9
The TSCE-J1 leak Detector may also be used to: • Detect leaks in other systems and storage/recovery containers.
It will respond toALL halogenated(contains Chlorine of Fluorine) refrigerants. This includes, but is not limited
to: CFCs e.g.R12,R1 1 ,R500,R503 etc... e.g.R22,R123,R124,R502 etc... e.g.R134a,R404a,R125 etc... HCFCs HFCs
Blends such as AZ-50.HP62.MP39 etc...
• Detect Ethylene Oxide gas leaks in hospital sterilizing equipment(it will detect the halogenated carrier gas)
• Detect SF-6 in high voltage circuit breakers • Detect most pases that contain chlorine,Fluorine and
Bromine(halogen gases)
• Detect cleaning agents used in dry cleaning applications such as perchloroethyl
APPLICATIONS
MAINTENANCE
Proper maintenance of your Leak Detector is very important. Carefully following the instructions, outlined below,
will reduce performance problems and increase the life expectancy of the unit.
WARNING:TURN UNIT OFF BEFORE REPLACING THE SENSING TIP. FAILURE TO DO SO MAY RESULT IN A MILD
ELECTRICAL SHOCK!
Keep the sensing tip clean: Prevent dust, moisture and grease build-up by utilizing the provided tip protector.
Never use the unit without the protector in place.
Before using the unit,always inspect the tip and protector to see that they are free of dirt and/or grease.To clean:
1. 2.
Remove protector by grasping and pulling the tip off . Clean protector with shop towel and/or compressed air .
3. If the tip itself is dirty, it can be cleaned by immersing in a mild solvent, such as alcohol ,for a few seconds, and
then using compressed air and/or a shop towel to clean.
NOTE: Never use solvents such as gasoline, turpentine ,mineral spirits. etc°gas these will leave a detectable
residue and desensitize your unit .
Sensing tip replacement: the tip will eventually wear out and require replacement It is difficult to predict exactly
when this will occur since tip longevity is directly related to the conditions and frequency of use. The tip should
be replaced whenever the alarm sounds or becomes erratic ,in a clean ,pure ,air environment.
TO replace the tip: 1. Make sure the unit is OFF. 2. Remove the old tip by unscrewing counter-clockwise.
3. Use the supplied replacement tip ,located in the carrying case. Replace by screwing on clockwise.