CONNECTION
Circuit Diagram
FM50 NEMA 4X (IP65 Indoor Duty) with operators (115V, 230V, 1/4 - 1HP models)
NOTE :
1. Power switch, REV-0-FWD switch and potentiometer are only for NEMA 4X units with operator devices.
2. Power supply cable: #14 AWG (2.0mm
2
)
3. Motor cable: #16 AWG (1.25mm
2
)
4. Tightening torque value for terminals:
(1). Power/Motor cable (plug-in) terminal: 4.34in-lb (5kg-cm)
(2). Remote control wire: 3.47in-lb (4kg-cm)
(3). Outer cover (M4): 5.20in-lb (6kg-cm)
5. Input source: single-phase (L1, L2, ), make sure that it is connected to the appropriate power supply.
6. Output motor: three-phase ( , T1, T2, T3)
CAUTION
- Do not start or stop the AC drive using the main circuit power.
- NEMA 4X with operators: Always maintain REV-0-FWD switch at 0 position.This will ensure that the AC drive is stopped
before power up after power supply interruption. Otherwise, injury may result to personnel.
24
FLUXMASTER 50 INSTRUCTION MANUAL
Summary of Contents for FM50101-X
Page 1: ...www tecowestinghouse com Instruction Manual User Manual...
Page 18: ...External 24V Supply 18 FLUXMASTER 50 INSTRUCTION MANUAL...
Page 33: ...33 FLUXMASTER 50 INSTRUCTION MANUAL 2 6 Mounting Instructions...
Page 53: ...4 Troubleshooting Procedures 53 FLUXMASTER 50 INSTRUCTION MANUAL 4 1 Flow Chart...
Page 54: ...FLUXMASTER 50 INSTRUCTION MANUAL Continued 54...
Page 55: ...FLUXMASTER 50 INSTRUCTION MANUAL Error handling of fault indication of OC OL 55...
Page 56: ...Error handling of fault indication of OV LV 56 FLUXMASTER 50 INSTRUCTION MANUAL...
Page 57: ...57 FLUXMASTER 50 INSTRUCTION MANUAL 1 Motor inoperative...
Page 58: ...FLUXMASTER 50 INSTRUCTION MANUAL 58 2 Motor overheat...
Page 59: ...FLUXMASTER 50 INSTRUCTION MANUAL 3 Unstable motor operation 59...
Page 66: ...Notes 66 FLUXMASTER 50 INSTRUCTION MANUAL...