Chapter 4 Software index
4-26
C10 Reset mode
000: Reset is enable when RUN switch is in OFF position.
001: Reset is enable with RUN switch, either OFF or ON .
C10=000. Fault can not be reset, therefore inverter can not start. If the RUN switch is in ON position.
(
F4=001
)
C11 2nd acceleration time
(
s
)
: 00.1 – 999
C12 2nd deceleration time
(
s
)
: 00.1 – 999
C13 Fan control
000: Auto-run by inverter temperature
001: Run when inverter running
002: Always run.
003: Always stop.
1.) C13=000: The fan will auto run as sensing certain temperature in order to extend the life span
of the fan.
2.) C13=001: The fan runs as long as inverter is running.
3.) C13=002: The fan runs as long as power is supplied.
3.) C13=003: The fan does not run at any time.
C14:Control mode
Vector control or V/F control
C17: Max. output frequency (HZ)
= 50.0 –200Hz
C18: Output voltage ratio in max. frequency (%) = 00.0 – 100%
C19: Mid frequency (HZ)
= 00.1 – 200Hz
C20: Output voltage ratio in mid. frequency (%)
= 00.0 – 100%
C21: Min. output frequency (HZ)
= 00.1 – 200Hz
C22: Output voltage ratio in min. frequency (%)
= 00.0 – 100%
C17~C22 please
refer to C15 description
C15
:
Preset V/F patterns = 1 – 7
C15 = 007. Selects user-set v/f pattern by setting parameters C17~C22 .
As shown in diagram below. Care should be taken when this feature is used as incorrect
setting of these parameters will have a direct effect motor performance.