22
Challenger10 Installation and Quick Programming Manual
Table 2: Install menu options and selected default values
Install menu option
Description
1. Input Database
Program all physical inputs on the control panel, DGP, or plug-in
expander, and inputs that are activated by macros.
The default values for inputs 1 to 16 are:
• Input type is set to type 2 Secure Alarm
• Report ID type is set to 25-140, General Alarm
• Siren event flag is selected
• Event flag 2 Secure Alarm is selected, and is mapped to relay 2
Strobe Output
2. Area Database
Program up to 99 areas. Areas determine how the system is
partitioned, and therefore provides the ability to limit users to
performing functions only in the areas relevant to their role.
The default values for areas are:
• Exit time is set to 60 seconds
• Entry time is set to 30 seconds
• Siren event flag is set to 1
3. RAS Database
Program the system’s remote arming stations (RASs). RASs provide
alarm system control, such as area arming or disarming; and provide
access control, such as unlocking a door for a user.
You may need to change the RAS’s default area LED assignments.
RAS 1 is programmed as an LCD RAS, to be polled, and is assigned
Alarm Group 2 (Master RAS).
4. DGP Database
Program any data gathering panels (DGPs) used to send information
to the control panel and to provide added access control functionality.
5. Alarm Groups
Program alarm groups to enable users, inputs, and arming stations to
control the system’s alarm control functionality.
6. Timers
Program the system’s timers if the default values are not suitable.
The default values for timers are:
• Each user category time is set to 0 minutes
• Access test time is set to 15 minutes
• Secure test time is set to 15 minutes
• Warning time is set to 5 minutes
• Delay holdup time is set to 60 seconds
• Suspicion time is set to 15 seconds
• Service time is set to 30 minutes
• Local alarm reminder time is set to 0 minutes
• Individual testmode time is set to 5 minutes
• Door unlock time is set to 5 seconds
• Tester event flag time is set to 15 seconds
• Siren time is set to 8 minutes
• Mains fail time is set to 0 minutes
• Card to code time is set to 8 seconds