
DataBox - additional data memory (internal)
512 kB
Internal memory for project archiving
2 MB
Slot for MMC/SD card
yes
RAM and RTC back up
1)
without/with optional back-up battery
typ. 500 hours/typ. 20 000 hours
Cycle time for 1k of log. instructions
0.2 ms
Number of user registers
- remanent registers (from the total number)
64 kB
32 kB
Number of timers (IEC)
4096
Number of counters (IEC)
8192
Instruction length
2 ÷ 10 bytes
CPU series
K
Number of serial channels
2)
2
Ethernet interface 10/100 Mbps
1
TCL2 bus
1
CIB (Common Installation Bus)
2
3)
Integrated web server
yes
1)
Valid for the central unit without supply, when the supply is on, the back-up circuit is disconnected.
2)
CH1 serial interface is fitted with fixed RS-232 interface. CH2 serial interface is optional by means of
exchangeable sub-modules.
3)
The module contains an internal separation for CIB from power supply. If the input current of CIB units
is less then 1 A it is not necessary to use an external separation module BPS2-01M.
1.4
ELECTRICAL PARAMETERS
Parameters of binary inputs DI0 – DI3
1)
Number of inputs
4
Diagnostics
Indication of energized input on the module panel
Notation
DI0 – DI3
IN 230 V, HDO
Number of inputs in a group
4
1+1
Galvanic insulation from internal circuits
no
yes, each separate
Common wire of a group
2)
GND terminal
-
Input type
potential-free contact
230 V AC
Input voltage
for log.0 (UL)
max. 12 V DC
min. 2.3 V DC
max. 120 V AC
min. 0 V AC
for log.1 (UH)
min. 0 V DC
max. 1 V DC
min. 200 V AC
max. 250 V AC
Input current at log.1
typ. –1.7 mA
typ. 5 mA
Delay from log.0 to log.1
1 ms
10 ms
Delay from log.1 to log.0
1 ms
10 ms
1)
Inputs DI0 – DI3 can be used alternatively as analog inputs (AI0 – AI3). Inputs are configured
TXV 110 00
10