![TECOM ChallengerPlus Installation And Quick Programming Manual Download Page 24](http://html1.mh-extra.com/html/tecom/challengerplus/challengerplus_installation-and-quick-programming-manual_1072585024.webp)
18
Figure 7: Four-state monitored zone input circuits
Alternatively, the Challenger system can be configured to monitor zone inputs for
two states (sealed and unsealed). This is accomplished by using one EOL
resistor in each circuit, as shown in Figure 8 below.
Figure 8: Two-state monitored zone input circuits
Note:
When the system is used in two-state configuration, inputs can only report
sealed and unsealed states. This prohibits the use of input types that need to
detect short or open states. See the
ChallengerPlus Programming Manual
for
details.
Special zone input types
Zone inputs programmed as area control type inputs can also be used to turn
areas on and off (as opposed to entering a PIN on a keypad). These inputs do
not have areas assigned to them: their functions are determined by assigning an
alarm group to them.